Plan Review Details - Permit 17041335
Plan Review Stops For Permit 17041335
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-16 Cont ID  
Sent By jwitmer Date 2017-08-16 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-28 Cont ID  
Sent By jwitmer Date 2017-07-28 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2017-07-28 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-21 Cont ID  
Sent By jwitmer Date 2017-06-21 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2017-06-21 Time 08:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-05-16 Cont ID  
Sent By jwitmer Date 2017-05-16 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2017-05-16 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-27 Cont ID  
Sent By jpearson Date 2017-07-27 Time 13:31 Rev Time 0.00
Received By jpearson Date 2017-07-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By jpearson Date 2017-06-20 Time 07:12 Rev Time 0.00
Received By jpearson Date 2017-06-20 Time 07:12 Sent To  
Notes
2017-06-20 07:16:30CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 1. PREVIOUS COMMENTS NOT ADDRESSED. SEVERAL LOCATIONS
 DO NOT SHOW LIGHTING CONTROL, AND I DO NOT SEE ANY
 RECEPTACLE CONTROL. PROVIODE CORRECTIONS. PREVIOUS
 COMMENTS AS FOLLOWS:
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND
 C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA.
 THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE
 OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL
 CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR
 LESS ENCLOSED BY FLOOR-TO-CEILING
 HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES
 SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS
 WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
  
  
 ASHRAE 90.1, 8.4.2 OUTLET CONTROL
 8.4.2 AUTOMATIC RECEPTACLE CONTROL.
 AT LEAST 50% OF ALL 125-VOLT, 15-AMP AND 20-AMP
 RECEPTACLES, INCLUDING THOSE IN MODULAR PARTITIONS,
 INSTALLED IN THESE SPACES:
 A. PRIVATE OFFICES
 B. OPEN OFFICES
 C. COMPUTER CLASSROOMS SHALL BE CONTROLLED BY AN
 AUTOMATIC CONTROL DEVICE THAT SHALL USE:
 A) A SCHEDULED BASIS WITH TIME-OF-DAY OPERATED
 PROGRAMMABLE CONTROL DEVICE ?
 FOR NO MORE THAN 25,000 FT2 AND NO MORE THAN ONE FLOOR
 PER DEVICE, OR
 B) AN OCCUPANT SENSOR THAT TURNS RECEPTACLES OFF WITHIN
 30 MINUTES OF ROOM
 BEING VACATED, OR
 C) A SIGNAL FROM ANOTHER CONTROL OR ALARM THAT SIGNALS
 THE ROOM IS UNOCCUPIED.
 EXCEPTIONS:
 A) RECEPTACLES FOR EQUIPMENT FOR 24-HOUR OPERATION.
 B) SPACES WHERE AUTOMATIC SHUTOFF WOULD ENDANGER LIFE
 SAFETY OR SECURITY.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 08:00 Rev Time 0.00
Received By jleahy Date 2017-05-18 Time 07:24 Sent To  
Notes
2017-05-18 07:57:48 
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND
 C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA.
 THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE
 OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL
 CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR
 LESS ENCLOSED BY FLOOR-TO-CEILING
 HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES
 SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS
 WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
  
  
 ASHRAE 90.1, 8.4.2 OUTLET CONTROL
 8.4.2 AUTOMATIC RECEPTACLE CONTROL.
 AT LEAST 50% OF ALL 125-VOLT, 15-AMP AND 20-AMP
 RECEPTACLES, INCLUDING THOSE IN MODULAR PARTITIONS,
 INSTALLED IN THESE SPACES:
 A. PRIVATE OFFICES
 B. OPEN OFFICES
 C. COMPUTER CLASSROOMS SHALL BE CONTROLLED BY AN
 AUTOMATIC CONTROL DEVICE THAT SHALL USE:
 A) A SCHEDULED BASIS WITH TIME-OF-DAY OPERATED
 PROGRAMMABLE CONTROL DEVICE ?
 FOR NO MORE THAN 25,000 FT2 AND NO MORE THAN ONE FLOOR
 PER DEVICE, OR
 B) AN OCCUPANT SENSOR THAT TURNS RECEPTACLES OFF WITHIN
 30 MINUTES OF ROOM
 BEING VACATED, OR
 C) A SIGNAL FROM ANOTHER CONTROL OR ALARM THAT SIGNALS
 THE ROOM IS UNOCCUPIED.
 EXCEPTIONS:
 A) RECEPTACLES FOR EQUIPMENT FOR 24-HOUR OPERATION.
 B) SPACES WHERE AUTOMATIC SHUTOFF WOULD ENDANGER LIFE
 SAFETY OR SECURITY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-21 Cont ID  
Sent By pleduc Date 2017-07-21 Time   Rev Time 0.00
Received By pleduc Date 2017-07-21 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By pleduc Date 2017-06-13 Time   Rev Time 0.00
Received By pleduc Date 2017-06-12 Time 16:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-04 Cont ID  
Sent By pleduc Date 2017-05-04 Time   Rev Time 0.00
Received By pleduc Date 2017-05-03 Time 16:20 Sent To  
Notes
2017-05-04 11:20:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL FIRE ALARM WORK SHALL DE DONE UNDER SEPARATE
 SHOP DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-16 Cont ID  
Sent By   Date 2017-08-16 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-08 Time 13:18 Sent To  
Notes
2017-08-09 13:18:15RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-17 Time 09:51 Sent To  
Notes
2017-07-19 09:52:02C17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-07 Time 16:03 Sent To  
Notes
2017-06-08 16:03:53C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 08:00 Rev Time 0.00
Received By jleahy Date 2017-04-28 Time 11:35 Sent To  
Notes
2017-05-01 11:35:20C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-16 Cont ID  
Sent By jwitmer Date 2017-05-16 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2017-05-16 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-26 Cont ID  
Sent By ccole Date 2017-07-26 Time 07:57 Rev Time 0.00
Received By ccole Date 2017-07-25 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 13:00 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 13:00 Sent To  
Notes
2017-06-20 13:03:562ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17041335
 6/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED. I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTAL.
  
 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17041335
 5/9/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PLANS DO NOT CLEARLY SHOW HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE FAN COIL UNITS. SOME UNITS HAVE
 O/A DUCTS IN THEIR VICINITIES BUT THERE ARE MANY OTHERS
 THAT DO NOT SHOW ANY O/A DUCT CONNECTIONS OR DUCTS IN
 THEIR VICINITIES I.E. WSHP- 24, 231, 232, 363, & 481.
  
 3) O/A DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS ARE NOT OPERATING ARE REQUIRED PER SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 4) REFER TO SECTION C403.2.7.5 AND INDICATE HOW THE AIR
 DISTRIBUTION SYSTEM WAS SIZED AND DESIGNED.
  
 5) PROVIDE A FIRE DAMPER INSTALLATION DETAIL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-09 Cont ID  
Sent By ccole Date 2017-05-09 Time 12:11 Rev Time 0.00
Received By ccole Date 2017-05-09 Time 12:11 Sent To  
Notes
2017-05-09 12:24:501ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17041335
 5/9/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PLANS DO NOT CLEARLY SHOW HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE FAN COIL UNITS. SOME UNITS HAVE
 O/A DUCTS IN THEIR VICINITIES BUT THERE ARE MANY OTHERS
 THAT DO NOT SHOW ANY O/A DUCT CONNECTIONS OR DUCTS IN
 THEIR VICINITIES I.E. WSHP- 24, 231, 232, 363, & 481.
  
 3) O/A DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS ARE NOT OPERATING ARE REQUIRED PER SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 4) REFER TO SECTION C403.2.7.5 AND INDICATE HOW THE AIR
 DISTRIBUTION SYSTEM WAS SIZED AND DESIGNED.
  
 5) PROVIDE A FIRE DAMPER INSTALLATION DETAIL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-08-16 Cont ID  
Sent By gjohnson Date 2017-08-16 Time 12:32 Rev Time 0.00
Received By gjohnson Date 2017-08-16 Time 12:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-07-26 Cont ID  
Sent By gjohnson Date 2017-07-26 Time 13:36 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 10:57 Sent To  
Notes
2017-07-26 14:30:1713RD REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENTS:
 NOT COMPLIED 3RD REQUEST 1) SUBMIT FIRE STOP DETAILS
 FOR THE PLUMBING PIPE PENETRATIONS THROUGH THE FLOORS
 PER FBC SEC.711.5 & 714.4.1.
  
 NOT COMPLIED 3RD 6) SHT. P201 - PLBG. NOTES #2 -
 TEMPERED WATER IS REQUIRED AT THE LAVATORY PER 2014
 FBC- PLUMBING SEC.416.5, 607.1.
  
 NOT COMPLIED 3RD 7) WATER HAMMER ARRESTORS ARE REQD.
 WHERE QUICK -CLOSING VALVES ARE UTILIZED. 2014
 FBC-PLUMBING SEC.604.9.
 SHOW COMPLIANCE AT DISHWASHER, ICE MAKER AND
 REFRIGERATOR.
  
 NEW COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3. SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 4. THE BRANCH DRAIN FOR BREAKROOM 233 SHALL CONNECT TO
 BUILDING DRAIN DOWNSTREAM OF THE BATHE ROOM GROUP. PER
 FBC PL 912.1
  
 5. THE HORIZONTAL DRY VENT FOR THE WC IS NOT PERMITTED.
 PER FBC ACC 905.3 AND 905.4
  
 6. P-201 NOTE ON RESTROOM PIPING REF. SHOCK ARRESTOR
 SEE DETAIL #6 P-401 , THERE IS NO DETAIL 6 ON P-401
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. P-401 ENLARGED PLAN KEY NOTES #1 PROVIDE
 CALCULATIONS AND MANUFACTURE SPECS FOR GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-401 ENLARGED PLAN KEY NOTES #1 GREASE
 INTERCEPTOR NOT SHOWN ON RISER NETHER IS THE FD-1
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P-401 ENLARGED PLAN KEY NOTES # 3 STATES A 4"
 SANITARY LINE THE RISER SHOWS A 3" PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 15:19 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 13:14 Sent To  
Notes
2017-06-16 15:20:131ST REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENTS:
 NOT COMPLIED1) SUBMIT FIRE SAFING DETAILS FOR THE
 PLUMBING PIPE PENETRATIONS THROUGH THE FLOORS PER FBC
 SEC.711.5 & 714.4.1.
  
 NOT COMPLIED 3) THE INSTALLATION OF THE GRAB BARS IN
 THE ACCESSIBLE TOILET ROOM SHALL COMPLY WITH 2014
 FBC-ACCESS. SECS.604.5 & 609.4.
  
 NOT COMPLIED 6) SHT. P201 - PLBG. NOTES #2 - TEMPERED
 WATER IS REQUIRED AT THE LAVATORY PER 2014 FBC-
 PLUMBING SEC.416.5, 607.1.
  
 NOT COMPLIED 7) WATER HAMMER ARRESTORS ARE REQD. WHERE
 QUICK -CLOSING VALVES ARE UTILIZED. 2014 FBC-PLUMBING
 SEC.604.9.
  
 NOT COMPLIED 8) THE PLANS SHOW COLD WATER TO THE
 DISHWASHER. CLARIFY. SUBMIT SPECIFICATIONS FOR THE
 DISHWASHER IF IT IS TO BE SUPPLIED WITH COLD WATER.
  
 NOT COMPLIED 9) SUBMIT A SANITARY AND WATER RISER FOR
 ALL THE CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
  
 NOT COMPLIED 10) THE LOCATION OF THE TOILET PAPER
 DISPENSER IN THE ACCESSIBLE TOILET ROOM SHALL COMPLY
 WITH 2014 FBC - ACCESS. SEC.604.7.
  
  
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By tklarge Date 2017-05-17 Time 13:38 Rev Time 0.00
Received By tklarge Date 2017-05-12 Time 04:25 Sent To  
Notes
2017-05-17 10:43:241) SUBMIT FIRE SAFING DETAILS FOR THE PLUMBING PIPE
 PENETRATIONS THROUGH THE FLOORS PER FBC SEC.711.5 &
 714.4.1.
 2) SHT. A300, DETAIL A16 - SHOW THE LENGTH AND WIDTH
 DIMENSIONS OF THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET PER 2014 FBC - ACCESS SEC.604.3.
 3) THE INSTALLATION OF THE GRAB BARS IN THE ACCESSIBLE
 TOILET ROOM SHALL COMPLY WITH 2014 FBC-ACCESS.
 SECS.604.5 & 609.4.
 4) SHT. A300 - DETAIL A16 - SHOW THE CLEAR INSIDE
 DIMENSIONS ( LENGTH X WIDTH) OF THE TOILET ROOM. THE
 MINIMUM WIDTH SHALL BE 85 INCHES. 86 INCHES ALLOWS FOR
 TOLERANCE.2014 FBC-ACCESS. SEC.604.3, 604.3.2.
 5) THE MINIMUM CLEARANCE UNDER A LAVATORY SHALL BE 27
 INCHES PER 2014 FBC-ACCESS. SEC. 306.3.1.DETAIL M1 ON
 A300 IS FOR A SINK. SUBMIT A DETAIL FOR THE LAVATORY.
 6) SHT. P201 - PLBG. NOTES #2 - TEMPERED WATER IS
 REQUIRED AT THE LAVATORY PER 2014 FBC- PLUMBING
 SEC.416.5, 607.1.
 7) WATER HAMMER ARRESTORS ARE REQD. WHERE QUICK
 -CLOSING VALVES ARE UTILIZED. 2014 FBC-PLUMBING
 SEC.604.9.
 8) THE PLANS SHOW COLD WATER TO THE DISHWASHER.
 CLARIFY. SUBMIT SPECIFICATIONS FOR THE DISHWASHER IF IT
 IS TO BE SUPPLIED WITH COLD WATER.
 9) SUBMIT A SANITARY AND WATER RISER FOR ALL THE
 CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 10) THE LOCATION OF THE TOILET PAPER DISPENSER IN THE
 ACCESSIBLE TOILET ROOM SHALL COMPLY WITH 2014 FBC -
 ACCESS. SEC.604.7.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692