| 2017-05-17 05:05:48 | 1) SHOW ALL THE TYPES OF PIPE MATERIAL BEING INSTALLED, |
| | ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE. |
| | WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | 2)LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS |
| | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 |
| | (37) OR 2014 FBC-RES. SEC. G2413. THE BTU LOAD OF |
| | 10,300 TO 180,000 FOR THE TANKLESS WATER HEATER IS |
| | UNACCEPTABLE. THE CORRECT PIPE SIZE CANNOT BE |
| | DETERMINED IF THE EXACT BTU LOAD IS NOT KNOWN. |
| | 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / |
| | OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014 |
| | FBC-RES. SEC. G 2413.3. |
| | 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | SPEC SHEET FOR THE STOVE DOES NOT SHOW THAT IT IS |
| | LISTED AND LABELED. 2014 FBC-RESIDENTIAL SEC.G2404.3. |
| | 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| | WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. |
| | 7) SUBMIT TWO COPIES OF ALL DOCUMENTS. ONLY ONE SET HAS |
| | BEEN SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |