Plan Review Details - Permit 17050506
Plan Review Stops For Permit 17050506
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-06-01 Time   Rev Time 0.00
Received By cpuell Date 2017-06-01 Time 15:29 Sent To  
Notes
2017-06-01 15:29:46CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-23 Cont ID  
Sent By ccole Date 2017-05-23 Time 08:18 Rev Time 0.00
Received By ccole Date 2017-05-19 Time 10:56 Sent To  
Notes
2017-05-22 10:56:35RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-12 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-10 Time 12:41 Sent To  
Notes
2017-05-11 12:41:14ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-01 Cont ID  
Sent By ccole Date 2017-06-01 Time 17:39 Rev Time 0.00
Received By ccole Date 2017-06-01 Time 17:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-23 Cont ID  
Sent By ccole Date 2017-05-23 Time 08:14 Rev Time 0.00
Received By ccole Date 2017-05-23 Time 08:14 Sent To  
Notes
2017-05-23 08:18:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050506
 5/23/17
  
 1) THE SUBMITTED WIND LOAD ENGINEERING BY JAMES F.
 BIAGI PE REQUIRES AN ORIGINAL SIGNATURE AND SEAL PER
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By ccole Date 2017-05-12 Time 10:49 Rev Time 0.00
Received By ccole Date 2017-05-12 Time 10:49 Sent To  
Notes
2017-05-12 11:38:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050506
 5/12/17
  
 RESULTS: DENIED.
  
 1) PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLER AND THE
 WATER TANK ON THE PLAN. THE CHILLER SCHEDULE MUST
 INCLUDE THE EFFICIENCY RATING OF THE UNIT AS REQUIRED
 BY TABLE C403.2.3(7) FBC-14 ENERGY CONSERVATION.
  
 2) SUBMIT A CUT SHEET FOR THE WATER TANK.
  
 3) THE CHILLER APPEARS TO BE ON THE ROOF: PROVIDE WIND
 LOAD ENGINEERING FOR INSTALLATION- SECTION 301.15.
  
 4) SUBMIT TWO COPIES OF THE CITY OF WEST PALM BEACH AC
 CHANGEOUT FORM,
  
 5) PROVIDE THE TYPE AND THICKNESS OF CHILLED WATER
 PIPING INSULATION- REFER TO TABLE C403.2.8.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  