Plan Review Details - Permit 17050665
Plan Review Stops For Permit 17050665
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 08:40 Rev Time 0.00
Received By shill Date 2017-06-27 Time 08:36 Sent To Z
Notes
2017-06-27 08:41:53PROVISO - PASSED AS GOLF PRO SHOP ONLY
  
 PER APPLICANT - THIS IS AN EXISTING GOLF PRO SHOP
 (15110532, PLANS ATTACHED FOR REFERENCE) TO BE
 RE-LOCATED ON THE SAME LOT. USE IS TO CONTINUE AS A
 GOLF PRO SHOP. ANY CHANGE OF USE OR OCCUPANCY REQUIRES
 A SEPARATE PERMIT. USE OF THIS STRUCTURE AS A CLUBHOUSE
 IS NOT COVERED UNDER THIS PERMIT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-31 Cont ID  
Sent By shill Date 2017-05-31 Time 10:41 Rev Time 0.00
Received By shill Date 2017-05-30 Time 17:35 Sent To  
Notes
2017-05-31 10:41:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SCOPE NOT CLEAR.
  
 ON THE PERMIT APPLICATION: DESCRIPTION IS FOR A
 TEMPORARY CLUBHOUSE IN THE DESCRIPTION
 ON THE PERMIT APPLICATION: PROJECT NAME IS "TEMPORARY
 SALES TRAILER"
 SITE PLAN HAS "CLUBHOUSE" HIGHLIGHTED
 ARCHITECT'S LETTER AND PLAN REFERS TO "MODULAR PRO
 SHOP" (STOFFT)
 MODULAR PLANS ARE FOR OFFICES
  
 PLEASE CORRELATE. A COMPLETE REVIEW CANNOT BE DONE AT
 THIS TIME. FOR THIS REVIEW, THIS IS BEING REVIEWED AS A
 DCA MANUFACTURED BUILDING RELOCATION, CHANGE OF
 OCCUPANCY. PLANS SHOULD BE REVISED TO CLEARLY REFLECT
 THIS OR, IF THIS IS NOT THE CASE, REVISE TO CLARIFY
 SCOPE FBC 107.
  
 2. MODULAR BUILDING IS FOR OFFICES AND BUSINESS
 OCCUPANCY (MODSPACE). SHEET A101 (STOFFT) DECLARES
 BUSINESS OCCUPANCY BUT CALLS THIS A "PRO SHOP" WHICH
 APPEARS TO BE MERCANTILE, FBC B 309. ARCHITECT USES 100
 SF PER PERSON, MERCANTILE REQUIRES 30 SF PER PERSON FBC
 B 1004.1.2.
  
 OTHER PLACES CALL THIS A "CLUBHOUSE" WHICH IS ASSEMBLY
 (FBC B 303.1) WITH A HIGHER OCCUPANT LOAD.
  
 IF ARCHITECT DOES NOT AGREE THAT THE PROPOSED "PRO
 SHOP" IS MERCANTILE, REVISE THE PLAN TO INCORPORATE
 PROPOSED USE TO CLARIFY WHY THE PRO SHOP IS BUSINESS
 OCCUPANCY.
  
 A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME DUE TO
 INCONSISTENT INFORMATION. REVISE ALL PLANS TO BE
 CONSISTENT.
  
 3. MODSPACE PLANS CALL THIS A "MODULAR", PROVIDE DCA
 APPROVAL (LETTER SHOWING APPROVAL NUMBER AND PLANS). IF
 THIS IS A DCA MANUFACTURED BUILDING, AND IT WAS
 DESIGNED TO BUSINESS OCCUPANCY, AND NOW MIXED OCCUPANCY
 (BUSINESS & MERCANTILE) IS PROPOSED, A CHANGE OF
 OCCUPANCY IS REQUIRED.
  
 MECHANICAL AND PLUMBING ARE NOT BEING REVIEWED AT THIS
 TIME AS OCCUPANCY AND PROPOSED USE IS NOT CLEAR.
  
 PER DCA, AN EXISTING MODULAR BUILDING BEING CONVERTED
 FROM ONE OCCUPANCY TYPE TO ANOTHER REQUIRES THAT THE
 BUILDING BE BROUGHT INTO COMPLIANCE WITH THE CURRENT
 FBC. MECHANICAL AND PLUMBING WILL BE REVIEWED AFTER
 SCOPE IS CLARIFIED AND PLANS ARE MADE CONSISTENT.
  
 HTTP://WWW.FLORIDABUILDING.ORG/FBC/MANUFACTURED_BUILDIN
 GS/Q_&_A_0208_V3.PDF
  
 THE DCA APPROVAL SHOULD BE PROVIDED TO DOCUMENT
 COMPLIANCE FOR EXISTING MODULAR STRUCTURE. PLANS SHOULD
 SHOW COMPLIANCE FOR THE CHANGE OF OCCUPANCY, ALL
 TRADES.
  
 4. SHEET C1 (MODSPACE) HAS NOTES REGARDING THE INITIAL
 CONSTRUCTION UNDER FBC 2010, BUT ALSO DECLARES FBC 2014
 UNDER "STRUCTURAL LOAD LIMITATIONS". A NOTE STATES THAT
 THIS WAS DESIGNED IN COMPLIANCE WITH ACI318, AISC,
 ACI530. PLEASE REMOVE STANDARDS NOT APPLICABLE TO THIS
 STRUCTURE, FBC 107.
  
 5. ONE ACCESSIBLE RAMP IS SHOWN, THREE ENTRANCES/EXITS
 ARE SHOWN. FBC A 206.4.1, IT APPEARS THAT TWO ARE
 REQUIRED (NOTE DEFINITION OF "PUBLIC ENTRANCE" INCLUDES
 ALL ENTRANCES THAT ARE NOT SERVICE OR RESTRICTED
 ENTRANCES), REVISE PLAN TO INCLUDE 2ND ACCESSIBLE
 ENTRANCE.
  
 6. A001, REMOVE NOTES NOT APPLICABLE OR REVISE TO BE
 APPLICABLE; FOR INSTANCE, CLIMATE NOTE REFERS TO FBC
 RESIDENTIAL CODE, FBC 107, ALSO OTHER PLACES REFER TO
 FBC R. A101 HAS A NOTE REGARDING "FBC 2010
 ACCESSIBILITY CODE, CHAPTER 11". REMOVE NOTES NOT
 APPLICABLE TO THIS JOB, REVISE NOTES WHICH ARE REQUIRED
 TO DEMONSTRATE CODE COMPLIANCE. DUE TO THE NATURE OF
 THIS JOB, IT APPEARS THAT MANY (POSSIBLY MOST) SHOULD
 BE REMOVED OR REVISED.
  
 7. IF THIS IS A MODIFICATION OF AN EXISTING DCA
 MODULAR, REVISE MODSPACE NOTES TO INCLUDE THE FOLLOWING
 INFORMATION FBC 107:
  
 MODSPACE PLAN SHEET A1 SHOWS A COUNTER TO BE TILED.
 REVISE PLAN TO CLARIFY USE OF COUNTER, FBC A 904.
 GENERAL NOTE 1 REGARDING ACCESSIBLE ENTRANCES IS NOT
 CORRECT (60% REQUIRED)
 FLOOR DESIGN LOAD NOT CLEAR; IF THIS IS A CLUBHOUSE
 100PSF REQUIRED
 VARIOUS NOTES REFER TO 170MPH HVHZ; THIS SITE IS 170MPH
 NON-HVHZ AND MUST COMPLY WITH NON-HVHZ REQUIREMENTS
 (HVHZ IS SOMETIMES MORE STRINGENT AND SOMETIMES LESS
 STRINGENT)
 OCCUPANT LOAD OF 100SF PER PERSON MAY NEED TO BE
 REVISED
 IMPACT PROTECTION REQUIRED; PROVIDE INFORMATION
 A NOTE STATES THAT THE ORIGINAL APPROVED PLANS ARE NOT
 AVAILABLE; THEY SHOULD BE ON THE INTERNET
 WWW.FLORIDABUILDING.ORG; CLARIFY
 CHECK ALL NOTES TO CLARIFY SCOPE AND CODE COMPLIANCE
  
 8. THE SITE PLAN SHOWS A ONE STORY CLUBHOUSE,
 HIGHLIGHTED, WHICH IS NOT CONSISTENT WITH THE PLAN
 PROVIDED, CLARIFY, FBC 107.
  
 9. REVISE SITE PLAN TO CLEARLY SHOW ALL PROPERTY LINES,
 DISTANCE OF PROPOSED STRUCTURE TO PROPERTY LINES AND
 ASSUMED PROPERTY LINES (LINES BETWEEN STRUCTURES) FBC
 705. IF THE DARK DASHED LINE IS THE PROPERTY LINE,
 PROVIDE A LEGEND TO DESIGNATE IT AS SUCH.
  
 10. IF THIS STRUCTURE IS TEMPORARY, ADVISE AS TO HOW
 LONG THIS WILL BE IN PLACE OR WHEN THIS WILL BE
 REMOVED, FBC 107 (IMPACT FEES).
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By skennedy Date 2017-05-18 Time 09:11 Rev Time 0.00
Received By skennedy Date 2017-05-18 Time 09:11 Sent To  
Notes
2017-05-18 09:11:34APPLICATION STATES A SEPARATE PERMIT WILL BE APPLIED
 FOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-10 Cont ID  
Sent By skennedy Date 2017-07-19 Time 15:07 Rev Time 0.00
Received By pleduc Date 2017-07-10 Time 14:05 Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-16 Cont ID  
Sent By pleduc Date 2017-06-16 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 09:57 Sent To  
Notes
2017-06-16 10:55:002ND REVIEW
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NEW COMMENT:
  
 1) THE SUBMITTED PLANS INDICATES WORK FOR THE STAIRS
 AND RAMPS ONLY, WITH THE TRAILERS INDICATED AS "BY
 OTHERS". THE APPLICATION STATES "ALL WE ARE DOING IS
 MOVING THE PREVIOUSLY PERMITTED TEMP CLUBHOUSE TO NEW
 LOCATION."
  
 IS THIS PERMIT JUST FOR THE STAIRS AND RAMPS, OR IS IT
 FOR THE ENTIRE PROJECT, INCLUDING THE TRAILER
 RELOCATION AND OCCUPANCY?
  
 IF AN APPROVED PERMIT EXISTS THEN A REVISION MAY NEED
 TO BE SUBMITTED TO SHOW CHANGES.WAS THAT PERMIT EVER
 CO'D? WAS THAT BUILDING EVER OCCUPOED? ARE THE EXISTING
 STAIRS BEING MOVED? ETC.
  
 PLEASE ADDRESS AND CLARIFY
  
  
  
 PREVIOUS COMMENTS:
  
  
 1) THE APPLICATION INDICATES A RELOCATION OF TRAILER.
 THERE IS NO INDICATION OF THE PLAN OF THE ORIGINAL
 LOCATION.
  
 PLEASE INDICATE.
  
 1A.) NOT ADDRESSED, FAILED.
  
 PLEASE SHOW PREVIOUS LOCATION IN RELATION TO NEW
 LOCATION.
  
  
  
 2) CONFIRMED
  
  
  
 3) THE FLOOR PLAN INDICATE OFFICE SPACES, EVEN IN THE
 CENTRAL OPEN AREA. SHEET A001 INDICATES PRO SHOP;
 MERCANTILE.
  
 IS THIS AN OFFICE TRAILER OR A PRO SHOP, MIXED
 OCCUPANCY OR SEPARATED?
  
 PLEASE PROVIDE THE APPLICABLE OCCUPANCY PER NFPA 101,
 5TH EDITION, CHAPTER 6, OCCUPANCY CLASSIFICATION AND
 ENSURE COMPLIANCE.
  
 3A) NOT ADDRESSED, FAILED. IS THIS PERMIT JUST FOR THE
 STAIRS AND RAMPS?
  
  
  
  
 4) ON REVIEW OF THE SUBMITTAL, NFPA 241 HAS BEEN
 REVIEWED. THESE TRAILERS ARE USED FOR THE TEMPORAY USE
 OF BUILDINGS UNDER CONSTRUCTION.
  
 THE CONFIGURATION OF THREE TRAILERS TOGETHER
 CONSTITUTIES AS A COMPLEX AND NEEDS TO BE PROTECTED
 ACCORDINGLY.
  
 CHAPTER 4 TEMPORARY CONSTRUCTION, EQUIPMENT, AND
 STORAGE
  
 4.1 APPLICATION. FOR THE PURPOSES OF CHAPTER 4, THE
 TERM TEMPORARY SHALL BE DEFINED AS THE DURATION OF THE
 CONSTRUCTION PROJECT.
 4.2 TEMPORARY OFFICES AND SHEDS.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE
 STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT
 IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE
 DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE
 LOSS. LARGE CONSTRUCTION SUPPORT
 COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE
 PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS,
 HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION.
  
  
 TEMPORARY FIRE SPRINKLER PROTECTION IS REQUIRED WITHIN
 THESE TRAILERS. A 13D SYSTEM CAN BE CONSIDERED IN LEIU
 OF NFPA 13 SYSTEM, BASED ON AN EOR REVIEW AND
 SUBMITTAL.
  
 AN ALTERNATIVE COMPREHENSIVE LIFE SAFETY SYSTEMS
 EQUIPMENT INSTALLATION AND WATER SUPPLY REVIEW MAY BE
 CONSIDERED.
  
 PLEASE ADDRESS.
  
  
 4A) NOT ADDRESSED, FAILED
  
 DIMENSIONS TO ALL EXISTING BUILDINGS AND PROPOSED
 BUILDINGS SHALL BE CLEARLY INDICATED.
  
 DIMENSION TO THE TWO NEAREST FIRE HYDRANTS SHALL BE
 INDICATED.
  
  
  
 5) PLEASE CONTACT/COORDINATE WITH THE OFFICE OF THE
 FIRE MARSHAL TO DISCUSS AND/OR CONFIRM INSTALLATION
 WITH FORTHCOMING SHOP DRAWINGS.
  
 PLEASE CLARIFY OR PROVIDE A NOTE OF FIRE SPRINKLER
 INSTALLATION.
  
  
 5A) NOT ADDRESSED, FAILED.
  
 PLEASE CLARIFY OR PROVIDE A NOTE OF FIRE SPRINKLER
 INSTALLATION.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 6A) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 7A) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-19 Cont ID  
Sent By pleduc Date 2017-05-19 Time   Rev Time 0.00
Received By pleduc Date 2017-05-19 Time 14:09 Sent To  
Notes
2017-05-19 14:31:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THE APPLICATION INDICATES A RELOCATION OF TRAILER.
 THERE IS NO INDICATION OF THE PLAN OF THE ORIGINAL
 LOCATION.
  
 PLEASE INDICATE.
  
  
  
 2) I SEEM TO RECALL A PREVIOUS PERMIT FOR THIS PROPOSED
 PROJECT. WAS IT FOF PPRC OR WAS IT FOR A PREVIOUSLY
 ISSUED PERMIT ?
  
 PLEASE CLARIFY.
  
  
  
 3) THE FLOOR PLAN INDICATE OFFICE SPACES, EVEN IN THE
 CENTRAL OPEN AREA. SHEET A001 INDICATES PRO SHOP;
 MERCANTILE.
  
 IS THIS AN OFFICE TRAILER OR A PRO SHOP, MIXED
 OCCUPANCY OR SEPARATED?
  
 PLEASE PROVIDE THE APPLICABLE OCCUPANCY PER NFPA 101,
 5TH EDITION, CHAPTER 6, OCCUPANCY CLASSIFICATION AND
 ENSURE COMPLIANCE.
  
  
  
 4) ON REVIEW OF THE SUBMITTAL, NFPA 241 HAS BEEN
 REVIEWED. THESE TRAILERS ARE USED FOR THE TEMPORAY USE
 OF BUILDINGS UNDER CONSTRUCTION.
  
 THE CONFIGURATION OF THREE TRAILERS TOGETHER
 CONSTITUTIES AS A COMPLEX AND NEEDS TO BE PROTECTED
 ACCORDINGLY.
  
 CHAPTER 4 TEMPORARY CONSTRUCTION, EQUIPMENT, AND
 STORAGE
  
 4.1 APPLICATION. FOR THE PURPOSES OF CHAPTER 4, THE
 TERM TEMPORARY SHALL BE DEFINED AS THE DURATION OF THE
 CONSTRUCTION PROJECT.
 4.2 TEMPORARY OFFICES AND SHEDS.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE
 STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT
 IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE
 DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE
 LOSS. LARGE CONSTRUCTION SUPPORT
 COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE
 PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS,
 HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION.
  
  
 TEMPORARY FIRE SPRINKLER PROTECTION IS REQUIRED WITHIN
 THESE TRAILERS. A 13D SYSTEM CAN BE CONSIDERED IN LEIU
 OF NFPA 13 SYSTEM, BASED ON AN EOR REVIEW AND
 SUBMITTAL.
  
 AN ALTERNATIVE COMPREHENSIVE LIFE SAFETY SYSTEMS
 EQUIPMENT INSTALLATION AND WATER SUPPLY REVIEW MAY BE
 CONSIDERED.
  
 PLEASE ADDRESS.
  
  
  
 5) PLEASE CONTACT/COORDINATE WITH THE OFFICE OF THE
 FIRE MARSHAL TO DISCUSS AND/OR CONFIRM INSTALLATION
 WITH FORTHCOMING SHOP DRAWINGS.
  
 PLEASE CLARIFY OR PROVIDE A NOTE OF FIRE SPRINKLER
 INSTALLATION.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-19 Cont ID  
Sent By skennedy Date 2017-07-19 Time 15:07 Rev Time 0.00
Received By skennedy Date 2017-07-07 Time 11:48 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-06 Cont ID  
Sent By jroach Date 2017-07-06 Time 14:25 Rev Time 0.00
Received By jroach Date 2017-06-12 Time 16:05 Sent To  
Notes
2017-06-13 16:05:53B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-12 Cont ID  
Sent By shill Date 2017-06-12 Time 10:01 Rev Time 0.00
Received By shill Date 2017-05-18 Time 09:11 Sent To  
Notes
2017-06-12 10:02:076/12 APPLICANT PULLED FROM REVIEW; SITE PLAN NOT
 CORRECT SO DOES NOT NEED ZONING REVIEW THIS CYCLE
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 08:44 Rev Time 0.00
Received By shill Date 2017-06-27 Time 08:44 Sent To  
Notes
2017-06-27 08:44:34SCOPE OF WORK IS RELOCATION OF EXISTING TEMPORARY GOLF
 PRO SHOP TO ANOTHER LOCATION ON THE SAME LOT
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-31 Cont ID  
Sent By shill Date 2017-05-31 Time 10:41 Rev Time 0.00
Received By shill Date 2017-05-31 Time 10:41 Sent To  
Notes
2017-05-31 10:42:16SEE BUILDING REVIEW. SCOPE NOT CLEAR. IMPACT FEE
 REQUIREMENTS WILL BE CONFIRMED AFTER SCOPE IS
 DETERMINED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By skennedy Date 2017-05-18 Time 09:10 Rev Time 0.00
Received By skennedy Date 2017-05-18 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By skennedy Date 2017-05-18 Time 09:10 Rev Time 0.00
Received By skennedy Date 2017-05-18 Time 09:10 Sent To  
Notes
2017-05-18 09:10:58APPLICATION STATES A SEPARATE PERMIT WILL BE APPLIED
 FOR.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By jroach Date 2017-07-14 Time 09:55 Rev Time 0.00
Received By jroach Date 2017-07-14 Time 09:55 Sent To B
Notes
2017-07-14 09:55:50PROVISO
  
 1. SEPARATE PERMITS REQUIRED FOR ALL SITE IMPROVEMENTS,
 PARKING, LANDSCAPING, AND IRRIGATION. ALL SITE
 IMPROVEMENTS AND LANDSCAPING SHALL BE INSTALLED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR THE
 PRO SHOP.
  
 2. THE PRO SHOP FACILITIES AND ASSOCIATED SITE
 IMPROVEMENTS SHALL BE DEEMED ?TEMPORARY? AND SHALL BE
 REMOVED WITHIN 24 MONTHS OF THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY / COMPLETION FOR SUCH
 IMPROVEMENTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  
 ROUTED TO JOHN ROACH
2017-07-12 09:09:56ROUTED TO JOHN ROACH

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-06 Cont ID  
Sent By jroach Date 2017-07-06 Time 14:24 Rev Time 0.00
Received By jroach Date 2017-07-06 Time 14:24 Sent To  
Notes
2017-07-06 14:25:09PROVISO
  
 1. SEPARATE PERMITS REQUIRED FOR ALL SITE IMPROVEMENTS,
 PARKING, LANDSCAPING, AND IRRIGATION. ALL SITE
 IMPROVEMENTS AND LANDSCAPING SHALL BE INSTALLED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR THE
 PRO SHOP.
  
 2. THE PRO SHOP FACILITIES AND ASSOCIATED SITE
 IMPROVEMENTS SHALL BE DEEMED ?TEMPORARY? AND SHALL BE
 REMOVED WITHIN 24 MONTHS OF THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY / COMPLETION FOR SUCH
 IMPROVEMENTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  
2017-07-05 09:25:25ROUTED TO JOHN ROACH