Plan Review Details - Permit 17050566
Plan Review Stops For Permit 17050566
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-20 Time 14:45 Sent To  
Notes
2017-06-21 14:45:46RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-30 Time 14:48 Sent To  
Notes
2017-05-31 14:49:05RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By lmarchan Date 2017-05-31 Time 14:48 Rev Time 0.00
Received By lmarchan Date 2017-05-11 Time 15:46 Sent To  
Notes
2017-05-12 15:46:40SUBMITTAL ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-28 Cont ID  
Sent By ccole Date 2017-06-28 Time 08:49 Rev Time 0.00
Received By ccole Date 2017-06-28 Time 08:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By ccole Date 2017-06-05 Time 09:42 Rev Time 0.00
Received By ccole Date 2017-06-05 Time 07:15 Sent To  
Notes
2017-06-05 09:52:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050566
 6/9/17
  
 RESULTS: DENIED.
  
 1) SHEET M2.01: REVISION #3 DESIGNATED BY LETTER C
 (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS
 SHEET. REVISON #3, AMONG OTHER THINGS, SHOWED THE
 GENERATOR INTAKE AND EXHAUST CLEARANCE DIMENSIONS, AND
 THE LAUNDRY AND NAIL SALON AIR BALANCE CALCULATIONS.
  
 2) M2.02: REVISION #3 DESIGNATED BY LETTER C
 (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS
 SHEET. REVISION #3, AMONG OTHER THINGS, SHOWED
 LOCATIONS OF ABOVE CEILING PLENUM SPACES, AND HAD A
 NOTE PROHIBITING COMBUSTIBLES TO BE INSTALLED IN THE
 MECHANICAL CLOSETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By ccole Date 2017-05-17 Time 07:07 Rev Time 0.00
Received By ccole Date 2017-05-16 Time 12:41 Sent To  
Notes
2017-05-17 07:45:541ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17050566
 MASTER #15111020
 5/17/17
  
 RESULTS: DENIED.
  
 1) PLAN SHEETS M2.01 & A0.32: A FIRE DAMPER IS REQUIRED
 WHERE THE 12X6 SUPPLY DUCT IS SHOWN PENETRATING A 2HR.
 FIRE RATED WALL IN THE CORRIDOR BY THE LAUNDRY ROOM-
 PLEASE NOTE EXCEPTION #3 UNDER SECTION 716.5.2 FBC-10
 BUILDING APPLIES ONLY TO 1HR RATED WALLS- PROVIDE THE
 REQUIRED FIRE DAMPER.
  
 2) SHEETS M2.02 & A0.33: FIRE DAMPERS ARE REQUIRED
 WHERE THE 26X12 SUPPLY DUCT IS SHOWN PENETRATING THE
 1HR FIRE RATED WALLS AT THE MEP CLOSET AND WOMEN'S
 RESTROOM- PLEASE NOTE EXCEPTION #3 DOES NOT APPLY
 BECAUSE THE DUCT SYSTEM CONTAINS FLEX DUCT BRANCHES.
  
 3) SHEETS M2.02 & A0.33: A FIRE DAMPER IS REQUIRED FOR
 THE 18X10 SUPPLY DUCT PENETRATING THE 1HR FIRE RATED
 YOGA/WOMEN'S RESTROOM WALL BECAUSE THE DUCT SYSTEM
 CONTAINS FLEX BRANCHES.
  
 4) SHEETS M2.22, M2.23, M2.24, M2.25, & M2.26: MANY OF
 THE DUCTS THAT ARE DESIGNATED AS FLAMEBAR PER THE
 ENGINEER'S NARRATIVE ARE NOT IDENTIFIED ON THE PLANS.
 PLEASE LABEL ALL FLAMEBAR DUCTS ON THESE PLAN SHEETS
  
 PLEASE SUBMIT CORRECTED PLANS ALONG WITH THE REQUESTED
 DETAILS AND SUBMITTALS LISTED UNDER PROVISOS #2 & #3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  