Plan Review Details - Permit 17050503
Plan Review Stops For Permit 17050503
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-01 Cont ID  
Sent By rmcdouga Date 2017-06-01 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2017-06-01 Time 18:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By rmcdouga Date 2017-05-22 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2017-05-22 Time 07:19 Sent To  
Notes
2017-05-22 08:07:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) THE GENERATOR TO SLAB ANCHORING DOCUMENTS FROM THE
 FLORIDA LICENSED ENGINEER IS REQUIRED TO BE SIGNED,
 SEALED AND DATED BY HIM. IN ADDITION TO THE DATE AND
 SEAL, THE ENGINEER'S HANDWRITTEN SIGNATURE IS REQUIRED
 ON THE DOCUMENTS, COPIES OR OTHER FASCIMILES ARE NOT
 ACCETABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 16:47 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 16:47 Sent To Z
Notes
2017-05-17 16:48:16ZONING MISSED TWO SET OF DRAWINGS WHEN SIGNING THEM.
 JLEAHY

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2017-05-22 Cont ID  
Sent By rmcdouga Date 2017-05-22 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2017-05-22 Time 08:07 Sent To  
Notes
2017-05-22 11:20:48G2427.8 (503.8) VENTING SYSTEM TERMINATION LOCATION.
 THE LOCATION OF VENTING SYSTEM TERMINATIONS SHALL
 COMPLY WITH THE FOLLOWING (SEE APPENDIX C):
 1. A MECHANICAL DRAFT VENTING SYSTEM SHALL TERMINATE AT
 LEAST 3 FEET (914 MM) ABOVE ANY FORCED-AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 2. A MECHANICAL DRAFT VENTING SYSTEM, EXCLUDING
 DIRECT-VENT APPLIANCES, SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR
 1 FOOT (305 MM) ABOVE ANY DOOR, OPERABLE WINDOW, OR
 GRAVITY AIR INLET INTO ANY BUILDING. THE BOTTOM OF THE
 VENT TERMINAL SHALL BE LOCATED AT LEAST 12 INCHES (305
 MM) ABOVE FINISHED GROUND LEVEL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-01 Cont ID  
Sent By rmcdouga Date 2017-06-01 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2017-05-31 Time 09:13 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-22 Cont ID  
Sent By rmcdouga Date 2017-05-22 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2017-05-10 Time 13:25 Sent To  
Notes
2017-05-11 13:25:11ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-15 Cont ID  
Sent By njwira Date 2017-05-15 Time 15:56 Rev Time 0.00
Received By njwira Date 2017-05-11 Time 16:37 Sent To E
Notes
***NONE***