Plan Review Details - Permit 17050583
Plan Review Stops For Permit 17050583
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By fstal Date 2017-05-17 Time 10:16 Rev Time  
Received By fstal Date   Time   Sent To M
Notes
2017-05-17 10:49:09PERMIT# 17050583: FIRE SPRINKLER PLAN REVIEW IS
 APPROVED WITH THE FOLLOWING FIRE CODE COMMENTS. NOTE:
 THIS PLAN WAS EXPEDITED PER REQUEST FROM CHAKIERA
 MORGAN 772-283-2320. GROUP ONE SAFETY.
  
 APPROVAL SHALL NOT RELIEVE THE APPLICANT OF THE
 RESPONSIBILITY OF COMPLIANCE WITH THE FIRE CODE.
  
 NFPA 1.14.2, 2012 EDITION THE APPLICANT SHALL BE
 RESPONSIBLE TO ENSURE THAT THE FOLLOWING CONDITIONS ARE
 MET: (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION
 DOCUMENTS ON SITE. INCLUDING FIRE SPRINKLER HEAD
 SPECIFICATION SHEET.
  
 NFPA 13-6.2.6 SPECIAL COATINGS. 6.2.6.1 CORROSION
 RESISTANT.6.2.6.1.1 LISTED CORROSION-RESISTANT
 SPRINKLERS SHALL BE INSTALLED IN LOCATIONS WHERE
 CHEMICALS, MOISTURE, OR OTHER CORROSIVE VAPORS
 SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES EXIST.
 6.2.6.1.2* UNLESS THE REQUIREMENTS OF 6.2.6.1.3 ARE
 MET, CORROSION-RESISTANT COATINGS SHALL BE APPLIED ONLY
 BY THE MANUFACTURER OF THE SPRINKLER AND IN ACCORDANCE
 WITH THE REQUIREMENTS OF 6.2.6.1.3.
  
 NFPA 13-6.2.8 GUARDS. SPRINKLERS SUBJECT TO MECHANICAL
 INJURY SHALL BE PROTECTED WITH LISTED GUARDS.
  
 NFPA 13-8.15.12.3, 2010 EDITION: SPRINKLER ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL SPRINKLERS FOR
 INSPECTION, TESTING, AND MAINTENANCE.
  
 NFPA 14-6.3.7.1: SYSTEM WATER SUPPLY VALVES, ISOLATION
 CONTROL VALVES, AND OTHER VALVES IN FEED MAINS SHALL BE
 SUPERVISED IN AN APPROVED MANNER IN THE OPEN POSITION
 BY ONE OF THE FOLLOWING METHODS:
 (1) A CENTRAL STATION, PROPRIETARY, OR REMOTE STATION
 SIGNALING SERVICE.(2) A LOCAL SIGNALING SERVICE THAT
 INITIATES AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.(3) LOCKING OF VALVES IN THE OPEN POSITION.
 (4) SEALING OF VALVES AND AN APPROVED WEEKLY RECORDED
 INSPECTION WHERE VALVES ARE LOCATED WITHIN FENCED
 ENCLOSURES UNDER THE CONTROL OF THE OWNER. 6.3.7.2
 UNDERGROUND GATE VALVES WITH ROADWAY BOXES SHALL NOT BE
 REQUIRED TO BE SUPERVISED.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-12 Time 12:52 Sent To  
Notes
2017-05-15 12:52:26ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-05-26 Cont ID  
Sent By ccole Date 2017-05-26 Time 07:58 Rev Time 0.00
Received By ccole Date 2017-05-26 Time 07:58 Sent To  
Notes
***NONE***