Plan Review Details - Permit 17050628
Plan Review Stops For Permit 17050628
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 16:26 Rev Time 0.00
Received By jleahy Date 2017-08-18 Time 16:26 Sent To I
Notes
2017-08-18 16:27:39RAISE VALUE OF JOB TO $15,000.00

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 08:06 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 08:06 Sent To  
Notes
2017-05-17 08:16:44JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 VALUE ASSESSED WILL BE $15,000 ELECTRIC SERVICE, PAGE
 E-2 NEED TO SHOW WHAT IS NEW AND WHAT IS EXISTING.
  
 IF ALL NEW OR EXISTING PLEASE STATE. THE NOTES STATE NO
 WORK OTHER THAN SERVICE?
  
 PROVIDE FAULT CURRENT CALCULATION PER 110.24.
  
 110.24 AVAILABLE FAULT CURRENT.
 (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED
 AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT
 INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT
 CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
 CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE
 SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE
 MAXIMUM
 AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE
 EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO
 REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT
 CURRENT
  
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND
 PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE-
 OR
 TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH
 DEVICE
 OR EQUIPMENT WHERE THE POWER ORIGINATES.
  
  
 NOC REQUIRERD FOR JOB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 16:27 Rev Time 0.00
Received By jleahy Date 2017-08-15 Time 13:59 Sent To  
Notes
2017-08-16 13:59:17RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 08:17 Rev Time 0.00
Received By jleahy Date 2017-05-15 Time 10:15 Sent To  
Notes
2017-05-16 10:16:13ELEC <5K