Plan Review Details - Permit 17050036
Plan Review Stops For Permit 17050036
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2018-09-16 Cont ID  
Sent By jpearson Date 2018-09-16 Time 12:47 Rev Time 0.00
Received By jpearson Date 2018-09-16 Time 12:47 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-08-15 Cont ID  
Sent By jpearson Date 2018-08-15 Time 14:41 Rev Time 0.00
Received By jpearson Date 2018-08-15 Time 14:36 Sent To I
Notes
2018-08-15 14:35:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481 (ONLY PARTIALLY CORRECTED, NOT ALL
 SHEETS FROM ORIGINAL SUBMISSION HAVE BEEN SUPPLIED. ONE
 OF THE MAIN ITEMS MISSING IS SHEET E6.01 WHICH HAS THE
 GENERATOR LOAD SUMMARY. PROVIDE ALL SHEETS FOR COMPLETE
 PLAN REVIEW.)
 2. PER THE WPB AMENDMENTS TO THE FBC, QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE
 CORRECTION. CURRENT PLAN SUBMITTED DOES NOT MEET THIS
 CRITERIA AND IS DIFFICULT TO READ. WPB FBC 107.2.1.4
 (ONLY PARTIALLY CORRECTED, NOT ALL SHEETS FROM ORIGINAL
 SUBMISSION HAVE BEEN SUPPLIED. ONE OF THE MAIN ITEMS
 MISSING IS SHEET E6.01 WHICH HAS THE GENERATOR LOAD
 SUMMARY. PROVIDE ALL SHEETS FOR COMPLETE PLAN REVIEW.)
  
 NEW COMMENTS:
  
 3. SHEET E5.02, FEEDER F-6 IS SHOWN FROM GENERATOR TO
 FIRE PUMP TRANSFER SWITCH. THE WIRE IS SIZED AS 250
 KCMIL AL, WHICH IS RATED FOR 205 AMPS TIMES 2 SETS,
 WHICH EQUALS A TOTAL AMPACITY OF 410 AMPS. THE NEXT
 BREAKER SIZE AVAILABLE IS 450 AMP, BUT THIS IS SHOWN ON
 A 500 AMP BREAKER. PROVIDE CORRECTION. NEC 240.4(B)
 4. PLEASE BE ADVISED THAT COMMENTS 1 AND 2 ABOVE HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-06-05 Cont ID  
Sent By jpearson Date 2018-06-05 Time 09:35 Rev Time 0.00
Received By jpearson Date 2018-06-05 Time 09:30 Sent To I
Notes
2018-06-05 09:35:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
 2. PER THE WPB AMENDMENTS TO THE FBC, QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE
 CORRECTION. CURRENT PLAN SUBMITTED DOES NOT MEET THIS
 CRITERIA AND IS DIFFICULT TO READ. WPB FBC 107.2.1.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-05-30 Cont ID  
Sent By ppetty Date 2017-05-30 Time 10:05 Rev Time 0.00
Received By ppetty Date 2017-05-30 Time 10:05 Sent To  
Notes
2017-05-30 10:07:06SPEC SHEETS ONLY OK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By jleahy Date 2017-05-08 Time 15:24 Rev Time 0.00
Received By jleahy Date 2017-05-08 Time 15:24 Sent To FIRE
Notes
2017-05-08 15:28:26JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED LARGER SET OF DRAWINGS TO REVIEW
  
 NEED A RISER DIAGRAM AND LOAD CALCULATION FOR THE
 GENERATOR.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-09-14 Cont ID  
Sent By fstal Date 2018-09-14 Time 08:56 Rev Time 0.00
Received By fstal Date 2018-09-14 Time 09:02 Sent To E
Notes
2018-09-14 09:02:34INSTALLATION SHALL COME INTO COMPLINACE WITH NFPA 70,
 72, & 110.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By fstal Date 2018-07-26 Time 11:15 Rev Time 0.00
Received By fstal Date   Time   Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-05-21 Time   Rev Time 0.00
Received By   Date   Time   Sent To E
Notes
2018-05-21 15:14:24PASS PENDING OTHERS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-16 Cont ID  
Sent By fstal Date 2017-05-16 Time 15:57 Rev Time 0.00
Received By fstal Date 2017-05-16 Time 16:06 Sent To E
Notes
2017-05-16 16:04:53EMERGENCY GENERATORS AND STANDBY POWER EQUIPMENT SHALL
 COME INTO COMPLIANCE WITH THE BELOW FIRE CODES:
  
 NFPA 110 STANDARDS FOR EMERGENCY & STANDBY POWER
 NFPA 70 NATIONAL ELECTRICAL CODE/NEC.
  
 NFPA 101-11.8.5, 2012 EDITION EMERGENCY LIGHTING AND
 STANDBY POWER.
 11.8.5.1 EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION
 7.9 SHALL BE PROVIDED. 11.8.5.2 REQUIREMENTS FOR
 STANDBY POWER SHALL BE AS SPECIFIED IN 11.8.5.2.1
 THROUGH 11.8.5.2.4.
 11.8.5.2.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN
 ACCORDANCE WITH ARTICLE 701 OF NFPA 70, NATIONAL
 ELECTRICAL CODE, AND NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS,
 SHALL BE PROVIDED.
 11.8.5.2.2 THE STANDBY POWER SYSTEM SHALL HAVE A
 CAPACITY AND RATING SUFFICIENT TO SUPPLY ALL EQUIPMENT
 REQUIRED TO BE CONNECTED BY 11.8.5.2.4.
 11.8.5.2.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING
 SHALL BE PERMITTED IN ACCORDANCE WITH NFPA 70, NATIONAL
 ELECTRICAL CODE.
 11.8.5.2.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED
 TO THE FOLLOWING:
 (1) ELECTRIC FIRE PUMP
 (2) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2
 FOR SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES
 (3) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION
 SYSTEMS, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 FOR
 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES
 (4) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING
 (5) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH
 STANDBY POWER TRANSFERABLE TO ANY ELEVATOR
 (6) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES
 (7) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE
 REQUIREMENTS OF SECTION 9.3
  
  
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-17 Cont ID  
Sent By cpuell Date 2018-09-17 Time 15:28 Rev Time 0.00
Received By cpuell Date 2018-08-31 Time 15:35 Sent To  
Notes
2018-09-04 15:35:18RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-08-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-19 Time 15:45 Sent To  
Notes
2018-07-20 15:45:44RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-07 Time 14:44 Sent To  
Notes
2018-05-08 14:44:41ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-30 Cont ID  
Sent By ppetty Date 2017-05-30 Time 10:07 Rev Time 0.00
Received By ppetty Date 2017-05-01 Time 09:56 Sent To  
Notes
2017-05-02 09:56:13ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-17 Cont ID  
Sent By jroach Date 2018-09-17 Time 14:58 Rev Time 0.00
Received By jroach Date 2018-09-17 Time 14:58 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By jroach Date 2018-07-23 Time 16:13 Rev Time 0.00
Received By jroach Date 2018-07-23 Time 16:13 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-02 Cont ID  
Sent By jroach Date 2017-05-02 Time 15:37 Rev Time 0.00
Received By jroach Date 2017-05-02 Time 14:51 Sent To E
Notes
2017-05-02 15:48:35PROPOSED GENERATOR LOCATED ENTIRELY WITHIN THE PROPOSED
 BUILDING...NO OUTSIDE IMPROVEMENTS. LOCATION APPROVED
 VIA THE MAIN BUILDING PERMIT (#15111020).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
2017-05-02 14:52:03ROUTED TO JOHN ROACH
  