| Plan Review Stops For Permit 17050545 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2017-06-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-27 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-27 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-24 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2017-06-24 13:30:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | TEST REPORTS FOR PROFLEX 250 WITH QUARRY TILE WAS | | | SUBMITTED. PROPOSED INSTALLATION IS ENGINEERED WOOD | | | FLOORING. PROVIDE THREE TEST REPORTS FOR ENGIENERED | | | WOOD FLOOR OR PROVIDE THREE TEST REPORTS ALONG WITH | | | MANUFACTURER'S COMPARATIVE ANALYSIS FOR ENGINEERED WOOD | | | FLOOR. | | | | | | PLEASE CONTACT ME TO DISCUSS. THIS WILL LIKELY BE | | | RESOLVED VIA TELEPHONE / EMAIL RATHER THAN A FORMAL | | | RESUBMISSION. | | | | | | 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE | | | REQUIRED SHOWING COMPLIANCE WITH: | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-02 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-02 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2017-06-02 12:31:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | PLAN SPECS ENGINEERED WOOD FLOOR. WE ARE ATTEMPTING TO | | | RESOLVE THIS VIA EMAIL. | | | | | | 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE | | | REQUIRED SHOWING COMPLIANCE WITH: | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-16 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-15 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2017-05-16 06:34:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC B 603, DETAIL A-A1.0 SPECS WOOD AS ALTERNATE, | | | ISN'T THIS A HIGH RISE? REVISE DETAIL OR CLARIFY. | | | | | | 2. DEMOLITION NOTES, REMOVE NOTES NOT APPLICABLE TO | | | THIS PROJECT (BURIED TANKS, SOIL TESTING, ETC.). | | | | | | 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE | | | REQUIRED SHOWING COMPLIANCE WITH: | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | 4. FLOOR PLANS 1 AND 2, PAGE A1.0 APPEAR TO PROPOSE A 4 | | | INCH CHANGE IN ELEVATION TO THE AREA SOUTH OF THE | | | KITCHEN. IF THIS IS INTENDED FOR THE COUNTERTOP, | | | RE-LOCATE THE DIMENSION AND REVISE ELEVATIONS C AND E. | | | | | | IF THIS IS FOR THE FLOOR - THE PURPOSE OF THIS IS NOT | | | CLEAR, NO CORRESPONDING DETAIL PROVIDED, ROOM | | | DESIGNATION FOR THE AREA NOT PROVIDED. FBC B CHAPTER | | | 10, FBC 107, REVISE TO CLARIFY. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-20 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-20 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-06-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-07 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-07 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2017-06-07 08:26:19 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL PLAN REVIEW COMMENTS: | | | | | | 1. BOTH SETS OF PLANS MUST BE SIGNED AND SEALED. | | | PROVIDE CORRECTION. FS 471.025, FBC 107.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-24 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-24 |
Time |
18:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-06-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-16 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2017-06-16 11:41:04 | 3RD REVIEW | | | | | | PROVISO COMMENT RESTATED FOR 2ND REVIEW: | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-06-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-05 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2017-06-05 12:32:24 | PROVISO COMMENT RESTATED FOR 2ND REVIEW: | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-05-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-15 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2017-05-15 12:34:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-13 |
Time |
12:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-06-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-13 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-31 |
Time |
10:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-24 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-11 |
Time |
12:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-20 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-20 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-06 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-06 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2017-06-06 12:36:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050545 | | | 6/6/17 | | | | | | RESULTS: DENIED. | | | | | | 1) HVAC NOTE #11 INDICATES THE PLAN IS INTENDED TO BE | | | AN "AS-BUILT OF CONTRACTOR DESIGN", HOWEVER NO DUCTWORK | | | LATYOUT AND DETAILS HAVE BEEN PROVIDED. | | | | | | 2) PROVIDE BATH EXHAUST DUCT DETAILS- TYPE AND SIZE OF | | | DUCTS AND SUBDUCT CONNECTIONS TO EXISTING CHASES. | | | | | | 3) THE ARCHITECT OF RECORD SHALL PROVIDE HIS SIGNATURE | | | AND SEAL ON BOTH SETS OF PLANS SUBMITTED IN ACCORDANCE | | | WITH SECTION 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-18 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2017-05-18 14:49:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050545 | | | 5/18/17 | | | | | | RESULTS: DENIED. | | | | | | 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED PER | | | TABLE 403.3. PROVIDE A SYSTEM THAT PROVIDES EITHER 25 | | | CFMS CONTINUOUSLY, OR 100 CFMS INTERMITTENTLY. | | | | | | 2) PROVIDE PRODUCT SPEC SHEETS FOR THE NEW RANGE AND | | | RANGE HOOD AND INCLUDE EQUIPMENT SCHEDULES ON THE PLAN- | | | SECTION 505. | | | | | | 3) SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION. | | | PLEASE INCLUDE THE TYPE AND SIZE OF DUCT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-20 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-20 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-06-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-06-13 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-06-12 |
Time |
17:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-23 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-23 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|