Plan Review Details - Permit 17050357
Plan Review Stops For Permit 17050357
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 06:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By jleahy Date 2017-08-21 Time 18:04 Rev Time 0.00
Received By jleahy Date 2017-08-21 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 14:26 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 14:26 Sent To  
Notes
2017-05-23 15:18:43JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1ST REVIEW: FBC 2014
  
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA.
 THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
 ASHRAE 90.1 8.4.2 RECEPTACLE CONTROL.
  
 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT LEAST 50% OF ALL
 125 VOLT 15- AND 20-AMPERE RECEPTACLES, INCLUDING THOSE
 INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE
 FOLLOWING
 SPACE TYPES:
  
 A. PRIVATE OFFICES
 B. OPEN OFFICES
 C. COMPUTER CLASSROOMS
  
 SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT
 SHALL
 FUNCTION ON:
  
 A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL
 DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC
 PROGRAMMED
 TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL BE PROVIDED
 FOR AREAS OF NO MORE THAN 25,000 FT2 BUT NOT MORE
 THAN ONE FLOOR, OR
 B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR
 C. A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES
 THE AREA IS UNOCCUPIED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By wjolin Date 2017-05-11 Time 11:44 Rev Time 0.00
Received By wjolin Date 2017-05-11 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-11-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-07 Time 13:55 Sent To  
Notes
2017-11-08 13:55:40RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-10-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-12 Time 13:02 Sent To  
Notes
2017-10-13 13:02:43RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-15 Time 14:57 Sent To  
Notes
2017-08-16 14:57:50RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-21 Time   Rev Time 0.00
Received By cpuell Date 2017-05-08 Time 09:18 Sent To  
Notes
2017-05-09 09:19:00B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-15 Time   Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-11-08 Cont ID  
Sent By ccole Date 2017-11-08 Time 17:38 Rev Time 0.00
Received By ccole Date 2017-11-08 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-10-17 Cont ID  
Sent By ccole Date 2017-10-17 Time 13:23 Rev Time 0.00
Received By ccole Date 2017-10-17 Time 13:23 Sent To  
Notes
2017-10-17 13:30:553RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17050357
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLAN SHOWS A FIBERGLASS O/A DUCT AND A
 "PROTECTIVE GRILL". PLEASE SEE SECTION 401.5 AND VERIFY
 THAT THE GRILL WILL PROTECT THE DUCT FROM WATER
 INTRUSION. IF USING A LOUVER IT SHALL COMPLY WITH AMCA
 50 AND SHALL BE WIND RESISTENT, IMPACT RATED, AND A
 FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA MUST BE
 SUBMITTED.
  
 2) PROVIDE THE SIZE OF THE MAIN DUCT TRUCK.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-18 Cont ID  
Sent By ccole Date 2017-08-18 Time 17:26 Rev Time 0.00
Received By ccole Date 2017-08-18 Time 17:26 Sent To  
Notes
2017-08-18 18:00:502ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050357
 8/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED MECHANICAL PLAN SHEET HAS A COPIED
 ARCHITECT'S SIGNATURE AND SEAL. PLEASE NOTE THAT ALL
 PLANS AND DOCUMENTS SUBMITTED FOR PUBLIC RECORD BY AN
 ARCHITECT MUST BEAR AN ORIGNAL SIGNATURE AND SEAL-
 SECTION 61G1-16.003 FAC.
  
 2) THE REQUESTED AC EQUIPMENT IS INCOMPLETE. PLEASE
 INDICATE WHICH MODEL NO. IS FOR THE CONDENSER AND WHICH
 IS FOR THE AIR HANDLER, AND INDICATE THE COOLING AND
 HEATING CAPACITIES IN BTU'S.
  
 3) THE OUTSIDE AIR CALCULATION IS NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH REQUIRES 5 CFMS PER PERSON +
 0.06 CFMS PER SQ. FT. PLEASE CORRECT AND NOTE THAT O/A
 CFMS ARE GENERALLY NOT MORE THAN 20% OF THE TOTAL
 SUPPLY AIR OF A SYSTEM,OR APPROXIMATELY 240 CFMS FOR A
 3-TON SYSTEM.
  
 4) THE 10" RETURN IS UNDERSIZED FOR 435 CFMS AT A
 TYPICAL FRICTION LOSS OF 0.1"
  
 5) REFER TO SECTION 401.5 AND INDICATE HOW THE O/A
 INTAKE OPENING WILL BE PROTECTED.
  
 6) FLEX DUCTS SHALL NOT BE USED TO CONVEY OUTSIDE AIR
 UNLESS CERTIFIED BY THE MANUFACTURER FOR THAT TYPE OF
 USE.
  
 7) THE INPUT DATA REPORT MUST BE ATTACHED WITH THE
 ENERGYGAUGE COMPLIANCE SUBMITTAL- SEE PAGE 1 OF THE
 SUBMITTAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By ccole Date 2017-05-11 Time 17:12 Rev Time 0.00
Received By ccole Date 2017-05-11 Time 17:10 Sent To  
Notes
2017-05-11 17:47:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050357
 5/11/17
  
 RESULTS: DENIED.
  
 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN
 INDICATING MAKE AND MODEL, COOLING AND HEATING
 CAPACITIES, ENERGY EFFICIENCY RATING, TOTAL SUPPLY
 CFMS, AND ELECTRICAL DATA.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.3 AND INDICATE HOW OUTSIDE
 AIR IS BEING PROVIDED TO THE OCCUPIED ROOMS AND SPACES-
 SECTION 403.3.
  
 3) INDICATE THE AIR FLOW IN CFMS AT THE SUPPLY
 DIFFUSERS AND RETURN GRILLS.
  
 4) PROVIDE AN INSTALLATION DETAIL FOR THE AIR HANDLER
 INDICATING HOW THE UNIT WILL BE SUSPENDED.
  
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS IN ACCORDANCE WITH SECTION 307. INDICATE THE TYPE
 AND SIZE OF CONDENSATE PIPING, CONDENSATE PIPING RUN,
 AND DISCHARGE LOCATION.
  
 6) PROVIDE DUCT HANGING AND CONNECTION DETAILS
 COMPLIANT WITH THE SMACNA STANDARDS.
  
 7) ENERGY CALCULATION SUBMITTAL: A) PROVIDE THE COVER
 SHEET. B) PROVIDE THE OWNER/AGENT SIGNATURE ON PAGE 3.
 C) THE CHECKLIST ON PAGE 7 MUST BE FILLED OUT BY THE
 DESIGNER OR ENGINEER.
  
 8) THE AC CALCULATIONS MUST BEAR THE NAME AND SIGNATURE
 OF THE PERSON WHO PREPARED THE CALCULATION- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-06-21 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-21 Time 14:09 Sent To  
Notes
2017-06-21 14:10:42PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved