Plan Review Details - Permit 17050545
Plan Review Stops For Permit 17050545
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 17:07 Rev Time 0.00
Received By shill Date 2017-06-27 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 13:25 Rev Time 0.00
Received By shill Date 2017-06-24 Time 13:25 Sent To  
Notes
2017-06-24 13:30:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TEST REPORTS FOR PROFLEX 250 WITH QUARRY TILE WAS
 SUBMITTED. PROPOSED INSTALLATION IS ENGINEERED WOOD
 FLOORING. PROVIDE THREE TEST REPORTS FOR ENGIENERED
 WOOD FLOOR OR PROVIDE THREE TEST REPORTS ALONG WITH
 MANUFACTURER'S COMPARATIVE ANALYSIS FOR ENGINEERED WOOD
 FLOOR.
  
 PLEASE CONTACT ME TO DISCUSS. THIS WILL LIKELY BE
 RESOLVED VIA TELEPHONE / EMAIL RATHER THAN A FORMAL
 RESUBMISSION.
  
 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE
 REQUIRED SHOWING COMPLIANCE WITH:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-02 Cont ID  
Sent By shill Date 2017-06-02 Time 12:29 Rev Time 0.00
Received By shill Date 2017-06-02 Time 12:27 Sent To  
Notes
2017-06-02 12:31:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 PLAN SPECS ENGINEERED WOOD FLOOR. WE ARE ATTEMPTING TO
 RESOLVE THIS VIA EMAIL.
  
 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE
 REQUIRED SHOWING COMPLIANCE WITH:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-16 Cont ID  
Sent By shill Date 2017-05-16 Time 06:34 Rev Time 0.00
Received By shill Date 2017-05-15 Time 17:24 Sent To  
Notes
2017-05-16 06:34:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 603, DETAIL A-A1.0 SPECS WOOD AS ALTERNATE,
 ISN'T THIS A HIGH RISE? REVISE DETAIL OR CLARIFY.
  
 2. DEMOLITION NOTES, REMOVE NOTES NOT APPLICABLE TO
 THIS PROJECT (BURIED TANKS, SOIL TESTING, ETC.).
  
 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE
 REQUIRED SHOWING COMPLIANCE WITH:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 4. FLOOR PLANS 1 AND 2, PAGE A1.0 APPEAR TO PROPOSE A 4
 INCH CHANGE IN ELEVATION TO THE AREA SOUTH OF THE
 KITCHEN. IF THIS IS INTENDED FOR THE COUNTERTOP,
 RE-LOCATE THE DIMENSION AND REVISE ELEVATIONS C AND E.
  
 IF THIS IS FOR THE FLOOR - THE PURPOSE OF THIS IS NOT
 CLEAR, NO CORRESPONDING DETAIL PROVIDED, ROOM
 DESIGNATION FOR THE AREA NOT PROVIDED. FBC B CHAPTER
 10, FBC 107, REVISE TO CLARIFY.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-20 Cont ID  
Sent By jpearson Date 2017-06-20 Time 07:45 Rev Time 0.00
Received By jpearson Date 2017-06-20 Time 07:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-07 Cont ID  
Sent By jpearson Date 2017-06-07 Time 08:13 Rev Time 0.00
Received By jpearson Date 2017-06-07 Time 08:13 Sent To  
Notes
2017-06-07 08:26:19CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL PLAN REVIEW COMMENTS:
  
 1. BOTH SETS OF PLANS MUST BE SIGNED AND SEALED.
 PROVIDE CORRECTION. FS 471.025, FBC 107.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 18:40 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 18:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-16 Cont ID  
Sent By pleduc Date 2017-06-16 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 09:58 Sent To  
Notes
2017-06-16 11:41:043RD REVIEW
  
 PROVISO COMMENT RESTATED FOR 2ND REVIEW:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By pleduc Date 2017-06-05 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 11:50 Sent To  
Notes
2017-06-05 12:32:24PROVISO COMMENT RESTATED FOR 2ND REVIEW:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-15 Cont ID  
Sent By pleduc Date 2017-05-15 Time   Rev Time 0.00
Received By pleduc Date 2017-05-15 Time 09:41 Sent To  
Notes
2017-05-15 12:34:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 13:30 Rev Time 0.00
Received By shill Date 2017-06-13 Time 12:45 Sent To  
Notes
2017-06-14 12:46:11B03

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 12:39 Rev Time 0.00
Received By gjohnson Date 2017-05-31 Time 10:31 Sent To  
Notes
2017-06-01 10:31:43B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 18:40 Rev Time 0.00
Received By jleahy Date 2017-05-11 Time 12:41 Sent To  
Notes
2017-05-12 12:41:41B02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 14:19 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 13:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By ccole Date 2017-06-06 Time 12:26 Rev Time 0.00
Received By ccole Date 2017-06-06 Time 12:26 Sent To  
Notes
2017-06-06 12:36:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050545
 6/6/17
  
 RESULTS: DENIED.
  
 1) HVAC NOTE #11 INDICATES THE PLAN IS INTENDED TO BE
 AN "AS-BUILT OF CONTRACTOR DESIGN", HOWEVER NO DUCTWORK
 LATYOUT AND DETAILS HAVE BEEN PROVIDED.
  
 2) PROVIDE BATH EXHAUST DUCT DETAILS- TYPE AND SIZE OF
 DUCTS AND SUBDUCT CONNECTIONS TO EXISTING CHASES.
  
 3) THE ARCHITECT OF RECORD SHALL PROVIDE HIS SIGNATURE
 AND SEAL ON BOTH SETS OF PLANS SUBMITTED IN ACCORDANCE
 WITH SECTION 61G1-16.003 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By ccole Date 2017-05-18 Time 14:34 Rev Time 0.00
Received By ccole Date 2017-05-18 Time 14:34 Sent To  
Notes
2017-05-18 14:49:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050545
 5/18/17
  
 RESULTS: DENIED.
  
 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED PER
 TABLE 403.3. PROVIDE A SYSTEM THAT PROVIDES EITHER 25
 CFMS CONTINUOUSLY, OR 100 CFMS INTERMITTENTLY.
  
 2) PROVIDE PRODUCT SPEC SHEETS FOR THE NEW RANGE AND
 RANGE HOOD AND INCLUDE EQUIPMENT SCHEDULES ON THE PLAN-
 SECTION 505.
  
 3) SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION.
 PLEASE INCLUDE THE TYPE AND SIZE OF DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-20 Cont ID  
Sent By gjohnson Date 2017-06-20 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2017-06-20 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 12:39 Rev Time 0.00
Received By gjohnson Date 2017-06-12 Time 17:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 10:02 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 10:02 Sent To  
Notes
***NONE***