Plan Review Details - Permit 17041336
Plan Review Stops For Permit 17041336
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 14:22 Rev Time 0.00
Received By cthroop Date 2018-05-01 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-28 Cont ID  
Sent By cthroop Date 2018-03-28 Time 08:05 Rev Time 0.00
Received By cthroop Date 2018-03-27 Time 10:47 Sent To  
Notes
2018-03-28 08:07:10BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE, 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE 2ND SET OF PLANS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By cthroop Date 2017-05-26 Time 16:40 Rev Time 0.00
Received By cthroop Date 2017-05-26 Time 10:59 Sent To  
Notes
2017-05-26 16:43:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RE-LOCATION OF KITCHEN ISLAND WILL REQUIRE SAW
 CUTTING OF EXISTING SLAB. PROVIDE REPAIR DETAIL OF
 SLAB.
 2. PROVIDE FRAMING DETAIL FOR INTERIOR WALLS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-04-25 Cont ID  
Sent By jleahy Date 2018-04-25 Time 16:17 Rev Time 0.00
Received By jleahy Date 2018-04-25 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-03-12 Cont ID  
Sent By jleahy Date 2018-03-12 Time 12:48 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 08:39 Sent To  
Notes
2018-03-12 08:40:03NEED ADDITIONAL SET TO STAMP ONLY ONE SET OF PLANS
 SUBMITTED JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 12:03 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 12:03 Sent To  
Notes
2017-05-23 12:13:47JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 NOT SURE WHAT YOUR SYBOLS MEAN PLEASE PLACE A SCHEDULE
 OF SYMBOLS ON PLANS.
  
 NEED TO SHOW ALL WORK RELEATED TO THE KITCHEN REMODEL
 INCLUDING A PANEL SCHEDULE
 WHICH SHOWS THE BRANCH CIRCUITS AND SIZES ON THE
 CIRCUITS.
  
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES
 (305 MM) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG
 THE WALL LINE IS MORE THAN 24 INCHES (610 MM), MEASURED
 HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2018-04-21 Cont ID  
Sent By gjohnson Date 2018-04-21 Time 10:34 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 10:34 Sent To  
Notes
2018-04-21 10:35:16GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-17 Cont ID  
Sent By lcrespo Date 2018-03-17 Time 11:58 Rev Time 0.00
Received By lcrespo Date 2018-03-17 Time 11:58 Sent To  
Notes
2018-03-17 12:08:32GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 2ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 LUIS CRESPO
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-805-6720
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By gjohnson Date 2017-05-18 Time 17:52 Rev Time 0.00
Received By gjohnson Date 2017-05-18 Time 17:52 Sent To  
Notes
2017-05-18 17:53:361ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 14:22 Rev Time 0.00
Received By cthroop Date 2018-04-11 Time 15:17 Sent To I
Notes
2018-04-12 15:18:03R30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-28 Cont ID  
Sent By cthroop Date 2018-03-28 Time 08:07 Rev Time 0.00
Received By cthroop Date 2018-03-02 Time 09:46 Sent To I
Notes
2018-03-06 09:46:59R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-26 Cont ID  
Sent By cthroop Date 2017-05-26 Time 16:40 Rev Time 0.00
Received By cthroop Date 2017-05-01 Time 13:16 Sent To  
Notes
2017-05-02 13:16:39R04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-25 Cont ID  
Sent By hmoser Date 2018-04-25 Time 06:25 Rev Time 0.00
Received By hmoser Date 2018-04-23 Time 16:03 Sent To  
Notes
2018-04-24 14:52:37MECHANICAL PASSED ON 3/27/18 NO MECHANICAL PLAN
 SUBMITTED THIS TIME HM.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By hmoser Date 2018-03-27 Time 10:24 Rev Time 0.00
Received By hmoser Date 2018-03-26 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By hmoser Date 2017-05-24 Time 15:05 Rev Time 0.00
Received By hmoser Date 2017-05-24 Time 14:32 Sent To  
Notes
2017-05-24 15:05:54PLAN DENIED
 PROVIDE MANUFACTURES SPECKS ON
 KITCHEN HOOD PER SECTION M1503.4
 MAKEUP AIR REQUIRED.2014 RESIDENTIAL
 CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-04-21 Cont ID  
Sent By gjohnson Date 2018-04-21 Time 10:34 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-17 Cont ID  
Sent By lcrespo Date 2018-03-17 Time 11:34 Rev Time 0.00
Received By lcrespo Date 2018-03-17 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By gjohnson Date 2017-05-18 Time 17:47 Rev Time 0.00
Received By gjohnson Date 2017-05-18 Time 16:29 Sent To  
Notes
2017-05-18 17:51:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: 5/18/17 DENIED
  
 1. IT IS UNCLEAR WHAT PLUMBING IS BEING DONE PLEASE
 PROVIDE CLEARER NOTE AND DRAWINGS. PER WPB AMEND TO FBC
 107.2.1
 I SUGGEST SETTING UP A MEETING TO GO OVER PLANS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  