Plan Review Details - Permit 17050028
Plan Review Stops For Permit 17050028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 10:46 Rev Time 0.00
Received By shill Date 2017-05-15 Time 10:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-10 Cont ID  
Sent By shill Date 2017-05-10 Time 06:42 Rev Time 0.00
Received By shill Date 2017-05-10 Time 06:42 Sent To  
Notes
2017-05-10 06:44:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLEASE UPLOAD THE ENGINEERING WHICH WAS PREVIOUSLY
 SUBMITTED BY PAPER.
  
 YOU MAY UPLOAD SCANS OF THE ENGINEERING AND THE PAPER
 ORIGINAL WILL BE USED AS A "SIGNATURE DOCUMENT".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By shill Date 2017-05-08 Time 15:42 Rev Time 0.00
Received By shill Date 2017-05-08 Time 15:42 Sent To  
Notes
2017-05-08 15:42:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL, FBC 107.
  
 2. THE PAGES OF THE NOA APPLICABLE TO ALL ASSEMBLIES
 WERE NOT SUBMITTED. THIS INCLUDES THE FIRST PAGES WHICH
 PROVIDE THE COMPONENT DESCRIPTIONS. THIS INCLUDES THE
 ROLL WIDTH WHICH IS ONE OF THE NUMBERS USED IN RAS117
 CALCULATIONS.
  
 ASSEMBLIES NOT APPLICABLE SHOULD BE REMOVED. IF
 APPLICANT IS UNSURE AS TO WHAT IS REQUIRED, PLEASE SEND
 A PDF TO ME VIA EMAIL FOR PRELIMINARY REVIEW PRIOR TO
 RESUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 10:55 Rev Time 0.00
Received By shill Date 2017-05-12 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-10 Cont ID  
Sent By shill Date 2017-05-10 Time 06:44 Rev Time 0.00
Received By shill Date 2017-05-09 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-08 Cont ID  
Sent By shill Date 2017-05-08 Time 15:42 Rev Time 0.00
Received By shill Date 2017-05-01 Time 11:06 Sent To  
Notes
2017-05-01 11:06:28SHILL'S DESK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 10:52 Rev Time 0.00
Received By shill Date 2017-05-15 Time 10:52 Sent To  
Notes
2017-05-15 10:55:10ORIGINAL PAPER ENGINEERING WITH APPLICATION
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 07:59 Rev Time 0.00
Received By shill Date 2017-05-11 Time 07:59 Sent To  
Notes
2017-05-11 08:00:33ENGINEERING NEEDS TO BE UPLOADED INTO PROJECTDOX
 AFTER THAT IS DONE, THE ORIGINAL ENGINEERING WITH THE
 PAPER SUBMITTAL CAN SERVE AS "SIGNATURE DOCUMENTS" IF
 THE UPLOADED DOCUMENT IS NOT DIGITALLY SIGNED & SEALED
 (SEE BUILDING REVIEW)
  
  