Plan Review Details - Permit 17050544
Plan Review Stops For Permit 17050544
Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-25 Time 14:43 Sent To  
Notes
2017-05-25 14:43:27GIVEN TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-12 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-11 Time 10:54 Sent To  
Notes
2017-05-12 10:54:18REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-25 Cont ID  
Sent By hmoser Date 2017-05-25 Time 15:09 Rev Time 0.00
Received By hmoser Date 2017-05-25 Time 15:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By ccole Date 2017-05-12 Time 16:30 Rev Time 0.00
Received By ccole Date 2017-05-12 Time 16:30 Sent To  
Notes
2017-05-12 16:39:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050544
 5/12/17
  
 RESULTS: DENIED.
  
 1) SHEET M400: PLEASE TAG THE SUPPLY DIFFUSERS AND
 RETURN GRILLS IN ACCORDANCE WITH THE AIR DISTRIBUTION
 SCHEDULE ON THE APPROVED SHEET 200. PLEASE NOTE THE
 APPROVED HVAC FLOOR PLAN WAS LABELED M100.
  
 2) M200: REVISE THE HEAT PUMP SCHEDULE N THE APPROVED
 M200 PLAN SHEET TO SHOW THE NEW HEAT PUMPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  