| 2017-05-23 08:36:25 | RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER MAY BE CHARGED FOUR TIMES THE PLAN REVIEW FEE |
| | AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR |
| | MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | 1- ORIGINAL COMMENT: INFORMATION ON DETAIL 5 TYPICAL |
| | PIER FOOTING IS INCOMPLETE. IT'S MISSING THE FOOTING |
| | SIZE, THIS IS NOT A CONTINUOUS FOOTING. THEREFORE THERE |
| | IS NO CONTINUOUS (2)#5. REVISE AS REQUIRED. PROVIDE |
| | CORRECT FOOTING INFORMATION. PROVIDE SPECIFICATIONS FOR |
| | THE FILLED CELLS. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE ATTACHMENT OF THE PORCH TO THE |
| | PIER. SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: DETAIL 5 WAS DELETED FROM REVISED DRAWINGS. |
| | NOW, THERE IS NO FOOTING INFORMATION SHOWN FOR THE |
| | PORCH. PLAN ON SHEET 1 DOESN'T SHOW ANY FOOTING. NEED |
| | TO PROVIDE COMPLETE PLANS, DETAILS AND SPECIFICATIONS |
| | FOR THE PORCH FOOTING AND ATTACHMENT. |
| | |
| | 2- ORIGINAL COMMENT: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE VENTILATION |
| | REQUIREMENTS OF SEC. R408 FBC-RESIDENTIAL FOR THE |
| | REVISED PORCH AREA. NOTE: MAKE SURE CROSS VENTILATION |
| | FOR THE STEM WALL IS NOT BLOCKED. |
| | RESPONSE: VENTILATION FOR PORCH AREA WAS PROVIDED, BUT |
| | IS MISSING THE ACCESS OPENING REQUIRED BY SEC. R408.4 |
| | FBC-RESIDENTIAL. |
| | |
| | ****** ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO HELP EXPEDITE THE REVIEW |
| | PROCESS. |
| | |