Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By vperez Date 2017-05-11 Time 14:54 Rev Time 0.00
Received By vperez Date 2017-05-11 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-09 Cont ID  
Sent By ccole Date 2017-05-10 Time 12:06 Rev Time 0.00
Received By pleduc Date 2017-05-09 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 12:06 Rev Time 0.00
Received By ccole Date 2017-05-05 Time 16:44 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By ccole Date 2017-05-11 Time 14:51 Rev Time 0.00
Received By ccole Date 2017-05-11 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 12:06 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 12:06 Sent To  
Notes
2017-05-10 12:12:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050307
 5/10/17
  
 1) SECTION 606.2.1 RETURN AIR SYSTEMS.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
  
 PLEASE CORRECT THE PLAN TO SHOW THE LOCATION OF THE
 REQUIRED DEVICE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  