Plan Review Details - Permit 17050133
Plan Review Stops For Permit 17050133
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-10 Cont ID  
Sent By ppetty Date 2017-05-10 Time 14:30 Rev Time 0.00
Received By ppetty Date 2017-05-10 Time 08:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-08 Cont ID  
Sent By fstal Date 2017-05-08 Time 08:41 Rev Time  
Received By fstal Date   Time   Sent To E
Notes
2017-05-08 08:45:58COMMERCIAL COOKING EQUIPMENT SHALL COME INTO COMPLIANCE
 WITH THE BELOW CODE.
 NFPA 1-50.4.8,1 2012 EDITION SYSTEM ANNUNCIATION: UPON
 ACTIVATION OF AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO SHOW THAT THE SYSTEM HAS ACTIVATED. [96:10.6.1]
  
 NFPA1-50.4.8.2: WHERE A FIRE ALARM SIGNALING SYSTEM IS
 SERVING THE OCCUPANCY WHERE THE EXTINGUISHING SYSTEM IS
 LOCATED, THE ACTIVATION OF THE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM SHALL ACTIVATE THE FIRE ALARM
 SIGNALING SYSTEM. [96:10.6.2].
  
 NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT
 INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE
 COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS
 CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S),
 SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE
 SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A
 QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
  
 10.18.2.4.1 VERIFICATION SHALL ENSURE THAT THE
 INSTALLED SYSTEM INCLUDES ALL COMPONENTS AND FUNCTIONS,
 THAT THOSE COMPONENTS AND FUNCTIONS ARE INSTALLED AND
 OPERATE AS REQUIRED, THAT THE SYSTEM HAS BEEN 100
 PERCENT ACCEPTANCE TESTED IN ACCORDANCE WITH CHAPTER
 14, AND THAT ALL REQUIRED DOCUMENTATION HAS BEEN
 PROVIDED TO THE SYSTEM OWNER.
  
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-10 Cont ID  
Sent By ppetty Date 2017-05-10 Time 14:31 Rev Time 0.00
Received By ppetty Date 2017-05-02 Time 14:47 Sent To  
Notes
2017-05-02 14:47:29ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved