Plan Review Details - Permit 17050508
Plan Review Stops For Permit 17050508
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By rmcdouga Date 2017-07-21 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2017-07-21 Time 06:54 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-06-20 Cont ID  
Sent By rmcdouga Date 2017-06-20 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2017-06-20 Time 13:44 Sent To  
Notes
2017-06-20 15:39:34PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - COMMENT NUMBER 1 FROM THE FIRST
 TWO REVIEWS WAS NOT ADDRESSED.
 PLEASE ADDRESS THE ITEM NOTED BELOW:
  
 1) THE GENERATOR PAD WINDLOAD ANCHORING DETAILS FROM
 RONALD H. WILSON A FLORIDA LICENSED ENGINEER ARE
 REQUIRED TO HAVE HIS ORIGINAL HANDWRITTEN SIGNATURE IN
 ADDITION TO HIS SEAL AND THE DATE. COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.002
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By rmcdouga Date 2017-06-05 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-06-05 Time 07:17 Sent To  
Notes
2017-06-05 07:47:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - COMMENTS FROM THE FIRST REVIEW
 WERE NOT ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD WINDLOAD ANCHORING DETAILS FROM
 RONALD H. WILSON A FLORIDA LICENSED ENGINEER ARE
 REQUIRED TO HAVE HIS ORIGINAL HANDWRITTEN SIGNATURE IN
 ADDITION TO HIS SEAL AND THE DATE. COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.002
  
 2) A MINIMUM OF TWO IDENTICAL SETS OF PLAN DOCUMENTS
 ARE REQUIRED. SEE GAS REVIEW COMMENTS. FBC 107.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By rmcdouga Date 2017-05-26 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2017-05-26 Time 17:39 Sent To  
Notes
2017-05-26 17:55:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD WINDLOAD ANCHORING DETAILS FROM
 RONALD H. WILSON A FLORIDA LICENSED ENGINEER ARE
 REQUIRED TO HAVE HIS ORIGINAL HANDWRITTEN SIGNATURE IN
 ADDITION TO HIS SEAL AND THE DATE. COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.002
  
 2) A MINIMUM OF TWO IDENTICAL SETS OF PLAN DOCUMENTS
 ARE REQUIRED. SEE GAS REVIEW COMMENTS. FBC 107.1
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-21 Cont ID  
Sent By jleahy Date 2017-07-21 Time 15:31 Rev Time 0.00
Received By jleahy Date 2017-07-21 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-20 Cont ID  
Sent By jleahy Date 2017-06-16 Time 12:45 Rev Time 0.00
Received By jleahy Date 2017-06-16 Time 17:03 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 07:56 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 07:56 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2017-08-11 Cont ID  
Sent By tklarge Date 2017-08-11 Time 10:09 Rev Time 0.00
Received By tklarge Date 2017-08-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 09:05 Rev Time 0.00
Received By tklarge Date 2017-07-20 Time 08:37 Sent To  
Notes
2017-07-20 09:05:391) CITY RECORDS SHOW AN EXISTING GAS SYSTEM WITH AN
 EXISTING BTU LOAD OF 540,000 BTU'S. THE ADDED 281,000
 BTU'S BRINGS THE TOTAL TO 821,000 BTU'S. THE GALVANIZED
 SUPPLY LINE FROM THE METER SHALL BE A MINIMUM OF 2
 INCHES FOR A LESS THAN 2 PSI SYSTEM PER TABLE 402.4 (2)
 . THE PLANS ON RECORD SHOWS THIS SUPPLY AS 1 1/2
 INCHES.
 2) ONE OF THE PE TABLES REFERENCED ON THE DRAWING
 (TABLE 402.4 (24) IS FOR PE TUBING WITH A MAX SIZE OF
 3/4 INCH. THIS TABLE IS NOT APPLICABLE.
 3) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 NOTE; I HAVE INCLUDED A COPY OF THE PLAN ON CITY FILE
 FOR YOUR INFORMATION.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-06-19 Cont ID  
Sent By jleahy Date 2017-06-20 Time 17:05 Rev Time 0.00
Received By tklarge Date 2017-06-19 Time 06:00 Sent To  
Notes
2017-06-19 06:05:301) THERE ARE SEVERAL SETS OF DOCUMENTS THAT HAVE BEEN
 SUBMITTED AND ALL THE SETS DO NOT CONTAIN THE SAME
 SHEETS. THERE ARE LOOSE SHEETS THAT I HAVE NO IDEA WHAT
 GOES WHERE. THIS SUBMITTAL IS VERY DISORGANIZED AND A
 PLAN REVIEW COULD NOT BE PERFORMED.REMOVE ALL OLD PLAN
 SHEETS AND ORGANIZE THE SUBMITTAL DOCUMENTS INTO 2
 COMPLETE SETS FOR REVIEW. WPB AMEND. TO FBC SEC.
 107.2.1. 3RD REQUEST. NOTE: THE NEXT RESUBMITTAL WILL
 BE SUBJECT TO 4 TIMES THE PLAN REVIEW FEE PER F.S.
 553.80 (2) (B).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By rmcdouga Date 2017-06-05 Time 07:51 Rev Time 0.00
Received By tklarge Date 2017-06-05 Time 05:53 Sent To  
Notes
2017-06-05 06:07:461) THERE ARE 4 SETS OF DOCUMENTS THAT HAVE BEEN
 SUBMITTED AND ALL THE SETS DO NOT CONTAIN THE SAME
 SHEETS. ORGANIZE THE SUBMITTAL DOCUMENTS INTO COMPLETE
 SETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) THE SURVEY AND ONE OF THE GAS PLANS SHOWS 1 INCH
 UNDERGROUND PE AND ANOTHER GAS DRAWING SHOWS 3/4 INCH
 PE. CLARIFY.2ND REQUEST.
 3) ONE OF THE GAS PLANS SHOWS A BTU LOAD OF 330,000
 BTU'S BUT THE MANUF. SPEC SHEETS FOR THE GENERATOR
 SHOWS 281,000 BTU'S AT FULL LOAD. CLARIFY.2ND REQUEST.
 4) THE GAS APPLICATION NOTES A NEW GAS METER UNDER THE
 DESCRIPTION OF WORK BUT THE PLANS SHOW AN EXISTING GAS
 METER. CLARIFY.2ND REQUEST.
 5) THE GAS PLAN SHOWS A LOW PRESSURE SYSTEM BUT YOU
 HAVE ALSO SUBMITTED A SIZING TABLE FOR A 2 PSI SYSTEM.
 IF THIS IS NOT APPLICABLE REMOVE COPIES OF THIS
 DOCUMENT FROM THE PLANS. WPB AMEND. TO FBC
 SEC.107.2.1.2ND REQUEST.
  
 NOTE: NONE OF THE COMMENTS FROM THE FIRST REVIEW HAVE
 BEEN ADDRESSED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By tklarge Date 2017-05-25 Time 06:21 Rev Time 0.00
Received By tklarge Date 2017-05-25 Time 05:44 Sent To  
Notes
2017-05-25 06:21:151) THERE ARE 4 SETS OF DOCUMENTS THAT HAVE BEEN
 SUBMITTED AND ALL THE SETS DO NOT CONTAIN THE SAME
 SHEETS. ORGANIZE THE SUBMITTAL DOCUMENTS INTO COMPLETE
 SETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE SURVEY AND ONE OF THE GAS PLANS SHOWS 1 INCH
 UNDERGROUND PE AND ANOTHER GAS DRAWING SHOWS 3/4 INCH
 PE. CLARIFY.
 3) ONE OF THE GAS PLANS SHOWS A BTU LOAD OF 330,000
 BTU'S BUT THE MANUF. SPEC SHEETS FOR THE GENERATOR
 SHOWS 281,000 BTU'S AT FULL LOAD. CLARIFY.
 4) THE GAS APPLICATION NOTES A NEW GAS METER UNDER THE
 DESCRIPTION OF WORK BUT THE PLANS SHOW AN EXISTING GAS
 METER. CLARIFY.
 5) THE GAS PLAN SHOWS A LOW PRESSURE SYSTEM BUT YOU
 HAVE ALSO SUBMITTED A SIZING TABLE FOR A 2 PSI SYSTEM.
 IF THIS IS NOT APPLICABLE REMOVE COPIES OF THIS
 DOCUMENT FROM THE PLANS. WPB AMEND. TO FBC SEC.107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-08-11 Cont ID  
Sent By tklarge Date 2017-08-11 Time 10:09 Rev Time 0.00
Received By tklarge Date 2017-08-01 Time 14:42 Sent To  
Notes
2017-08-02 14:42:12RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-21 Cont ID  
Sent By jleahy Date 2017-07-21 Time 17:18 Rev Time 0.00
Received By jleahy Date 2017-07-17 Time 08:31 Sent To  
Notes
2017-07-19 08:31:19RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-20 Cont ID  
Sent By jleahy Date 2017-06-20 Time 17:05 Rev Time 0.00
Received By jleahy Date 2017-06-13 Time 10:27 Sent To  
Notes
2017-06-14 10:28:04RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-05 Cont ID  
Sent By rmcdouga Date 2017-06-05 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2017-05-31 Time 09:10 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-26 Cont ID  
Sent By rmcdouga Date 2017-05-26 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2017-05-10 Time 13:23 Sent To  
Notes
2017-05-11 13:24:04ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-15 Cont ID  
Sent By njwira Date 2017-06-15 Time 09:18 Rev Time 0.00
Received By njwira Date 2017-06-14 Time 14:40 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By njwira Date 2017-05-17 Time 16:51 Rev Time 0.00
Received By njwira Date 2017-05-11 Time 16:43 Sent To E
Notes
***NONE***