| 2017-05-24 13:25:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE NO PLAN SHEETS SUBMITTAL THAT INDICATES |
| | LOCATION AND OR COMPLAINCE WITH ANY FIRE CODE. |
| | |
| | PLEASE PROVIDE DETAILED FLOOR PLAN SHEETS INDICATING |
| | LOCATION OF THE GENERATOR AND THE LOCATION AND |
| | IDENTIFICATION OF EACH PIECE OF EQUIPMENT IN THE ROOM. |
| | |
| | |
| | |
| | 2) THERE IS NO SCOPE OF WORK SUBMITTED. |
| | |
| | |
| | PLEASE A DETAILED PROVIDE THE SCOPE OF WORK UNDER THIS |
| | PERMIT. |
| | |
| | |
| | |
| | 3) THIS APPEARS TO BE AN EMERGENCY GENERATOR THAT |
| | PROVIDES EMERGENCY POWER TO THE LIFE SAFETY FEATURES OF |
| | THE BUILDING. |
| | |
| | IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR |
| | EMERGENCY AND STANDBY POWER SYSTEMS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE |
| | INDICATING NOTE OF THE PLAN SHEETS. |
| | |
| | |
| | |
| | |
| | 4) THE EMERGENCY GENERATOR SHALL BE TIED INTO THE FIRE |
| | COMMAND ROOM. THE FIRE COMMAND CENTER SHALL COMPLY WITH |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL |
| | CONTAIN, BUT NOT LIMITED TO, THE FOLLOWING FEATURES: |
| | |
| | 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | |
| | 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | |
| | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | PLEASE ENSURE COMPLAINCE AND PROVIDE AN APPLICABLE NOTE |
| | OF COMPLIANCE ON THE PLAN SHEETS. |
| | |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |