Plan Review Details - Permit 17050701
Plan Review Stops For Permit 17050701
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2017-07-06 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-28 Cont ID  
Sent By jwitmer Date 2017-06-28 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 07:41 Sent To  
Notes
2017-06-28 08:25:362014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050701
 ADD: 480 HIBISCUS ST. SUITE # 116
 CONT: FLORIDA DEVELOPMENT
 TEL: 954-707-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. 28, 2017
 ACTION: BUILDING PROVISO/ HOLD ON ISSUANCE
  
 1) PLEASE PROVIDE DOCUMENTATION OF OWNERSHIP FOR THIS
 UNIT. THE CITY RECORDS ARE DIFFERENT FROM THE PERMIT
 APPLICATION AND THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE IS DIFFERENT FROM BOTH.
 PROVIDE DOCUMENTATION OF OWNERSHIP BEFORE PERMIT
 ISSUANCE. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1PERMITS/ REQUIRED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-19 Cont ID  
Sent By jwitmer Date 2017-05-19 Time 10:55 Rev Time 0.00
Received By jwitmer Date 2017-05-19 Time 07:23 Sent To  
Notes
2017-05-19 10:55:312014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050701
 ADD: 480 HIBISCUS ST. SUITE # 116
 CONT: FLORIDA DEVELOPMENT
 TEL: 954-707-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 19, 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE DOCUMENTATION OF OWNERSHIP FOR THIS
 UNIT. THE CITY RECORD ARE DIFFERENT FROM THE PERMIT
 APPLICATION AND THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE IS DIFFERENT FROM BOTH.
 PROVIDE DOCUMENTATION OF OWNERSHIP. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 105.1PERMITS/ REQUIRED.
  
  
 2) BOTH SETS OF THE ARCHITECTURAL SHEETS ARE MISSING
 THE ARCHITECTS SIGNATURE, DATE AND SEALED PLANS.
 61 G 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000. THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 SHALL APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD.
  
 3) SHEET A210:
 3A) PLEASE NOTE THIS IS CONSIDERED A CHANGE IN
 OCCUPANCY, WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-EXISTING BUILDING CODE CHAPTER 10, SECTION 1001.3.1
 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 3B) TYPE OF CONSTRUCTION IS LABELED III-B & ALLOWABLE
 HEIGHT OF 3 STORIES. PLEASE NOTE THIS TENANT SPACE IS
 LOCATED WITHIN A 10 STORY HIGH RISE, ON THE 2ND FLOOR
 AND ABOVE ALL UNITS BEING R2 OCCUPANCY. IN THE 2014
 FBC-B TABLE 503 INDICATES THIS BUILDING TO BE A MINIMUM
 BUILDING TYPE IB FOR 11 STORIES.
  
 3C) OCCUPANCY TYPE INDICATED FOR THE BAKERY IS A
 BUSINESS OCCUPANCY. THERE IS NO LIFE SAFETY PLAN
 PROVIDED. NOTED THERE IS A PROPOSED KITCHEN LAYOUT PLAN
 AND AN EQUIPMENT PLAN WITH PROPOSED FURNITURE LAYOUT
 WITH FURNITURE SCHEDULE, THE FURNITURE SCHEDULE HAS
 LEFT OUT THE BENCH SEATING AT THE MIRRORED WALL. WITH
 THE ADDITIONAL SEATING ALONE THE SEAT COUNT ALONE IS 56
 OCCUPANTS. WITH THIS OCCUPANT LOAD ALONE THIS TENANT
 SPACE IS AN A2 OCCUPANCY303.3.
  
 3D) PLEASE PROVIDE A LIFE SAFETY PLAN. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT AISLES
 EXIT ACCESS
 EXITS
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3E) WITH THE PLANS INDICATING A SEATING AREA OF 1,317
 SQ. FT. / 15= 88 OCCUPANTS A A2 OCCUPANCY, OVER 50
 OCCUPANTS AND AN SQUARE FOOT AREA OF 750 SQ. FT. FBC-B
 303.3.
  
 3F) SHEET A210 INDICATES THE DOORS AND DOOR SCHEDULE
 BUT DOES NOT INDICATE THE HARDWARE ON THE EXIT DOORS.
 PLEASE INDICATE COMPLIANCE WITH 2014 FBC-B 1008.1.10
 PANIC AND FIRE EXIT HARDWARE. PANIC HARDWARE REQUIRED
 WITH OCCUPANT LOAD OF 50 OR MORE.
  
 4) SHEET A211:
 4A) THIS SHEET SHOWS THE SEATING FLOOR PLAN BUT DOES
 NOT SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY
 CODE FOR;
  
 4A)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4A)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES. THIS WOULD ALSO INCLUDE
 EXTERIOR SEASONAL SEATING.
  
 4A)(3) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, BOOTHS AND SEASONAL SEATING.
  
 4A)(4)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4A)(4)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4B) EXIT PLEASE IDENTIFY WHICH DOORS ARE ACCESSIBLE
 EXITS (2) REQUIRED > THAN 50,
 ACCESS. CODE 06.4.1 PUBLIC ENTRANCES. IN ADDITION TO
 ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9,
 AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL
 COMPLY WITH 404.(MINIMUM OF 2 ENTRANCES).
  
 4C) IN THE ORIGINAL BUILDING DESIGN THE STAIRS TO THE
 MEZZANINE WENT UP TO A MID-LANDING AND RETURNED ON
 THEMSELVES. THE PLANS ARE SILENT IF THESE ARE A NEW
 STAIRCASE TO THE MEZZANINE LEVEL? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) SHEET A401 DOES NOT PROVIDE ANY DETAILS FOR REQUIRED
 ACCESSIBLE SIGNAGE. SEE ACCESSIBILITY CODE:
 5A) 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH
 VISUAL AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE
 SIGN WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 5B) 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 07:59 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 07:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 09:56 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 09:56 Sent To  
Notes
2017-06-16 09:56:58REVIEWED PER COMMENTS ONLY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 16:20 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 16:20 Sent To  
Notes
2017-05-23 16:27:41JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 PAGE E0.3
  
 NEED TO SHOW GROUNDING OF THE SERVICE FROM GUTTER
 LOADS ON PANEL "H" SHOW 50 KVA FOR "LA", 10 KVA FOR
 "LB"
 LOADS ON PANELS SHOWN ARE 102.7 KVA FOR "LA", AND 33.5
 KVA FOR "LB"
  
 PLEASE SHOW DETAILED LOAD CALCULATION FOR "H" PANEL
  
 NEED FAULT CURRENT CALCULATION FOR THE NEW TRANSFORMERS
 TA AND TC AND "H"
  
 PAGE E1.1
  
 NO FIXTURES SHOWN IN HALF OF THE UNIT, NEED CUT SHEETS
 ON FIXTURES IN ORDER TO CHECK
 COMPLIANCE WITH POWER ALLOWNACES

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-05 Cont ID  
Sent By pleduc Date 2017-07-05 Time   Rev Time 0.00
Received By pleduc Date 2017-07-03 Time 16:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-19 Time 11:45 Sent To  
Notes
2017-06-19 12:07:332ND REVIEW
  
 THE COMMENTS PROVIDED BY FIRE WERE NOT SPECIFICALLY
 ADDRESSED AND SHALL BE PROVIDED WITH THE REQUIRED
 PROVISIONS AND/OR CLARIFIED WITH CODE REFERENCES.
  
  
  
 1) SHEET A 210 - THERE ARE INCORRECT REFERENCES TO THE
 FLORIDA FIRE PREVENTION CODE EDITION; 2010.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 2) SHEET A 210 - THE DOOR SCHEDULE DOES NOT SHOW ANY
 HARDWARE AND/OR EXIT HARDWARE.
  
 PLEASE RECIEW AND CORRECT.
  
  
  
  
 3) SHEET A 210 - THE OCCUPANCY CLASSIFICATION IS NOTED
 AS BUSINESS; HOWEVER, A STORAGE, EMPLOYEE LOUNGE, A
 BUSINESS OFFICE, AND A BAKERY WITH SEATING OVER 50 IS
 INDICATED.
  
 PLEASE PROVIDE WHAT THE OCCUPANCY CLASSIFICATION IS AND
 WHETHER IT IS MIXED OR SEPARATED PER NFPA 101.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS FOLLOWS SHALL BE PERMITTED TO BE
 CONSIDERED PART OF THE PREDOMINANT OCCUPANCY AND SHALL
 BE SUBJECT TO THE PROVISIONS OF THE CODE THAT APPLY TO
 THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2)* NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY
 THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY NON-HAZARDOUS USES NECESSARY FOR
 TRANSACTING THE PRINCIPAL BUSINESS IN STORAGE AND
 INDUSTRIAL OCCUPANCIES NEED NOT BE SEPARATED FROM THE
 PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD PRODUCTS IN ACCORDANCE WITH SUBDIVISION
 6.2.2 NEED NOT BE SEPARATED BY FIRE-RESISTANT
 CONSTRUCTION FROM THE OCCUPANCIES TO WHICH THEY ARE
 ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE 508.2.5 OF THE FLORIDA BUILDING CODE
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
  
  
  
  
 4) THERE IS NO LIFE SAFETY PLAN SHEET PROVIDED.
  
 BASED ON WHAT OCCUPANCY CLASSIFICATION NOTED FOR # 3
 ABOVE, COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY
 SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS
 LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS,
 AND ALL FIRE SAFETY FEATURES AND EQUIPMENT.
  
 NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.11.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING.
 1.7.11.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
 1.7.11.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN.
  
  
  
  
 5) SHEET A 210 - A MEZZANINE IS INDICATED WITH ONLY ONE
 EXIT THAT PASSES THROUGH ANOTHER OCCUPANCY
 CLASSIFICATION.
  
 PER NFPA 1 -
  
 14.9.1 GENERAL.
 14.9.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY
 BALCONY, MEZZANINE, STORY, OR PORTION THEREOF SHALL BE
 NOT LESS THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING
 CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43 OF NFPA 101.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY AND THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 OF NFPA 101 ARE
 MET. [101:7.4.1.1]
  
 NFPA 101
  
 8.6.10 MEZZANINES.
 8.6.10.1 GENERAL. MULTILEVEL RESIDENTIAL HOUSING AREAS
 IN DETENTION AND CORRECTIONAL OCCUPANCIES IN ACCORDANCE
 WITH CHAPTERS 22 AND 23 SHALL BE EXEMPT FROM THE
 PROVISIONS OF
 8.6.10.2 AND 8.6.10.3.
 8.6.10.2 AREA LIMITATIONS.
 8.6.10.2.1 THE AGGREGATE AREA OF MEZZANINES LOCATED
 WITHIN A ROOM, OTHER THAN THOSE LOCATED IN
 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES, SHALL NOT
 EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN WHICH THE
 MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE SIZE OF THE ROOM IN
 WHICH THE MEZZANINE IS LOCATED.
  
 8.6.10.3 OPENNESS. THE OPENNESS OF MEZZANINES SHALL BE
 IN ACCORDANCE WITH 8.6.10.3.1 OR 8.6.10.3.2.
 8.6.10.3.1 ALL PORTIONS OF A MEZZANINE, OTHER THAN
 WALLS NOT MORE THAN 42 IN. (1065 MM) HIGH, COLUMNS, AND
 POSTS, SHALL BE OPEN TO AND UNOBSTRUCTED FROM THE ROOM
 IN WHICH THE MEZZANINE IS LOCATED, UNLESS THE OCCUPANT
 LOAD OF THE AGGREGATE AREA OF THE ENCLOSED SPACE DOES
 NOT EXCEED 10.
  
 PLEASE ENSURE THIS MEZZANINE AND PROPOSED OCCUPANCY
 CLASSIFICATION MEETS THE REQUIREMENT OF THE PROPOSED
 OCCUPANCY PER # 3 ABOVE.
  
  
  
  
  
 6) SHEET 210 - A KITCHEN AREA IS INDICATED WITH SEVERAL
 OVENS NOTED
  
 NFPA 101
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTSOF THIS STANDARD.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMP[LIANCE.
  
  
  
  
  
 7) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. IT APPEARS TO BE OPEN.
  
 PER NFPA 101
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH
 7.1.3.2.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY.
  
  
  
  
 8) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. THERE IS NO STAIR DETAIL, INCLUDING
 RAILINGS, GAURDS AND/OR HAND RAILS THAT MEET THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7 MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
  
  
 9) SHEET A 211 - THERE IS A NOTE INDICATING "UNDER
 STAIR CART PARKING". THERE SHALL BE NOT COMBUSTIBLES
 STORED UNDER STAIRS.
  
 PER NFPA 101 -
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF
 SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2,
 UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2.
  
  
 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN
 EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER
 STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2.
 7.2.2.5.3.1 OPEN SPACE WITHIN THE EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE THAT HAS THE POTENTIAL TO
 INTERFERE WITH EGRESS.
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THESAME FIRE RESISTANCE AS THE EXIT
 ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE,
 OR OTHERWISE HAZARDOUS MATERIALS.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY
  
  
  
  
 10) SHEET E 2.1 - EXIT SIGNS ARE INDICATED OVER SEVERAL
 DOORS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY
 AS PER # 4 ABOVE.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
  
  
 11) A FIRE SPRINKLER SYSTEM IS INDICATED.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE
  
  
  
  
 12) THERE IS NO INDICATIONS OF A FIRE ALARM SYSTEM.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By pleduc Date 2017-05-22 Time   Rev Time 0.00
Received By pleduc Date 2017-05-22 Time 10:04 Sent To  
Notes
2017-05-22 12:34:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 210 - THERE ARE INCORRECT REFERENCES TO THE
 FLORIDA FIRE PREVENTION CODE EDITION; 2010.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 2) SHEET A 210 - THE DOOR SCHEDULE DOES NOT SHOW ANY
 HARDWARE AND/OR EXIT HARDWARE.
  
 PLEASE RECIEW AND CORRECT.
  
  
  
  
 3) SHEET A 210 - THE OCCUPANCY CLASSIFICATION IS NOTED
 AS BUSINESS; HOWEVER, A STORAGE, EMPLOYEE LOUNGE, A
 BUSINESS OFFICE, AND A BAKERY WITH SEATING OVER 50 IS
 INDICATED.
  
 PLEASE PROVIDE WHAT THE OCCUPANCY CLASSIFICATION IS AND
 WHETHER IT IS MIXED OR SEPARATED PER NFPA 101.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS FOLLOWS SHALL BE PERMITTED TO BE
 CONSIDERED PART OF THE PREDOMINANT OCCUPANCY AND SHALL
 BE SUBJECT TO THE PROVISIONS OF THE CODE THAT APPLY TO
 THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2)* NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY
 THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY NON-HAZARDOUS USES NECESSARY FOR
 TRANSACTING THE PRINCIPAL BUSINESS IN STORAGE AND
 INDUSTRIAL OCCUPANCIES NEED NOT BE SEPARATED FROM THE
 PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD PRODUCTS IN ACCORDANCE WITH SUBDIVISION
 6.2.2 NEED NOT BE SEPARATED BY FIRE-RESISTANT
 CONSTRUCTION FROM THE OCCUPANCIES TO WHICH THEY ARE
 ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE 508.2.5 OF THE FLORIDA BUILDING CODE
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
  
  
  
  
 4) THERE IS NO LIFE SAFETY PLAN SHEET PROVIDED.
  
 BASED ON WHAT OCCUPANCY CLASSIFICATION NOTED FOR # 3
 ABOVE, COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY
 SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS
 LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS,
 AND ALL FIRE SAFETY FEATURES AND EQUIPMENT.
  
 NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.11.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING.
 1.7.11.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
 1.7.11.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN.
  
  
  
  
 5) SHEET A 210 - A MEZZANINE IS INDICATED WITH ONLY ONE
 EXIT THAT PASSES THROUGH ANOTHER OCCUPANCY
 CLASSIFICATION.
  
 PER NFPA 1 -
  
 14.9.1 GENERAL.
 14.9.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY
 BALCONY, MEZZANINE, STORY, OR PORTION THEREOF SHALL BE
 NOT LESS THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING
 CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43 OF NFPA 101.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY AND THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 OF NFPA 101 ARE
 MET. [101:7.4.1.1]
  
 NFPA 101
  
 8.6.10 MEZZANINES.
 8.6.10.1 GENERAL. MULTILEVEL RESIDENTIAL HOUSING AREAS
 IN DETENTION AND CORRECTIONAL OCCUPANCIES IN ACCORDANCE
 WITH CHAPTERS 22 AND 23 SHALL BE EXEMPT FROM THE
 PROVISIONS OF
 8.6.10.2 AND 8.6.10.3.
 8.6.10.2 AREA LIMITATIONS.
 8.6.10.2.1 THE AGGREGATE AREA OF MEZZANINES LOCATED
 WITHIN A ROOM, OTHER THAN THOSE LOCATED IN
 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES, SHALL NOT
 EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN WHICH THE
 MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE SIZE OF THE ROOM IN
 WHICH THE MEZZANINE IS LOCATED.
  
 8.6.10.3 OPENNESS. THE OPENNESS OF MEZZANINES SHALL BE
 IN ACCORDANCE WITH 8.6.10.3.1 OR 8.6.10.3.2.
 8.6.10.3.1 ALL PORTIONS OF A MEZZANINE, OTHER THAN
 WALLS NOT MORE THAN 42 IN. (1065 MM) HIGH, COLUMNS, AND
 POSTS, SHALL BE OPEN TO AND UNOBSTRUCTED FROM THE ROOM
 IN WHICH THE MEZZANINE IS LOCATED, UNLESS THE OCCUPANT
 LOAD OF THE AGGREGATE AREA OF THE ENCLOSED SPACE DOES
 NOT EXCEED 10.
  
 PLEASE ENSURE THIS MEZZANINE AND PROPOSED OCCUPANCY
 CLASSIFICATION MEETS THE REQUIREMENT OF THE PROPOSED
 OCCUPANCY PER # 3 ABOVE.
  
  
  
  
  
 6) SHEET 210 - A KITCHEN AREA IS INDICATED WITH SEVERAL
 OVENS NOTED
  
 NFPA 101
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTSOF THIS STANDARD.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMP[LIANCE.
  
  
  
  
  
 7) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. IT APPEARS TO BE OPEN.
  
 PER NFPA 101
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH
 7.1.3.2.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY.
  
  
  
  
 8) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. THERE IS NO STAIR DETAIL, INCLUDING
 RAILINGS, GAURDS AND/OR HAND RAILS THAT MEET THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7 MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
  
  
 9) SHEET A 211 - THERE IS A NOTE INDICATING "UNDER
 STAIR CART PARKING". THERE SHALL BE NOT COMBUSTIBLES
 STORED UNDER STAIRS.
  
 PER NFPA 101 -
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF
 SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2,
 UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2.
  
  
 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN
 EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER
 STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2.
 7.2.2.5.3.1 OPEN SPACE WITHIN THE EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE THAT HAS THE POTENTIAL TO
 INTERFERE WITH EGRESS.
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THESAME FIRE RESISTANCE AS THE EXIT
 ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE,
 OR OTHERWISE HAZARDOUS MATERIALS.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY
  
  
  
  
 10) SHEET E 2.1 - EXIT SIGNS ARE INDICATED OVER SEVERAL
 DOORS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY
 AS PER # 4 ABOVE.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
  
  
 11) A FIRE SPRINKLER SYSTEM IS INDICATED.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE
  
  
  
  
 12) THERE IS NO INDICATIONS OF A FIRE ALARM SYSTEM.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 16:58 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 16:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 13:22 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 13:22 Sent To  
Notes
2017-05-23 13:36:391ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/23/17
  
 1. THE REGULATOR SHALL BE INSTALLED ON THE BRANCH FOR
 FUTURE USE. FBC FG 410.1
  
 2. A DIRT LEG IS REQUIRED FOR EACH APPLIANCE. PER FBC
 FG 408.4
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-12 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-29 Time 13:02 Sent To  
Notes
2017-06-30 13:02:45B23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-28 Time   Rev Time 0.00
Received By cpuell Date 2017-06-14 Time 12:50 Sent To  
Notes
2017-06-15 12:51:10B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 16:27 Rev Time 0.00
Received By jleahy Date 2017-05-16 Time 15:11 Sent To  
Notes
2017-05-17 15:11:19B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2017-07-06 Time 12:02 Sent To  
Notes
2017-07-06 12:05:56IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-06-28 Cont ID  
Sent By jwitmer Date 2017-06-28 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 07:41 Sent To  
Notes
2017-06-28 07:57:56IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2017-07-12 Cont ID  
Sent By jwitmer Date 2017-05-19 Time 10:56 Rev Time 0.00
Received By spalmer Date 2017-05-19 Time 07:23 Sent To  
Notes
2017-07-12 13:17:08PASSED PER SIGNED COPY FROM PALM BEACH COUNTY IMPACT
2017-05-19 10:56:00IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By ccole Date 2017-07-12 Time 11:21 Rev Time 0.00
Received By ccole Date 2017-07-12 Time 10:47 Sent To  
Notes
2017-07-12 11:27:11MECHANICAL PROVISOS 7/12/17
 PERMIT #17050701
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE REVENT,
 VULCAN, AND STONE HEARTH DECK OVENS AND EXHAUST
 VENTILATION AND MAKEUP AIR SYSTEMS,
 AND THE WALK-IN COOLER AND FREEZER, AND REFRIGERATION
 SYSTEMS.
  
 CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-21 Time 11:34 Rev Time 0.00
Received By ccole Date 2017-06-21 Time 09:32 Sent To  
Notes
2017-06-21 11:53:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050701
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MANY NEW SPEC SHEETS FOR EQUIPMENT WERE SUBMITTED
 INCLUDING THE VULCAN OVEN, THE REVENT OVEN, THE STONE
 HEARTH OVEN, TWO DIFFERENT PROOFING CABINERS, THE APEX
 REFRIGERATION SYSTEM ETC. PLEASE SHOW AND LABEL ALL THE
 EQUIPMENT LOCATIONS ON SHEET A211, AND PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN.
  
 2) SHEET M1.1: SECOND REQUEST TO SHOW HOW COMBUSTION
 AIR FOR THE NEW ROTARY OVEN IS BEING PROVIDED. THE
 DESIGN PROFESSIONALS NARRATIVE IS POINTING TO THE OVEN
 EXHAUST EXHAUST VENT IN RESPONSE TO THE COMMENT.
  
 3) M1.1: AS PREVIOUSLY REQUESTED INDICATE HOW MAKE-UP
 AIR FOR THE REVENT OVEN IS BEING PROVIDED. THE BUILDING
 PRESSURIZATION TABLE ON M0.1 INDICATES MUA AT 883 CFMS
 WITHOUT SHOWING HOW THAT AIR IS BEING SUPPLIED.
  
 4) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF AHU-1 & 2 PER SECTION 606.2.1. PLEASE NOTE
 THAT A TYPICAL 5-TON AIR HANDLER CAN PRODUCE SUPPLY AIR
 IN EXCESS OF 2000 CFMS DESPITE THE DESIGN CAPACITIES
 SHOWN IN THE AC SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By ccole Date 2017-05-23 Time 07:16 Rev Time 0.00
Received By ccole Date 2017-05-22 Time 17:36 Sent To  
Notes
2017-05-23 07:47:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050701
 5/23/17
  
 RESULTS: DENIED.
  
 1) THERE APPEARS TO BE CONFLICTING AND INCOMPLETE
 INFORMATION ON THE PLAN REGARDING HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE VARIOUS ROOMS AND SPACES SHOWN ON
 THE LAYPOUT PLAN. REGARDING AHU-1 THE CALCULATIONS ON
 M0.1 INDICATE NATURAL VENTILATION FOR THE SEATING AREA
 , HOWEVER THERE IS AN O/A DUCT CONNECTED TO AHU-1 WHICH
 IS THE MECHANICAL UNIT SUPPLYING CONDITIONED AIR
  
 TO BOTH THE SERVING AND SEATING AREA. THE CALCULATIONS
 ARE ALSO INDICATING 250 CFMS OF O/A SUPPLIED BY AHU-1
 TO THE CORRIDOR, HOWEVER THERE IS NO CORRIDOR SHOWN ON
 THE PLAN IN THE AREA OF AHU-1. REGARDING AHU-2 THE
 CALCULATIONS ARE INDICATING 250 CFMS OF O/A TO THE
 CORRIDOR AND STORAGE ARE. THIS APPEARS INCOMPLETE
 BECAUSE THE AREAS BEING SERVED BY AHU-2 ALSO INCLUDE
 THE
  
 SERVICE AND KITCHEN AREAS, AND MEZZANINE AREA.
  
 2) EXHAUST VENTILATION AT A RATE OF .70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN AREA PER TABLE 403.3.
 PLEASE PROVIDE THE MEANS AND A CALCULATION.
  
 3) PROVIDE EQUIPMENT SCHEDULES FOR THE TWO GAS-FIRED
 OVENS ON THE PLAN AND SUBMIT PRODUCT DATA SHEETS FOR
 EACH.
  
 4) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 TWO GAS-FIRED OVENS AND PROVIDE CALCULATIONS- SECTION
 304 FBC-14 FUEL GAS.
  
 5) PROVIDE VENTING PLANS FOR THE TWO OVENS THAT
 INDICATE THE TYPES AND SIZES OF VENT, VENT RUNS, AND
 TERMINATION LOCATIONS- SEE SECTIONS 502, 503, & 504
 FBC-14 FUEL GAS.
  
 6) PROVIDE AIR BALANCE CALCULATIONS.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND
 WALK-IN COOLERS AND FREEZERS. PLEASE PLACE NOTES ON THE
 PLAN ACCORDINGLY.
  
 8) SHOW THE ACTUAL LOCATIONS ON THE ROOF WHERE THE TWO
 AC CONDENSERS WILL BE INSTALLED INCLUDING CLEARANCE
 DISTANCE MEASUREMENTS FROM ROOF EDGES.
  
 9) SUBMIT THE NOA'S FOR THE AC STANDS, AND O/A LOUVERS
 WITH APPROVAL SIGNATURES AND MARK-UPS BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 16:57 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 16:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 12:44 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 10:44 Sent To  
Notes
2017-05-23 13:22:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/23/17
  
 1.SHT. P0.2 THE BRANCH DRAIN FOR THE URINAL SHALL
 CONNECT DOWN STREAM OF THE LAVATORY'S IT CAN NOT
 CONNECT TO WET VENT PER FBC PL 912.1
  
 2. TEMPERED WATER IS REQUIRED ON PUBLIC LAVATORY'S PER
 FBC PL
  
 3 BACKFLOW REQUIRED ON WATER SUPPLY TO OVEN PROFFER AND
 ESPRESSO MACHINE. PER FBC PL 608.3
  
 4. SHUT OFF VALVES ARE REQUIRED ON THE HOT AND COLD
 DROPS TO ISLAND WITH ESPRESSO AND DRINK MACHINES. PER
 FBC PL 606.1
  
 5. ONE OF THE VENTS FOR GREASE SYSTEM SHALL TERMINATE
 OUTDOORS. PER FBC PL 904.1
  
 6. PLACE A NOTE ON THE PLAN THAT AN INSPECTION ON THE
 EXISTING GREASE INTERCEPTOR SHALL BE COMPLETED BY
 UTILITIES PRIOR TO FINAL PLUMBING INSPECTION, THE OWNER
 CAN CONNECT JEFF ODOMS AT 822-2172 OR [email protected] TO
 SCHEDULE AN INSPECTION WITH UTILITIES.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  