Plan Review Details - Permit 17050420
Plan Review Stops For Permit 17050420
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 14:43 Rev Time 0.00
Received By shill Date 2018-09-22 Time 14:43 Sent To  
Notes
2018-09-22 14:44:38****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 ALL OTHER ITEMS OTHER THAN BMEP
  
 D. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED
 PRIOR TO C.O.
  
 E. IMPACT FEE ASSESSMENT, STAMP AND PAYMENT REQUIRED
 PRIOR TO PERMIT ISSUANCE.
  
 THE DESIGNER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-03-23 Cont ID  
Sent By jwitmer Date 2018-03-23 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2018-03-23 Time 09:59 Sent To  
Notes
2018-04-12 15:34:3404/12/18 MET WITH JOSE ALFONSO AND JIM WITMER TO GO
 OVER COMMENTS. JIM TALKED TO ARCHITECT OVER THE PHONE
 TO DISCUSS THE TYPE II CONSTRUCTION AND NONCOMBUSTIBLE
 MATERIALS.
2018-03-23 11:24:552014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: FRIDAY MARCH 23/2018
 ACTION: DENIED
  
 1) COMPLIED. UNITY OF TITLE FOR LOTS 5215, 5207 S.
 DIXIE AND 407 PUTNAM RD.
  
 2) COMPLIED: . 108.3* BUILDING PERMIT VALUATION.
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
 ADJUSTED VALUE FOR LISTED PERMITS BELOW $560,110.00.
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3A) PROVISO: ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE,
 THE CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY
 CERTIFICATE OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS
 INVOLVED AND IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER
 OF THE BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND
 REQUEST FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE
 ANIMAL HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD
 BE REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS
 NOT COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO
 THE BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION
 OF THE TCO, FEES ASSOCIATED WITH THE BOARD OF
 ADJUSTMENT & APPEAL ARE $100.00.
  
 3B)PROVISO: THE DESIGNER OF RECORD HAS SPOKEN WITH MR.
 SWOOPE AND MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS
 AND CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 3C) 4TH REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) .
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 OF THE 3 SETS OF PLANS, THE ONE SET MARKED FOR
 ENGINEERING SHOWS THE NEW CORRECTED FS-1 PLAN. PLEASE
 NOTE ONLY ONE OF THE THREE SETS OF PLANS UPDATES WITH
 NEW FIRE SPRINKLER PLANS. THE THIRD ISSUE THAT WILL
 NEED TO BE CORRECTED IS FOUND ON THE FS-1 PLAN. AS
 DEPICTED THE FIRE LINE WILL NOT BE INSTALLED UNTIL THE
 PHASE III SINCE IT IS SHOWN GOING THROUGH THE SOUTH END
 OF THE BUILDING. THE FIRE SPRINKLER WILL NEED TO BE IN
 THE ANIMAL HOSPITAL IN PHASE ONE! THE PLAN NEEDS TO BE
 ROUTED IN A WAY THAT THE FIRE LINE ENTERS THE BUILDING
 AT PHASE ONE AND THEN IS EXTENDED IN PHASE III.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) 3RD REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING THE COVERSHEET A0.00.
  
 3E) 3RD REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING A7.01 & A8.00
  
 3F) 3RD REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING SHEET S3.3 IN ONE SET OF PLANS.
  
 3G) COMPLIED.
  
 4-6) COMPLIED.
  
 7) 3RD REQUEST. ( 7A-7F) . 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B) .
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 SHEET S2.1 UPPER RIGHT CORNER OF THE SHEET, NOTES
 INDICATE THE USE OF 5/8 INCH PERFORMANCE RATED PLYWOOD.
 SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE USE OF 5/8
 INCH PLYWOOD. THE DESIGNER OF RECORD HAS DESIGNED THIS
 BUILDING TO BE CONSTRUCTION TYPE II-B. IN THE 2014
 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT TREATED WOOD
 SHALL BE PERMITTED IN ROOF CONSTRUCTION INCLUDING,
 GIRDERS, TRUSSES, FRAMING, AND DECKING. PLEASE CORRECT
 THE PLANS, TO FIRE RETARDANT TREATED WOOD.
  
 DETAILS STILL SHOWING EITHER 5/8 INCH CDX PLYWOOD OR
 3/4 INCH PLYWOOD AND WOOD TRUSSES ON THE TOWERS:
  
 7A) A5.01 DETAIL 3 5/8 INCH CDX PLYWOOD , WOOD OR METAL
 TRUSSES.
  
 7B) SHEETS, A4.00 NOTE #9 , A4.01 NOTE # 9 & A5.00 NOTE
 # 9 ALL STATE INCH CDX PLYWOOD WITH EITHER WOOD OR
 METAL TRUSSES.
  
 7C) SHEET S1.1 HEADING: PRE-ENGINEERED WOOD TRUSSES
 7D) SHEET 52.1 NOTES ON PLYWOOD AT LIGHT GAUGE NOTES
 5/8 INCH PLYWOOD.
  
 7E) SHEET S2.2 HIGH ROOF FRAMING WOOD TRUSSES AND 5/8
 INCH SHEATHING, NOTE 2 5/8 INCH WOOD SHEATHING
  
 7F) SHEET S3.3 DETAIL 5, 8, & 9 ALL INDICATE THE USE OF
 PLYWOOD SHEATHING. SEE COMMENT (3F).
  
 8) 3RD REQUEST. SHEET S2.1 THE BOTTOM TOWER (SOUTH) HAS
 A WALL SECTION DETAIL # 8/ S3.2. THE WALL SECTION ON
 THE OTHER SIDE OF THE TOWER DETAIL # 9/ S3.3, MISSING
 SHEET S3.3. DISCREPANCY IN PLANS.
  
 8A) 3RD REQUEST. DETAIL 8/S3.2 IS THE ROOF TOP CURB NOT
 THE WALL SECTION ON THE BAR JOIST, PLEASE CORRECT.
  
 8B) 3RD REQUEST. STILL MISSING THE S3.3 IN THE 3RD SET
 OF PLANS INDICATING ENGINEERING. . SEE COMMENT (3F).
  
 9) 3RD REQUEST. SHEET A 5.01 DETAIL # 3 THE UPPER ROOF
 DETAIL INDICATES SHEATHING IS TO BE ATTACHED TO
 PRE-FABRICATED WOOD TRUSSES OR METAL ROOF TRUSSES REFER
 TO STRUCTURAL DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 10-11) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. SHEET
 S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU SUPPORT.
 THE DETAIL DOES SHOW THE ATTACHMENT OF THE CURB TO THE
 ROOF FRAMING MEMBERS AND A MAXIMUM CURB HEIGHT OF 14
 INCHES FROM THE FINISH ROOF DECK TO THE TOP OF THE
 CURB, THE DETAIL DOES NOT SHOW THE OVERLAP OF THE TOP
 OF THE RTU CURB, AS DETAILED ON M3. THE BOTTOM OF THE
 RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR
 WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT. FBC-B
 1509.6.5 MECHANICAL UNITS.
  
  
 12) 4TH REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 COMMENTS 7, 8 & 9 ALL DEAL WITH WOOD SHEATHING STATED
 THROUGHOUT THE PLANS.
 RESPONSE INDICATES REFER TO THE ATTACHED DENSEGLASS
 FLORIDA PRODUCT APPROVAL.
 SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH
 DENSGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL SHOWING
 THE TESTING AND TO WHAT DESIGN PRESSURES THE DENSGLASS
 CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS & CLADDING.
 RESPONSE INDICATES SEE ATTACHED DENSGLASS PRODUCT
 APPROVAL. THERE WERE NO PRODUCT APPROVALS AT ALL IN
 THIS SUBMISSION, THIS CAN BE A DEFERRED SUBMITTAL.
  
 13) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 15) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 16) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PROVISO/
 DEFERRED SUBMITTAL. 107 .3.4.2.
 EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 (MIAMI-DADE AND THE FLORIDA APPROVAL BOTH HAVE EFIS
 SYSTEMS UNDER THE PRODUCT APPROVAL SYSTEMS),
 MANUFACTURERS PRODUCT DATA FOR THE SYSTEM TO BE
 INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE
 NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE
 OF RIGID INSULATION BOARD OVER CORRUGATED METAL
 DECKING. PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE DESIGNER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-03-06 Cont ID  
Sent By jwitmer Date 2018-03-06 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2018-03-06 Time 09:40 Sent To  
Notes
2018-03-06 13:21:422014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MARCH 06/2018
 ACTION: DENIED
  
 1) COMPLIED. UNITY OF TITLE FOR LOTS 5215, 5207 S.
 DIXIE AND 407 PUTNAM RD.
  
 2) COMPLIED: . 108.3* BUILDING PERMIT VALUATION.
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
 ADJUSTED VALUE FOR LISTED PERMITS BELOW $560,110.00.
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3A) PROVISO: ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE,
 THE CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY
 CERTIFICATE OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS
 INVOLVED AND IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER
 OF THE BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND
 REQUEST FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE
 ANIMAL HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD
 BE REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS
 NOT COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO
 THE BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION
 OF THE TCO, FEES ASSOCIATED WITH THE BOARD OF
 ADJUSTMENT & APPEAL ARE $100.00.
  
 3B)PROVISO: THE DESIGNER OF RECORD HAS SPOKEN WITH MR.
 SWOOPE AND MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS
 AND CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 3C) 3RD REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) .
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 OF THE 3 SETS OF PLANS, THE ONE SET MARKED FOR
 ENGINEERING SHOWS THE NEW CORRECTED FS-1 PLAN. PLEASE
 NOTE ONLY ONE SET OF PLANS UPDATES WITH NEW FIRE
 SPRINKLER PLANS. THE THIRD ISSUE THAT WILL NEED TO BE
 CORRECTED IS FOUND ON THE FS-1 PLAN. AS DEPICTED THE
 FIRE LINE WILL NOT BE INSTALLED UNTIL THE PHASE III
 SINCE IT IS SHOWN GOING THROUGH THE SOUTH END OF THE
 BUILDING. THE FIRE SPRINKLER WILL NEED TO BE IN THE
 ANIMAL HOSPITAL IN PHASE ONE! THE PLAN NEEDS TO BE
 ROUTED IN A WAY THAT THE FIRE LINE ENTERS THE BUILDING
 AT PHASE ONE AND THEN IS EXTENDED IN PHASE III.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING THE COVERSHEET A0.00.
  
 3E) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING A7.01 & A8.00
  
 3F) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING SHEET S3.3 IN ONE SET OF PLANS.
  
 3G) 2ND REQUEST. THE 1 SET OF PLANS MARKED FOR
 ENGINEERING HAS C1-C6 DATED 09/28/17/ (2) SETS OF
 PLANS ARE MISSING THE CIVIL DRAWINGS C1-C6.
  
 4-6) COMPLIED.
  
 7) 2ND REQUEST. SHEET S2.1 UPPER RIGHT CORNER OF THE
 SHEET, NOTES INDICATE THE USE OF 5/8 INCH PERFORMANCE
 RATED PLYWOOD. SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE
 USE OF 5/8 INCH PLYWOOD. THE DESIGNER OF RECORD HAS
 DESIGNED THIS BUILDING TO BE CONSTRUCTION TYPE II-B. IN
 THE 2014 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT
 TREATED WOOD SHALL BE PERMITTED IN ROOF CONSTRUCTION
 INCLUDING, GIRDERS, TRUSSES, FRAMING, AND DECKING.
 PLEASE CORRECT THE PLANS, TO FIRE RETARDANT TREATED
 WOOD.
  
 DETAILS STILL SHOWING EITHER 5/8 INCH CDX PLYWOOD OR ?
 INCH PLYWOOD AND WOOD TRUSSES ON THE TOWERS:
  
 7A) A5.01 DETAIL 3 5/8 INCH CDX PLYWOOD , WOOD OR METAL
 TRUSSES.
  
 7B) SHEETS, A4.00 NOTE #9 , A4.01 NOTE # 9 & A5.00 NOTE
 # 9 ALL STATE ? INCH CDX PLYWOOD WITH EITHER WOOD OR
 METAL TRUSSES.
  
 7C) SHEET S1.1 HEADING: PRE-ENGINEERED WOOD TRUSSES
 7D) SHEET 52.1 NOTES ON PLYWOOD AT LIGHT GAUGE NOTES
 5/8 INCH PLYWOOD.
  
 7E) SHEET S2.2 HIGH ROOF FRAMING WOOD TRUSSES AND 5/8
 INCH SHEATHING, NOTE 2 5/8 INCH WOOD SHEATHING
  
 7F) SHEET S3.3 DETAIL 5, 8, & 9 ALL INDICATE THE USE OF
 PLYWOOD SHEATHING. SEE COMMENT (3F).
  
 8) SEMI-COMPLIED. SHEET S2.1 THE BOTTOM TOWER (SOUTH)
 HAS A WALL SECTION DETAIL # 8/ S3.2. THE WALL SECTION
 ON THE OTHER SIDE OF THE TOWER DETAIL # 9/ S3.3,
 MISSING SHEET S3.3. DISCREPANCY IN PLANS.
  
 8A) DETAIL 8/S3.2 IS THE ROOF TOP CURB NOT THE WALL
 SECTION ON THE BAR JOIST, PLEASE CORRECT.
  
 8B) STILL MISSING THE S3.3 IN THE 3RD SET OF PLANS
 INDICATING ENGINEERING. . SEE COMMENT (3F).
  
 9) 2ND REQUEST. SHEET A 5.01 DETAIL # 3 THE UPPER ROOF
 DETAIL INDICATES SHEATHING IS TO BE ATTACHED TO
 PRE-FABRICATED WOOD TRUSSES OR METAL ROOF TRUSSES REFER
 TO STRUCTURAL DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 10-11) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. SHEET
 S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU SUPPORT.
 THE DETAIL DOES SHOW THE ATTACHMENT OF THE CURB TO THE
 ROOF FRAMING MEMBERS AND A MAXIMUM CURB HEIGHT OF 14
 INCHES FROM THE FINISH ROOF DECK TO THE TOP OF THE
 CURB, THE DETAIL DOES NOT SHOW THE OVERLAP OF THE TOP
 OF THE RTU CURB, AS DETAILED ON M3. THE BOTTOM OF THE
 RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR
 WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT. FBC-B
 1509.6.5 MECHANICAL UNITS.
  
  
 12) 3RDND REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 RESPONSE INDICATES REFER TO THE ATTACHED DENSEGLASS
 FLORIDA PRODUCT APPROVAL.
 SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH
 DENSGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL SHOWING
 THE TESTING AND TO WHAT DESIGN PRESSURES THE DENSGLASS
 CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS & CLADDING.
 RESPONSE INDICATES SEE ATTACHED DENSGLASS PRODUCT
 APPROVAL. THERE WERE NO PRODUCT APPROVALS AT ALL IN
 THIS SUBMISSION, THIS CAN BE A DEFERRED SUBMITTAL.
  
 13) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 15) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 16) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PROVISO/
 DEFERRED SUBMITTAL. 107 .3.4.2.
 EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 (MIAMI-DADE AND THE FLORIDA APPROVAL BOTH HAVE EFIS
 SYSTEMS UNDER THE PRODUCT APPROVAL SYSTEMS),
 MANUFACTURERS PRODUCT DATA FOR THE SYSTEM TO BE
 INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE
 NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE
 OF RIGID INSULATION BOARD OVER CORRUGATED METAL
 DECKING. PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE DESIGNER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2017-12-18 Time 16:38 Sent To  
Notes
2017-12-19 09:27:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. DEC. 19/2017
 ACTION: DENIED
  
 1) COMPLIED. UNITY OF TITLE FOR LOTS 5215, 5207 S.
 DIXIE AND 407 PUTNAM RD.
  
 2) 2ND REQUEST. 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 WITH REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY
 THE INTERNATIONAL CODE CONGRESS.
  
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) PLEASE BE AWARE OF PROBLEMS INVOLVED WITH THE PHASED
 PERMITTING;
 3A) PROVISO: ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE,
 THE CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY
 CERTIFICATE OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS
 INVOLVED AND IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER
 OF THE BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND
 REQUEST FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE
 ANIMAL HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD
 BE REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS
 NOT COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO
 THE BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION
 OF THE TCO, FEES ASSOCIATED WITH THE BOARD OF
 ADJUSTMENT & APPEAL ARE $100.00.
  
 3B)PROVISO: A SECOND ISSUE IS HOW THE COUNTY IMPACT
 FEES ARE TO BE PAID FOR THE WHOLE BUILDING BEFORE THE
 DEMOLITION OF THE EXISTING BUILDING AND CREDITS THAT
 WOULD BE DUE. THE CONTRACTOR OR OWNER WILL NEED TO
 DISCUSS THIS WITH MR. SWOOP 561-233-2014 AT PALM BEACH
 COUNTY IMPACT FEE OFFICE.
  
 3C) SEMI-COMPLIED. PLEASE NOTE ONLY ONE SET OF PLANS
 UPDATES WITH NEW FIRE SPRINKLER PLANS. THE THIRD ISSUE
 THAT WILL NEED TO BE CORRECTED IS FOUND ON THE FS-1
 PLAN. AS DEPICTED THE FIRE LINE WILL NOT BE INSTALLED
 UNTIL THE PHASE III SINCE IT IS SHOWN GOING THROUGH THE
 SOUTH END OF THE BUILDING. THE FIRE SPRINKLER WILL NEED
 TO BE IN THE ANIMAL HOSPITAL IN PHASE ONE! THE PLAN
 NEEDS TO BE ROUTED IN A WAY THAT THE FIRE LINE ENTERS
 THE BUILDING AT PHASE ONE AND THEN IS EXTENDED IN PHASE
 III. ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) NEW COMMENT. ONE SET OF ARCHITECTURAL PLANS MISSING
 THE COVERSHEET A0.00.
  
 3E) NEW COMMENT. ONE SET OF PLANS MISSING A7.01 & A8.00
  
 3F) NEW COMMENT. MISSING SHEET S3.3 IN ONE SET OF
 PLANS.
  
 3G) NEW COMMENT. ONE SET OF PLANS HAS (2) SETS OF
 C1-C6) DATED 09/28/17.
  
 4-7) COMPLIED.
  
 8) SEMI-COMPLIED. SHEET S2.1 THE BOTTOM TOWER (SOUTH)
 HAS A WALL SECTION DETAIL # 9/ S3.2. THE WALL SECTION
 ON THE OTHER SIDE OF THE TOWER DETAIL # 9/ S3.3,
 MISSING SHEET S3.3 CANNOT VALIDATE DETAIL FOR CODE
 COMPLIANCE.
  
 9) COMPLIED.
  
 10-11) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. SHEET
 S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU SUPPORT.
 THE DETAIL DOES SHOW THE ATTACHMENT OF THE CURB TO THE
 ROOF FRAMING MEMBERS AND A MAXIMUM CURB HEIGHT OF 14
 INCHES FROM THE FINISH ROOF DECK TO THE TOP OF THE
 CURB, THE DETAIL DOES NOT SHOW THE OVERLAP OF THE TOP
 OF THE RTU CURB, AS DETAILED ON M3. THE BOTTOM OF THE
 RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR
 WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT. FBC-B
 1509.6.5 MECHANICAL UNITS.
  
  
 12) 2ND REQUEST. SHEET A 5.00 NOTE 25 INDICATES THE USE
 OF 5/8 INCH DENSGLASS SHEATHING, PROVIDE A PRODUCT
 APPROVAL SHOWING THE TESTING AND TO WHAT DESIGN
 PRESSURES THE DENSGLASS CAN BE INSTALLED. 1609.6.4.4.1
 COMPONENTS & CLADDING. RESPONSE INDICATES SEE ATTACHED
 DENSGLASS PRODUCT APPROVAL. THERE WERE NO PRODUCT
 APPROVALS AT ALL IN THIS SUBMISSION, THIS CAN BE A
 DEFERRED SUBMITTAL.
  
 13) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 15) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 16) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PROVISO/
 DEFERRED SUBMITTAL. 107 .3.4.2.
 EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 (MIAMI-DADE AND THE FLORIDA APPROVAL BOTH HAVE EFIS
 SYSTEMS UNDER THE PRODUCT APPROVAL SYSTEMS),
 MANUFACTURERS PRODUCT DATA FOR THE SYSTEM TO BE
 INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE
 NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE
 OF RIGID INSULATION BOARD OVER CORRUGATED METAL
 DECKING. PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE DESIGNEER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISITNG VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jwitmer Date 2017-08-09 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2017-08-08 Time 07:28 Sent To  
Notes
2017-08-09 08:26:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. AUGUST 08/2017
 ACTION: DENIED
  
 1) THE PLANS INDICATE THAT THERE IS A UNITY OF TITLE
 FOR LOTS 5215, 5207 S. DIXIE AND 407 PUTNAM RD. THE
 PERMIT APPLICATION ALSO STATES THAT THERE IS A UNITY OF
 TITLE ON FILE. A RECORDED COPY OF THE UNITY OF TITLE
 NEEDS TO BE SUBMITTED WITH THIS PLAN TO SHOW PROOF THAT
 THE BUILDING DOES NOT TRANSGRESS PROPERTY LINES.
 2014 FBC-B TABLE 602.
  
 2) 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 WITH REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY
 THE INTERNATIONAL CODE CONGRESS.
  
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) PLEASE BE AWARE OF PROBLEMS INVOLVED WITH THE PHASED
 PERMITTING;
 3A) ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE, THE
 CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY CERTIFICATE
 OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS INVOLVED AND
 IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER OF THE
 BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND REQUEST
 FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE ANIMAL
 HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD BE
 REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS NOT
 COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO THE
 BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION OF
 THE TCO, FEES ASSOCIATED WITH THE BOARD OF ADJUSTMENT &
 APPEAL ARE $100.00.
  
 3B) A SECOND ISSUE IS HOW THE COUNTY IMPACT FEES ARE TO
 BE PAID FOR THE WHOLE BUILDING BEFORE THE DEMOLITION OF
 THE EXISTING BUILDING AND CREDITS THAT WOULD BE DUE.
 THE CONTRACTOR OR OWNER WILL NEED TO DISCUSS THIS WITH
 MR. SWOOP 561-233-2014 AT PALM BEACH COUNTY IMPACT FEE
 OFFICE.
  
 3C) THE THIRD ISSUE THAT WILL NEED TO BE CORRECTED IS
 FOUND ON THE FS-1 PLAN. AS DEPICTED THE FIRE LINE WILL
 NOT BE INSTALLED UNTIL THE PHASE III SINCE IT IS SHOWN
 GOING THROUGH THE SOUTH END OF THE BUILDING. THE FIRE
 SPRINKLER WILL NEED TO BE IN THE ANIMAL HOSPITAL IN
 PHASE ONE! THE PLAN NEEDS TO BE ROUTED IN A WAY THAT
 THE FIRE LINE ENTERS THE BUILDING AT PHASE ONE AND THEN
 IS EXTENDED IN PHASE III. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET A 1.00 THE LIFE SAFETY PLAN:
 4A) GENERAL LIFE SAFETY PLAN NOTE # 4 INDICATES THE
 MAXIMUM ELEVATION CHANGE AT ALL BUILDING ENTRANCE DOORS
 (INCLUDING THRESHOLDS) AND ALONG THE REQUIRED MEANS OF
 EGRESS SHALL BE EQUAL TO OR LESS THAN ? INCH. THE LIFE
 SAFETY PLAN DOES NOT PROVIDE EXIT SIGNS DIRECTING WHICH
 DOOR IS THE REQUIRED MEANS OF EGRESS. SHEET E2 SHOWS
 EXIT LIGHT AND BATTERY BACKUP LIGHTS OVER BOTH EXITS.
 THE COMMON PATH OF TRAVEL IS NOT EXCEEDED (75 FEET
 LIMIT). WHEN YOU GO TO THE C-1 SHEET SHOWS AT THE
 ANIMAL HOSPITAL, BAY # 1 AND BAY # 2 APPROXIMATELY A
 CHANGE IN GRADE FROM THE LANDING TO THE CITY SIDEWALK.
 THE ELEVATION TAGS ON SHEET C1 SHOW A 2 STEP RISERS
 APPROXIMATE 4 ? INCHES EACH. PLEASE SHOW THIS SAME
 CHANGE IN ELEVATION ON THE LIFE SAFETY PLAN A 1.00.
  
 4B) WITH THE CHANGE IN GRADE AT THE EAST SIDE OF THE
 BUILDING AND CLOSENESS TO THE CITY SIDEWALK PLEASE
 PROVIDE HOW COMPLIANCE WILL BE MET WITH SECTION 1003.5
 OF THE 2014 FBC-B OR EXCEPTION # 2?
  
 4C) DEPENDING ON THE OUTCOME OF COMMENT 4B) IF THE RAMP
 METHOD OF COMPLIANCE IS NOT USED THEN PLEASE PROVIDE
 COMPLIANCE WITH SECTION 216.4.3 DIRECTIONAL SIGNAGE OF
 WHERE THE ACCESSIBLE ENTRANCE IS LOCATED.
  
 5) SHEET C-1. FOR THE HANDICAPPED PARKING SPACE AND
 ACCESS AISLE PLEASE PROVIDE ELEVATION MARKERS AT THE
 FOUR CORNERS TO VERIFY COMPLIANCE WITH 2014
 ACCESSIBILITY CODE 502.4 AND EXCEPTION SLOPES NOT
 STEEPER THAN 1:48 SHALL BE PERMITTED.
  
 6) SHEETS A 4.00, A 4.01 & S1.4, NONE OF THESE SHEETS
 INDICATE THE SLOPE OF THE UPPER ROOF, WILL NEED THE
 SLOPE OF THE UPPER ROOF TO VERIFY PRESSURES ON THE
 UPPER ROOF, MEAN ROOF IS GIVEN, THANK YOU. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED TO VERIFY PRESSURES.
  
 7) SHEET S2.1 UPPER RIGHT CORNER OF THE SHEET, NOTES
 INDICATE THE USE OF 5/8 INCH PERFORMANCE RATED PLYWOOD.
 SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE USE OF 5/8
 INCH PLYWOOD. THE DESIGNER OF RECORD HAS DESIGNED THIS
 BUILDING TO BE CONSTRUCTION TYPE II-B. IN THE 2014
 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT TREATED WOOD
 SHALL BE PERMITTED IN ROOF CONSTRUCTION INCLUDING,
 GIRDERS, TRUSSES, FRAMING, AND DECKING. PLEASE CORRECT
 THE PLANS, TO FIRE RETARDANT TREATED WOOD.
  
 8) SHEET S2.1 THE BOTTOM TOWER (SOUTH) HAS A WALL
 SECTION DETAIL # 8/ S3.2, PLEASE CORRECT FOR A WALL
 SECTION. TYPO, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9A) SHEET A 5.01 DETAIL # 3 THE UPPER ROOF DETAIL
 INDICATES SHEATHING IS TO BE ATTACHED TO PRE-FABRICATED
 WOOD TRUSSES OR METAL ROOF TRUSSES REFER TO STRUCTURAL
 DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 9B) SHEET S2.2 IN THE HIGH ROOF FRAMING PLAN THE
 TRUSSES ARE INDICATED TO BE PRE-MANUFACTURED WOOD
 TRUSSES. TYPE II-B. PLEASE UPDATE PLANS THAT THE
 TRUSSES HAVE TO BE FIRE RETARDANT TREATED TRUSSES. WE
 WILL ALSO NEED CONFIRMATION FOR THE TRUSS PLANT THEY
 WILL BUILD WOOD FIRE RETARDANT TREATED WOOD TRUSSES
 BECAUSE OF THE FIRE RETARDANT IMPREGNATED TREATMENT.
 THAT THE SALTS WILL NOT AFFECT THE TEETH IN THE TRUSS
 PANEL FASTENERS. IN THE 2014 FBC-B SECTION 603.1.1.1.3
 FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN ROOF
 CONSTRUCTION INCLUDING, GIRDERS, TRUSSES, FRAMING, AND
 DECKING. PLEASE CORRECT THE PLANS, TO FIRE RETARDANT
 TREATED WOOD.
 10) SHEET S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU
 SUPPORT. THE DETAIL DOES SHOW THE ATTACHMENT OF THE
 CURB TO THE ROOF FRAMING MEMBERS AND A MAXIMUM CURB
 HEIGHT OF 14 INCHES FROM THE FINISH ROOF DECK TO THE
 TOP OF THE CURB, THE DETAIL DOES NOT SHOW THE OVERLAP
 OF THE TOP OF THE RTU CURB, AS DETAILED ON M3. THE
 BOTTOM OF THE RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE
 ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH
 THE UNIT. FBC-B 1509.6.5 MECHANICAL UNITS.
  
 11) SHEET M-3 ROOF TOP MOUNTING DETAIL SHOWS THE USE OF
 A HURRICANE STRAP BEING USED FOR ANCHORING OF THE RTU
 TO THE CURB. PLEASE PROVIDE THE MANUFACTURER OF THE
 STRAP DETAIL WHERE THIS IS AN APPROVED METHOD OF USE.
 IT APPEARS THE STRAP IS BEING BENT AT 90 DEGREE ANGLES.
 SPECIFY MANUFACTURER AND MODEL OF STRAP AND THE AMOUNT
 OF ANCHORS AND SIZE OF ANCHORS.
 FOR ALL ROOF TOP EQUIPMENT, CURBS DETAILED ATTACHMENT
 TO THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 12) SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH
 DENSEGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL
 SHOWING THE TESTING AND TO WHAT DESIGN PRESSURES THE
 DENSEGLASS CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 13) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 15A) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PLEASE NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM
 AND THE USE OF RIGID INSULATION BOARD OVER CORRUGATED
 METAL DECKING. PLEASE SUPPLY THE INSULATION PRODUCT
 APPROVAL, DEPENDING ON THE TYPE OF INSULATION BOARD
 INSTALLED ADDITIONAL MANUFACTURERS SPECIFICATION WILL
 PROVIDE THE VARIOUS WAYS THE INSULATION BOARD CAN BE
 VENTILATED. NOTE THE DESIGNER OF RECORD HAS NOT
 SPECIFIED WHAT TYPE OF VENTING WILL BE REQUIRED FOR
 THIS PROJECT, NOR IS THERE ANY SPEC LISTED UNDER THE
 STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) FOR ALL ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 14:05 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-29 Cont ID  
Sent By jpearson Date 2018-03-29 Time 11:11 Rev Time 0.00
Received By jpearson Date 2018-03-29 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-21 Cont ID  
Sent By jpearson Date 2017-12-21 Time 09:47 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 09:15 Sent To  
Notes
2017-12-21 09:33:54ALL COMMENTS HAVE BEEN ADDRESSED SATISFACTORILY.
 HOWEVER, THE PLAN SHEETS ARE ALL STAPLED TOGETHER IN
 ONE SET AND NOT IN PROPER ORDER. PLANS NEED TO BE
 ORGANIZED CORECTLY BEFORE APPROVAL IS GRANTED. FBC
 107.1, 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By jpearson Date 2017-08-17 Time 13:35 Rev Time 0.00
Received By jpearson Date 2017-08-17 Time 13:35 Sent To  
Notes
2017-08-17 13:34:29CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 2. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS.
 NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. AN ESTIMATE FOR RETAIL SPACES BASED ON SQUARE
 FOOTAGE WILL BE ACCEPTABLE IF USE IS NOT DETERMINED.
 NEC 220
 6. PROVIDE AUTOMATIC CONTROL FOR SHOW WINDOW OUTLETS
 PER ENERGY CODE. FBC C405.2.3
 7. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE FOR EACH SPACE. FBC
 C405.5
 8. PANEL A SHOWS THE WATER HEATER BREAKER SIZED AT 30
 AMPS, WHICH IS TOO LARGE. BREAKER SHOULD BE SIZED AT
 125% OF LOAD. PROVIDE CORRECTION. NEC 422.13
 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE FOR THE RETAIL BAYS. FBC
 C405.2.2, 405.2.2.2
 10. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE FOR THE COVERED PATIO AREA. FBC
 C405.2.4
 11. NAME OF PANELS ON POWER PLAN IS DIFFERENT THAN
 PANEL SCHEDULES AND RISER DIAGRAM. PROVIDE CORRECTION.
 FBC 107.2.1
 12. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. FBC 105.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2018-09-12 Cont ID  
Sent By RRossano Date 2018-09-12 Time   Rev Time 1.00
Received By rrossano Date 2018-09-12 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2018-04-04 Cont ID  
Sent By shill Date 2018-04-04 Time 07:48 Rev Time 0.00
Received By shill Date 2018-04-04 Time 07:48 Sent To  
Notes
2018-04-04 07:48:36CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-01-23 Cont ID  
Sent By mgonzale Date 2018-01-23 Time   Rev Time 0.00
Received By mgonzale Date 2018-01-23 Time   Sent To  
Notes
2018-01-23 10:00:23SEPARATE PERMIT REQUIRED THRU CITY OF WEST PALM BEACH
 ENGINEERING PERMITS.
  
 [email protected]
 (561)818-1322

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-16 Cont ID  
Sent By mgonzale Date 2017-05-16 Time   Rev Time 1.00
Received By mgonzale Date 2017-05-16 Time   Sent To I
Notes
2017-05-16 13:41:35SEPARATE PERMIT REQUIRED THRU CITY OF WEST PALM BEACH
 ENGINEERING PERMITS.
  
 [email protected]
 (561)517-7270
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-03-13 Cont ID  
Sent By pleduc Date 2018-03-13 Time   Rev Time 0.00
Received By pleduc Date 2018-03-13 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-02-28 Cont ID  
Sent By pleduc Date 2018-02-28 Time   Rev Time 0.00
Received By pleduc Date 2018-02-28 Time 09:47 Sent To  
Notes
2018-02-28 10:28:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 MONITORED AND SUPERVISED PER NFPA 101 AND THE BUILDING
 CODE.
  
  
 NFPA 101, CHAPTER 9,
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 SUPERVISORY ATTACHMENTS SHALL BE INSTALLED AND
 MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE ALARM AND SIGNALING CODE, AND A
 DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO
 INDICATE A CONDITION THAT WOULD IMPAIR THE SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
  
 FL BUILDING CODE
  
 901.6 SUPERVISORY SERVICE.
  
 WHERE REQUIRED, FIRE PROTECTION SYSTEMS SHALL BE
 MONITORED BY AN APPROVED SUPERVISING STATION IN
 ACCORDANCE WITH NFPA 72.
  
 901.6.1 AUTOMATIC SPRINKLER SYSTEMS.
  
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE MONITORED BY AN
 APPROVED SUPERVISING STATION.
  
  
  
 PLEASE ENSURE THE REQUIRED COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-12-04 Cont ID  
Sent By pleduc Date 2017-12-04 Time   Rev Time 0.00
Received By pleduc Date 2017-12-04 Time 11:23 Sent To  
Notes
2017-12-04 13:50:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 PREVIOUS COMMENT # 3 IS RE-POSTED HERE FOR
 INFORMATIONAL PURPOSES:
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL
 LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE
 ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT
 READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS.
  
 PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING
 NOTE OF COMPLAINCE.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PER NFPA 101 CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.7.2.2 ALARM SIGNAL TRANSMISSION. WHERE SUPERVISION OF
 AUTOMATIC SPRINKLER SYSTEMS IS PROVIDED IN ACCORDANCE
 WITH ANOTHER PROVISION OF THIS CODE, WATERFLOW ALARMS
 SHALL BE TRANSMITTED TO AN APPROVED, PROPRIETARY
 ALARM-RECEIVING FACILITY, A REMOTE STATION, A CENTRAL
 STATION, OR THE FIRE DEPARTMENT. SUCH CONNECTION SHALL
 BE IN ACCORDANCE WITH 9.6.1.3.
  
  
 A FIRE ALARM SYSTEM COMPLYING WITH THE ABOVE CODE SHALL
 BE INSTALLED.
  
  
 NEW COMMENT
  
 1) THE REVISED SHEETS APPEAR TO ALL STAPLED TOGETHER
 AND IN RANDOM ORDER. THEY HAVE NOT BEEN PROPERLY
 INSERTED INTO THE ORIGINAL SET. IT IS UCLEAR WHAT THE
 FINAL SET IS OR WHAT IS REPRESENTED OF THE OFFICIAL
 FINAL SET.
  
 PLEASE CORRECT OR JUSTIFY
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By pleduc Date 2017-07-28 Time   Rev Time 0.00
Received By pleduc Date 2017-07-27 Time 13:53 Sent To  
Notes
2017-07-27 14:47:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1.00 THERE ARE NO INDICATIONS OF REVEIW AND/OR
 COMPLIANCE WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLAINCE.
  
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL
 LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE
 ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT
 READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS.
  
 PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING
 NOTE OF COMPLAINCE.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 4) SHEET A 4.00 - THE ROOF TRUSS ARE OF LIGHTWEIGHT
 TRUSS DESIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 5) SHEET 6.00 - THE DOOR SCHEDULE INDICATES HARDWARE
 AND LOCKS/DEAD BOLTS ON THE EXIT DOORS.
  
 ALL EXIT HARWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS.
  
 PER CHAPTER 38, NEW BUSINESS
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PER CHAPTER, 36, NEW MERCANTILE
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED. 7.2.1.5.5.2 THE
 ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1 SHALL BE
 PERMITTED TO BE REVOKED BY THE AUTHORITY HAVING
 JURISDICTION FOR CAUSE.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF SPEC SHEETS THAT
 WILL INDICATE COMPLIANCE WITH THE REQUIRMENTS.
  
  
  
  
 6) SHEET E 1 - THIS IS RELATED TO # 3 ABOVE. THERE ARE
 NO INDICATIONS ON THE ELECTRICAL PLAN SHEETS OF A FIRE
 ALARM SYSTEM OR EQUIPMENT.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF COMPLAINCE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 15:03 Rev Time 0.00
Received By shill Date 2018-08-09 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-04-04 Cont ID  
Sent By shill Date 2018-04-04 Time 07:49 Rev Time 0.00
Received By shill Date 2018-03-08 Time 13:13 Sent To  
Notes
2018-03-09 13:13:26C32

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-09 Cont ID  
Sent By lmarchan Date 2018-03-09 Time 13:09 Rev Time 0.00
Received By lmarchan Date 2018-02-22 Time 11:00 Sent To  
Notes
2018-02-23 11:00:14C32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-23 Cont ID  
Sent By cpuell Date 2018-01-23 Time 11:42 Rev Time 0.00
Received By cpuell Date 2017-11-30 Time 13:43 Sent To  
Notes
2017-12-01 13:43:41C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By skennedy Date 2017-07-25 Time 11:32 Sent To  
Notes
2017-07-25 12:18:27C34
2017-07-25 11:33:16FEES WERE PAID, PLACING INTO REVIEW CYCLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 15:02 Rev Time 0.00
Received By shill Date 2018-09-22 Time 15:02 Sent To  
Notes
2018-09-22 15:03:26PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 05:57 Sent To  
Notes
2017-12-19 09:20:40BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE DESIGNEER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISITNG VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jwitmer Date 2017-08-09 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2017-08-08 Time 07:28 Sent To  
Notes
2017-08-09 08:27:18COUNTY IMPACT FEES ARE TO BE PAID FOR THE WHOLE
 BUILDING BEFORE THE DEMOLITION OF THE EXISTING BUILDING
 AND CREDITS THAT WOULD BE DUE. THE CONTRACTOR OR OWNER
 WILL NEED TO DISCUSS THIS WITH MR. SWOOP 561-233-2014
 AT PALM BEACH COUNTY IMPACT FEE OFFICE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-22 Cont ID  
Sent By ccole Date 2018-03-22 Time 09:40 Rev Time 0.00
Received By ccole Date 2018-03-22 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-22 Cont ID  
Sent By ccole Date 2017-12-22 Time 11:56 Rev Time 0.00
Received By ccole Date 2017-12-22 Time 11:48 Sent To  
Notes
2017-12-22 11:59:132ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050420
 12/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED MECHANCIAL PLAN IS NOT IN COMPLIANCE.
 PLEASE SEE 1ST REVIEW COMMENT PRINTED BELOW:
  
 "MECHANICAL EXHAUST AT A RATE OF 0.90 CFMS PER SQUARE
 FOOT IS REQUIRED FOR ALL ANIMAL ROOMS OR SPACES OF THE
 PROPOSED ANIMAL HOSPITAL, AND RECIRCULATION OF AIR FROM
 THOSE ROOMS OR SPACES IS PROHIBITED- SEE TABLE 403.3
 AND FOOTNOTE B. PLEASE CORRECT THE PLAN ACCORDINGLY."
  
 THE REVISED PLAN SHOWS A 300 CFM EXHAUST FAN IN THE LAB
 ROOM, HOWEVER IT IS NOT SIZED LARGE ENOUGH TO EXHAUST
 ALL ANIMAL AREAS OF THE OCCUPANCY, AND IS NOT LOCATED
 WHERE IT CAN ACTUALLY PROVIDE EXHAUST VENTILATION FOR
 ALL THE ANIMAL ROOMS AND AREAS. IN ADDITION, THE PLAN
 IS STILL INDICATING AIR FROM THE ANIMAL AREAS
 RECIRCULATING INTO THE WAITING ROOM, RECEPTION ROOM,
 CORRIDOR, AND
  
 RESTROOM WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE
 B., AND SECTION 403.2.1 ITEM #3. "WHERE MECHANICAL
 EXHAUST IS REQUIRED BY NOTE B IN TABLE 403.3,
 RECIRCULATION OF AIR FROM SUCH SPACES SHALL BE
 PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES SHALL BE
 EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT REQUIRED
 BY TABLE 403.3. "
  
 PLEASE REVISE THE PLAN TO SHOW THE REQUIRED EXHAUST
 SYSTEM, AND INCLUDE BOTH AN EXHAUST VENTILATION
 CALCULATION AND AN AIR BALANCE CALCULATION.
  
 ADVISORY: DUE TO THE LARGE PERCENTAGE OF EXHAUST AND
 MAKEUP AIR REQUIRED FOR THE OCCUPANCY, AN ERV WILL MOST
 LIKELY BE REQUIRED. THE ENGINEER OF RECORD SHOULD
 REVIEW SECTION AND TABLE C403.2.6 FBC-14 ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 12:47 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 12:46 Sent To  
Notes
2017-08-24 13:33:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050420
 8/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MECHANICAL EXHAUST AT A RATE OF 0.90 CFMS PER SQUARE
 FOOT IS REQUIRED FOR ALL ANIMAL ROOMS OR SPACES OF THE
 PROPOSED ANIMAL HOSPITAL, AND RECIRCULATION OF AIR FROM
 THOSE ROOMS OR SPACES IS PROHIBITED- SEE TABLE 403.3
 AND FOOTNOTE B. PLEASE CORRECT THE PLAN ACCORDINGLY.
  
 2) M-3: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 COMPLETE ENGINEERING FOR INSTALLATION OF THE NEW RTU.
 MISSING FROM THE DETAIL ARE: LENGTH DIMENSIONS OF THE
 HURRICANE STRAPS, NUMBER OF STRAPS TO BE INSTALLED AND
 PLACEMENT OF THE STRAPS, PLACEMENT OF THE L-ANGLES; AND
 FOR THE CURB TO ROOF STRUCTURE ATTACHEMENT- TYPE AND
 SIZE OF ANCHORS, AND NUMBER AND PLACEMENT OF ANCHORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-09-13 Cont ID  
Sent By gjohnson Date 2018-09-13 Time 17:07 Rev Time 0.00
Received By gjohnson Date 2018-09-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-03-27 Cont ID  
Sent By tklarge Date 2018-03-27 Time 14:45 Rev Time 0.00
Received By tklarge Date 2018-03-27 Time 06:13 Sent To  
Notes
2018-03-27 11:14:171) THE WATER SUPPLY VALVES FOR THE STACKABLE
 WASHER/DRYER SHALL BE ACCESSIBLE PER THE 2014
 FBC-PLUMBING SEC.606.3.
 2) INDICATE ON THE PLANS WHERE THE TRENCH DRAIN FROM
 THE DUMPSTER DISCHARGES.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE CLOTHES WASHER SHALL DISCHARGE TO A MINIMUM 3
 INCH STACK. 2014 FBC-PLUMBING SEC. 406.2.
 5) SHOW THE LINT INTERCEPTOR ON THE SANITARY RISER. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-02 Cont ID  
Sent By gjohnson Date 2018-01-02 Time 13:04 Rev Time 0.00
Received By gjohnson Date 2018-01-02 Time 12:08 Sent To  
Notes
2018-01-02 13:27:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ALL THE PLAN SHEETS ARE STAPLED TOGETHER AND OUT OF
 ORDER AND MISSING SHEETS PLEASE PROVIDE TWO SEPARATE
 AND COMPLETE PLAN SETS. PER WPB AMEND TO FBC 107.1
  
 2. SHT. A-2.00 THE NOTE ABOVE ENLARGED TOILET ROOM PLAN
 STATES ADA MOUNTING HEIGHTS DETAILS ON SHT. A-8.00 THAT
 PAGE IS MISSING FROM PLAN SET . PER WPB AMEND TO FBC
 107.1
  
 3. THE WATER HEATER DETAIL SHOWS TWO DIFFERENT SIZE
 WATER HEATERS A RHEEM EGSP30 AND ELDS52 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT IS
 REQUIRED FOR BACK FLOW DEVISES. PER WPB UTILITIES
 DEPARTMENT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By gjohnson Date 2017-08-24 Time 10:53 Rev Time 0.00
Received By gjohnson Date 2017-08-24 Time 10:52 Sent To  
Notes
2017-08-24 11:24:581ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A MIN OF ONE OF THE EXAM ROOM SINKS SHALL COMPLY
 WITH FBC ACC 606 PER FBC ACC 212.3
  
 2. TEMPERED WATER IS REQUIRED AT LAVATORY. PER FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 3. IN THE FIXTURE SCHEDULE A P4H DRINKING FOUNTAIN IS
 SHOWN BUT THERE IS NOT ONE SHOWN ON THE FLOOR PLAN OR
 RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. A LENT TRAP IS REQUIRED ON WASHING MACHINE. PER FBC
 PL 1003.6 LAUNDRIES.
 LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL
 DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE
 SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE
 BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT
 PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2
 INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS
 OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 09:19 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time   Sent To  
Notes
2017-12-19 09:19:232014 FBC- BUILDING PLAN REVIEW/ ROOFING
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. DEC. 19/2017
 ACTION: BUILDING PROVISO
  
 1) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND
 SLOPED ROOFING, CURBS, ROOF TOP VENTILATORS
  
 2) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 3) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE NOTE
 SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE OF
 RIGID INSULATION BOARD OVER CORRUGATED METAL DECKING.
 PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 4) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jwitmer Date 2017-08-09 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 08:27 Sent To  
Notes
2017-08-09 08:30:022014 FBC-ROOFING/ BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. AUGUST 08/2017
 ACTION: DENIED
  
  
 1) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 2) PLEASE NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM
 AND THE USE OF RIGID INSULATION BOARD OVER CORRUGATED
 METAL DECKING. PLEASE SUPPLY THE INSULATION PRODUCT
 APPROVAL, DEPENDING ON THE TYPE OF INSULATION BOARD
 INSTALLED ADDITIONAL MANUFACTURERS SPECIFICATION WILL
 PROVIDE THE VARIOUS WAYS THE INSULATION BOARD CAN BE
 VENTILATED. NOTE THE DESIGNER OF RECORD HAS NOT
 SPECIFIED WHAT TYPE OF VENTING WILL BE REQUIRED FOR
 THIS PROJECT, NOR IS THERE ANY SPEC LISTED UNDER THE
 STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 3) FOR ALL ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop X PERMIT EXTENSION
Rev No 6 Status N Date 2020-07-06 Cont ID  
Sent By rbrown Date 2020-07-06 Time 09:23 Rev Time 0.00
Received By rbrown Date 2020-07-06 Time 09:23 Sent To  
Notes
2020-07-06 09:24:19EXTEND PERMIT APPLICATION TO 9/8/2020. OWNER SUBMITTED
 LETTERS, DATED 3/5/20 AND 6/19/20, REQUESTING AN
 EXTENSION ON THE PERMIT APPLICATION.

Review Stop X PERMIT EXTENSION
Rev No 5 Status N Date 2020-01-07 Cont ID  
Sent By rbrown Date 2020-01-07 Time 12:40 Rev Time 0.00
Received By rbrown Date 2020-01-07 Time 12:40 Sent To  
Notes
2020-01-07 12:40:36EXTEND PERMIT APPLICATION TO 3/8/2020. OWNER SUBMITTED
 A LETTER, DATED 1/6/20, REQUESTING AN EXTENSION ON THE
 PERMIT APPLICATION.

Review Stop X PERMIT EXTENSION
Rev No 4 Status N Date 2019-10-11 Cont ID  
Sent By rbrown Date 2019-10-11 Time 20:24 Rev Time 0.00
Received By rbrown Date 2019-10-11 Time 20:24 Sent To  
Notes
2019-10-11 20:24:54EXTEND PERMIT APPLICATION TO 1/8/2020. OWNER SUBMITTED
 A LETTER, DATED 9/27/19, REQUESTING AN EXTENSION ON THE
 PERMIT APPLICATION.

Review Stop X PERMIT EXTENSION
Rev No 3 Status N Date 2019-06-26 Cont ID  
Sent By rbrown Date 2019-06-26 Time 16:35 Rev Time 0.00
Received By rbrown Date 2019-06-26 Time 16:35 Sent To  
Notes
2019-06-26 16:35:54EXTEND PERMIT APPLICATION TO 10/8/19. OWNER SUBMITTED A
 LETTER, DATED 6/27/19, REQUESTING AN EXTENSION ON THE
 PERMIT APPLICATION.

Review Stop X PERMIT EXTENSION
Rev No 2 Status N Date 2019-03-21 Cont ID  
Sent By rbrown Date 2019-03-21 Time 16:59 Rev Time 0.00
Received By rbrown Date 2019-03-21 Time 16:59 Sent To  
Notes
2019-03-21 16:59:34EXTEND PERMIT APPLICATION TO 7/8/19. OWNER SUBMITTED A
 LETTER, DATED 3/21/19, REQUESTING AN EXTENSION ON THE
 PERMIT APPLICATION.

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By rbrown Date 2019-01-10 Time 13:22 Rev Time 0.00
Received By rbrown Date 2019-01-10 Time 13:22 Sent To  
Notes
2019-01-10 13:24:17EXTEND PERMIT APPLICATION TO 4/8/19. OWNER SUBMITTED A
 LETTER, DATED 1/8/19, REQUESTING AN EXTENSION ON THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-09-20 Time   Rev Time 0.00
Received By pgreilic Date 2018-09-18 Time 11:08 Sent To  
Notes
2018-09-20 08:50:581.) LANDSCAPE PERMIT AND TREE ALTERATION PERMIT
 REQUIRED. SUBMIT APPROVED LANDSCAPE PLAN WITH PROPOSED
 PHASES TO CORRESPOND WITH PHASING PLAN ON BUILDING
 PERMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-12-14 Time   Rev Time 0.00
Received By pgreilic Date 2017-12-12 Time 09:07 Sent To  
Notes
2017-12-14 11:22:19PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-18 Time 16:37 Sent To  
Notes
2017-08-22 10:51:34PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]