Plan Review Details - Permit 17050687
Plan Review Stops For Permit 17050687
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-06-09 Cont ID  
Sent By spalmer Date 2017-06-09 Time 10:06 Rev Time 0.00
Received By spalmer Date 2017-06-09 Time 10:06 Sent To  
Notes
2017-06-09 10:07:05PLANS APPROVED AND STAMPED BY TIM LARGE ON 6/9/17
 NATALEE

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-05 Time 13:26 Rev Time 0.00
Received By tklarge Date 2017-06-05 Time 13:27 Sent To  
Notes
2017-06-05 13:03:111) THE SUBMITTED FLOOR PLAN FOR THE GAS IS ILLEGIBLE.
 SUBMIT A CLEAR, EXPANDED FLOOR PLAN THAT REFLECTS THE
 SCOPE OF WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) ONE EDGE OF THE GAS PIPE SCHEMATIC IS CUT OFF AND
 CANNOT BE READ.SUBMIT A COMPLETE PIPE SCHEMATIC FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW ALL THE CORRESPONDING EHD NUMBERS OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1, 2014 FBC-FUEL GAS
 TABLES 402.4. (15) THROUGH 402.4 (17).
 4 ) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413. REFER TO GAS PIPE
 SCHEMATIC WHERE THE EDGE IS CUT OFF.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014
 FBC-RES. SEC. G 2413.3.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 7) THE PIPING SCHEMATIC INDICATES A 2 LB. SYSTEM. SHOW
 THE LOCATION OF ALL STEP DOWN REGULATORS AND HOW THEY
 ARE BEING VENTED. SUBMIT MANUF. SPECS FOR THE
 REGULATORS.2014 FGC SEC.410.3, 410.1.
 8) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2014 FGC
 SEC.409.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By tklarge Date 2017-05-17 Time 05:05 Rev Time 0.00
Received By tklarge Date 2017-05-17 Time 04:41 Sent To  
Notes
2017-05-17 05:05:481) SHOW ALL THE TYPES OF PIPE MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 2)LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413. THE BTU LOAD OF
 10,300 TO 180,000 FOR THE TANKLESS WATER HEATER IS
 UNACCEPTABLE. THE CORRECT PIPE SIZE CANNOT BE
 DETERMINED IF THE EXACT BTU LOAD IS NOT KNOWN.
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014
 FBC-RES. SEC. G 2413.3.
 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 SPEC SHEET FOR THE STOVE DOES NOT SHOW THAT IT IS
 LISTED AND LABELED. 2014 FBC-RESIDENTIAL SEC.G2404.3.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 7) SUBMIT TWO COPIES OF ALL DOCUMENTS. ONLY ONE SET HAS
 BEEN SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-06-09 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-07 Time 15:50 Sent To  
Notes
2017-06-08 15:50:44RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-05 Time 13:27 Rev Time 0.00
Received By tklarge Date 2017-05-30 Time 09:40 Sent To  
Notes
2017-05-31 09:40:24RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-17 Cont ID  
Sent By tklarge Date 2017-05-17 Time 05:06 Rev Time 0.00
Received By tklarge Date 2017-05-15 Time 09:22 Sent To  
Notes
2017-05-16 09:23:07PLUMB <5K