| Plan Review Stops For Permit 17050357 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-15 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-08-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-21 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-21 |
Time |
18:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-23 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-23 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2017-05-23 15:18:43 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2014 | | | | | | | | | C405.2.1.1 INTERIOR LIGHTING CONTROLS. | | | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING | | | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR | | | THE LIGHTING SERVING THAT AREA. | | | THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA | | | SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT | | | IDENTIFIES THE LIGHTS SERVED | | | AND INDICATES THEIR STATUS. | | | | | | ASHRAE 90.1 8.4.2 RECEPTACLE CONTROL. | | | | | | 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT LEAST 50% OF ALL | | | 125 VOLT 15- AND 20-AMPERE RECEPTACLES, INCLUDING THOSE | | | INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE | | | FOLLOWING | | | SPACE TYPES: | | | | | | A. PRIVATE OFFICES | | | B. OPEN OFFICES | | | C. COMPUTER CLASSROOMS | | | | | | SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT | | | SHALL | | | FUNCTION ON: | | | | | | A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED | | | CONTROL | | | DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC | | | PROGRAMMED | | | TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL BE PROVIDED | | | FOR AREAS OF NO MORE THAN 25,000 FT2 BUT NOT MORE | | | THAN ONE FLOOR, OR | | | B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF | | | WITHIN | | | 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR | | | C. A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT | | | INDICATES | | | THE AREA IS UNOCCUPIED. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-05-11 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-05-11 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-05-11 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-07 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2017-11-08 13:55:40 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-10-12 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2017-10-13 13:02:43 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-08-15 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2017-08-16 14:57:50 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-05-08 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-05-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-15 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-11-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-08 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-08 |
Time |
17:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-17 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-17 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2017-10-17 13:30:55 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050357 | | | 10/17/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED PLAN SHOWS A FIBERGLASS O/A DUCT AND A | | | "PROTECTIVE GRILL". PLEASE SEE SECTION 401.5 AND VERIFY | | | THAT THE GRILL WILL PROTECT THE DUCT FROM WATER | | | INTRUSION. IF USING A LOUVER IT SHALL COMPLY WITH AMCA | | | 50 AND SHALL BE WIND RESISTENT, IMPACT RATED, AND A | | | FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA MUST BE | | | SUBMITTED. | | | | | | 2) PROVIDE THE SIZE OF THE MAIN DUCT TRUCK. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-08-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-08-18 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-08-18 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2017-08-18 18:00:50 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050357 | | | 8/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESUBMITTED MECHANICAL PLAN SHEET HAS A COPIED | | | ARCHITECT'S SIGNATURE AND SEAL. PLEASE NOTE THAT ALL | | | PLANS AND DOCUMENTS SUBMITTED FOR PUBLIC RECORD BY AN | | | ARCHITECT MUST BEAR AN ORIGNAL SIGNATURE AND SEAL- | | | SECTION 61G1-16.003 FAC. | | | | | | 2) THE REQUESTED AC EQUIPMENT IS INCOMPLETE. PLEASE | | | INDICATE WHICH MODEL NO. IS FOR THE CONDENSER AND WHICH | | | IS FOR THE AIR HANDLER, AND INDICATE THE COOLING AND | | | HEATING CAPACITIES IN BTU'S. | | | | | | 3) THE OUTSIDE AIR CALCULATION IS NOT IN COMPLIANCE | | | WITH TABLE 403.3 WHICH REQUIRES 5 CFMS PER PERSON + | | | 0.06 CFMS PER SQ. FT. PLEASE CORRECT AND NOTE THAT O/A | | | CFMS ARE GENERALLY NOT MORE THAN 20% OF THE TOTAL | | | SUPPLY AIR OF A SYSTEM,OR APPROXIMATELY 240 CFMS FOR A | | | 3-TON SYSTEM. | | | | | | 4) THE 10" RETURN IS UNDERSIZED FOR 435 CFMS AT A | | | TYPICAL FRICTION LOSS OF 0.1" | | | | | | 5) REFER TO SECTION 401.5 AND INDICATE HOW THE O/A | | | INTAKE OPENING WILL BE PROTECTED. | | | | | | 6) FLEX DUCTS SHALL NOT BE USED TO CONVEY OUTSIDE AIR | | | UNLESS CERTIFIED BY THE MANUFACTURER FOR THAT TYPE OF | | | USE. | | | | | | 7) THE INPUT DATA REPORT MUST BE ATTACHED WITH THE | | | ENERGYGAUGE COMPLIANCE SUBMITTAL- SEE PAGE 1 OF THE | | | SUBMITTAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-11 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-11 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2017-05-11 17:47:02 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050357 | | | 5/11/17 | | | | | | RESULTS: DENIED. | | | | | | 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN | | | INDICATING MAKE AND MODEL, COOLING AND HEATING | | | CAPACITIES, ENERGY EFFICIENCY RATING, TOTAL SUPPLY | | | CFMS, AND ELECTRICAL DATA. | | | | | | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS IN | | | COMPLIANCE WITH TABLE 403.3 AND INDICATE HOW OUTSIDE | | | AIR IS BEING PROVIDED TO THE OCCUPIED ROOMS AND SPACES- | | | SECTION 403.3. | | | | | | 3) INDICATE THE AIR FLOW IN CFMS AT THE SUPPLY | | | DIFFUSERS AND RETURN GRILLS. | | | | | | 4) PROVIDE AN INSTALLATION DETAIL FOR THE AIR HANDLER | | | INDICATING HOW THE UNIT WILL BE SUSPENDED. | | | | | | 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL | | | PLANS IN ACCORDANCE WITH SECTION 307. INDICATE THE TYPE | | | AND SIZE OF CONDENSATE PIPING, CONDENSATE PIPING RUN, | | | AND DISCHARGE LOCATION. | | | | | | 6) PROVIDE DUCT HANGING AND CONNECTION DETAILS | | | COMPLIANT WITH THE SMACNA STANDARDS. | | | | | | 7) ENERGY CALCULATION SUBMITTAL: A) PROVIDE THE COVER | | | SHEET. B) PROVIDE THE OWNER/AGENT SIGNATURE ON PAGE 3. | | | C) THE CHECKLIST ON PAGE 7 MUST BE FILLED OUT BY THE | | | DESIGNER OR ENGINEER. | | | | | | 8) THE AC CALCULATIONS MUST BEAR THE NAME AND SIGNATURE | | | OF THE PERSON WHO PREPARED THE CALCULATION- SECTION | | | 107.2.1 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-06-21 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|