Plan Review Details - Permit 17050594
Plan Review Stops For Permit 17050594
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-23 Cont ID  
Sent By cthroop Date 2017-08-23 Time 11:00 Rev Time 0.00
Received By cthroop Date 2017-08-23 Time 10:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-02 Cont ID  
Sent By cthroop Date 2017-08-02 Time 16:20 Rev Time 0.00
Received By cthroop Date 2017-08-02 Time 14:37 Sent To  
Notes
2017-08-02 16:25:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. WORK DESCRIPTION INCLUDES NEW FLOORING.
 2. IDENTIFY AREAS OF NEW FLOORING ON PLAN.
 3. PROVIDE DEMENSIONS OR TOTAL SQUARE FOOTAGE OF
 PROPOSED FLOORING.
 4. VALUE OF $25,000 APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-11 Cont ID  
Sent By cthroop Date 2017-07-11 Time 11:14 Rev Time 0.00
Received By cthroop Date 2017-07-10 Time 13:37 Sent To  
Notes
2017-07-11 11:17:29BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. 2ND REQUEST. CANNOT VERIFY VALUE.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By cthroop Date 2017-06-06 Time 15:08 Rev Time 0.00
Received By cthroop Date 2017-06-06 Time 14:57 Sent To  
Notes
2017-06-06 15:39:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT VERIFY VALUE AT THIS TIME. ADDITIONAL
 INFORMATION REQUIRED.
 2. DESIGN PROFESSIONAL MAY BE REQUIRED TO SIGN AND SEAL
 PLANS.
 3. PROVIDE THE FOLLOWING ASTM'S FOR THE FLOORING
 UNDERLAYMENT - E-84 (FLAME SPREAD), E-90 (AIRBOURNE
 SOUND) & E-492 (IMPACT SOUND).
 4. PROVIDE ENRERGY SUBMITTAL FOR INSULATION REPLACED IN
 EXTERIOR WALLS.
 5. IDENTIFY RATED WALLS ON PLAN.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN MAY EXCEED $25,000.00 IN VALUE, THE DESIGN MUST
 BE PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS
 481.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 08:56 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 08:56 Sent To  
Notes
2017-08-15 08:56:42NO CHANGES TO ELECTRICAL PREVIOUSLY APPROVED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-08-03 Cont ID  
Sent By jleahy Date 2017-08-03 Time 10:47 Rev Time 0.00
Received By jleahy Date 2017-08-03 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-07-27 Cont ID  
Sent By jpearson Date 2017-07-27 Time 07:52 Rev Time 0.00
Received By jpearson Date 2017-07-27 Time 07:52 Sent To  
Notes
2017-07-27 07:53:55CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (3RD REVIEW):
  
 1. THIS PREVIOUS COMMENT NOT ADDRESSED: ELECTRICAL PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. THIS PREVIOUS COMMENT NOT ADDRESSED: PROVIDE PANEL
 SCHEDULE AS PREVIOUSLY REQUESTED, INDICATING NEW OR
 ALTERED CIRCUITS. ANY ALTERED CIRCUITS ARE REQUIRED TO
 HAVE AFCI PROTECTION WHERE NORMALLY REQUIRED PER CODE.
 NEC 210.12, 215.5
 3. THIS PREVIOUS COMMENT NOT ADDRESSED COMPLETELY,
 EXISTING OUTLETS IN DEN-BED ROOM NOT SHOWN, OUTLETS
 NEED TO BE SPACED PER CODE: SHOW REQUIRED OUTLETS WHERE
 POCKET DOOR IS REMOVED AND NEW WALL INSTALLED. NEC
 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-05 Time 09:05 Rev Time 0.00
Received By jpearson Date 2017-07-05 Time 09:05 Sent To  
Notes
2017-07-05 09:24:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
 2. ELECTRICAL PLAN PROVIDED SHALL BE A MINIMUM 1/8"
 SCALE AS PREVIOUSLY REQUESTED. "BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT." WPB AMENDMENTS TO FBC 107.2.1.4
 3. PROVIDE PANEL SCHEDULE AS PREVIOUSLY REQUESTED,
 INDICATING NEW OR ALTERED CIRCUITS. ANY ALTERED
 CIRCUITS ARE REQUIRED TO HAVE AFCI PROTECTION WHERE
 NORMALLY REQUIRED PER CODE. NEC 210.12, 215.5
 4. SHOW REQUIRED OUTLETS WHERE POCKET DOOR IS REMOVED
 AND NEW WALL INSTALLED. NEC 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By jpearson Date 2017-06-06 Time 10:55 Rev Time 0.00
Received By jpearson Date 2017-06-06 Time 10:55 Sent To  
Notes
2017-06-06 10:59:02CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC 107.2.1 (SEE ALSO SECTION 107.3.5).
 2. QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. FBC 107.2.1.4
 3. PROVIDE ELECTRICAL RISER DIAGRAM. NEC 215.5
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THEIR WIRE AND BREAKER SIZE. FBC 107.2.1, NEC
 408.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-23 Cont ID  
Sent By cthroop Date 2017-08-23 Time 11:00 Rev Time 0.00
Received By cthroop Date 2017-08-08 Time 14:20 Sent To  
Notes
2017-08-09 14:20:50B12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-02 Cont ID  
Sent By cthroop Date 2017-08-02 Time 16:20 Rev Time 0.00
Received By cthroop Date 2017-07-17 Time 15:27 Sent To  
Notes
2017-07-18 15:27:18B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-11 Cont ID  
Sent By cthroop Date 2017-07-11 Time 11:14 Rev Time 0.00
Received By cthroop Date 2017-06-22 Time 13:05 Sent To  
Notes
2017-06-23 13:06:57B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-06 Cont ID  
Sent By cthroop Date 2017-06-06 Time 15:08 Rev Time 0.00
Received By cthroop Date 2017-05-12 Time 10:47 Sent To  
Notes
2017-06-06 10:50:03B11

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-08-17 Cont ID  
Sent By ccole Date 2017-08-17 Time 09:53 Rev Time 0.00
Received By ccole Date 2017-08-17 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-25 Cont ID  
Sent By ccole Date 2017-07-25 Time 12:21 Rev Time 0.00
Received By ccole Date 2017-07-25 Time 12:16 Sent To  
Notes
2017-07-25 12:30:043RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17050594
 7/25/17
  
 1) SHOW BEDROOM RETURNS, AND HOW THE AIR IS BEING
 RETURNED FROM THE MAIN 16X16 GRILL TO THE AIR HANDLER-
 SECTION 601.5.
  
 2) SHOW THE BRANCH DUCT SUPPLYING THE KITCHEN AND
 PROVIDE ALL BRANCH DUCT SIZES.
  
 3) THE DUCT BOARD SHALL BE MINIMUM R-4.2 PER TABLE
 C403.2.7.1 FBC-14 EBNERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-03 Cont ID  
Sent By ccole Date 2017-07-03 Time 13:54 Rev Time 0.00
Received By ccole Date 2017-07-03 Time 13:54 Sent To  
Notes
2017-07-03 14:08:342ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050594
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN. CLARIFY
 IF A NEW AC SYSTEM AND DUCTWORK ARE BEING INSTALLED, OR
 WHAT ALTERATIONS TO THE EXISTING SYSTEM ARE PROPOSED.
 SHOW POINTS OF CONNECTION FOR NEW AND EXISTING DUCTWORK
 IF APPLICABLE, AND PROVIDE AN AC EQUIPMENT SCHEDULE.
  
 2) THE PLANS SHALL BEAR THE SIGNATURE OF THE PERSON WHO
 PREPARED THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By ccole Date 2017-06-06 Time 11:16 Rev Time 0.00
Received By ccole Date 2017-06-06 Time 11:16 Sent To  
Notes
2017-06-06 11:27:471ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050594
 6/6/17
  
 RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING THE RELOCATION OF
 THE AC (PER THE WORK DESCRIPTION ON THE PERMIT
 APPLICATION), AND ALL OTHER ALTERATIONS TO THE EXISTING
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 08:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-26 Cont ID  
Sent By gjohnson Date 2017-07-26 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 06:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-07-07 Cont ID  
Sent By gjohnson Date 2017-07-07 Time 13:42 Rev Time 0.00
Received By gjohnson Date 2017-07-07 Time 12:29 Sent To  
Notes
2017-07-07 13:54:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLANS SHALL BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By gjohnson Date 2017-06-06 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2017-06-06 Time 12:45 Sent To  
Notes
2017-06-06 12:55:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE APPLICATION INDICATES PLUMBING WORK BEING DONE,
 NONE IS SHOWN ON THE PLANS PLEASE PROVIDE INFORMATION
 AND DETAILS ON THE PLAN OF THE PLUMBING WORK TO BE
 DONE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  