| Plan Review Stops For Permit 17041320 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-05-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-15 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-15 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-02 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-02 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2017-05-02 12:42:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SCOPE NOT CLEAR. | | | | | | SHEET A1 IS LABELED "SECOND FLOOR DEMOLITION PLAN", BUT | | | HAS NOTES ABOUT THE 3RD FLOOR DEMO. | | | | | | SHEET A2 IS LABELED "THIRD FLOOR DEMOLITION PLAN", BUT | | | THE NOTES ADJACENT TO THE FLOOR PLAN REFERS TO SECOND | | | FLOOR DEMO. | | | | | | REVISE TO CLARIFY WORK TO BE DONE ON EACH FLOOR. | | | | | | 2. REVISE PLAN TO INCLUDE BUILDING HEIGHT, FBC 107 | | | (EITHER IN FEET OR NUMBER OF FLOORS). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-23 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-23 |
Time |
08:13 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-05 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-05 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2017-05-05 12:13:00 | REFER TO BUILDING COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-05-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-17 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2017-05-19 10:09:17 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-05-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-23 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-10 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-08 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-28 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2017-05-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-15 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-15 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2017-05-15 15:18:35 | MECHANICAL PERMIT NOT REQUIRED FOR REMOVAL OF GRILLS. | | | | | | SUBMIT MECHANICAL PLANS AND SPECIFICATIONS WITH | | | REMODELING PERMIT. | | | | | | CCOLE- 5/15/17 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-08 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-08 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2017-05-08 11:40:48 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041320 | | | 5/8/17 | | | | | | RESULTS: DENIED | | | PLEASE ADDRESS THE COMMENT PRINTED BELOW. | | | | | | 1) CLARIFY IF ANY OTHER COMPONENT BEYOND THE AC GRILLS | | | WILL BE REMOVED FOR EXAMPLE DUCTWORK, OR EXHAUST FANS | | | AND EXHAUST DUCTS IN THE BATHROOMS. | | | | | | 2) COMPLY WITH BUILDING REVIEW COMMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-05-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-17 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-17 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-05-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-03 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-03 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2017-05-03 17:18:15 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. COMPLY WITH BUILDINGS COMMENTS. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|