| 2017-05-17 10:49:09 | PERMIT# 17050583: FIRE SPRINKLER PLAN REVIEW IS |
| | APPROVED WITH THE FOLLOWING FIRE CODE COMMENTS. NOTE: |
| | THIS PLAN WAS EXPEDITED PER REQUEST FROM CHAKIERA |
| | MORGAN 772-283-2320. GROUP ONE SAFETY. |
| | |
| | APPROVAL SHALL NOT RELIEVE THE APPLICANT OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH THE FIRE CODE. |
| | |
| | NFPA 1.14.2, 2012 EDITION THE APPLICANT SHALL BE |
| | RESPONSIBLE TO ENSURE THAT THE FOLLOWING CONDITIONS ARE |
| | MET: (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF |
| | CONSTRUCTION |
| | DOCUMENTS ON SITE. INCLUDING FIRE SPRINKLER HEAD |
| | SPECIFICATION SHEET. |
| | |
| | NFPA 13-6.2.6 SPECIAL COATINGS. 6.2.6.1 CORROSION |
| | RESISTANT.6.2.6.1.1 LISTED CORROSION-RESISTANT |
| | SPRINKLERS SHALL BE INSTALLED IN LOCATIONS WHERE |
| | CHEMICALS, MOISTURE, OR OTHER CORROSIVE VAPORS |
| | SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES EXIST. |
| | 6.2.6.1.2* UNLESS THE REQUIREMENTS OF 6.2.6.1.3 ARE |
| | MET, CORROSION-RESISTANT COATINGS SHALL BE APPLIED ONLY |
| | BY THE MANUFACTURER OF THE SPRINKLER AND IN ACCORDANCE |
| | WITH THE REQUIREMENTS OF 6.2.6.1.3. |
| | |
| | NFPA 13-6.2.8 GUARDS. SPRINKLERS SUBJECT TO MECHANICAL |
| | INJURY SHALL BE PROTECTED WITH LISTED GUARDS. |
| | |
| | NFPA 13-8.15.12.3, 2010 EDITION: SPRINKLER ACCESS. |
| | ACCESS SHALL BE PROVIDED TO ALL SPRINKLERS FOR |
| | INSPECTION, TESTING, AND MAINTENANCE. |
| | |
| | NFPA 14-6.3.7.1: SYSTEM WATER SUPPLY VALVES, ISOLATION |
| | CONTROL VALVES, AND OTHER VALVES IN FEED MAINS SHALL BE |
| | SUPERVISED IN AN APPROVED MANNER IN THE OPEN POSITION |
| | BY ONE OF THE FOLLOWING METHODS: |
| | (1) A CENTRAL STATION, PROPRIETARY, OR REMOTE STATION |
| | SIGNALING SERVICE.(2) A LOCAL SIGNALING SERVICE THAT |
| | INITIATES AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION.(3) LOCKING OF VALVES IN THE OPEN POSITION. |
| | (4) SEALING OF VALVES AND AN APPROVED WEEKLY RECORDED |
| | INSPECTION WHERE VALVES ARE LOCATED WITHIN FENCED |
| | ENCLOSURES UNDER THE CONTROL OF THE OWNER. 6.3.7.2 |
| | UNDERGROUND GATE VALVES WITH ROADWAY BOXES SHALL NOT BE |
| | REQUIRED TO BE SUPERVISED. |
| | |
| | FRANK STALLWORTH, FIRE INSPECTOR I |