Plan Review Details - Permit 17041277
| Plan Review Stops For Permit 17041277 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2018-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-09 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-08 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2018-01-08 12:32:34 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17041277 | | | ADD: 2115 MERCER AVE. | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 5TH REVIEW | | | DATE: MON. JAN. 08/ 2018 | | | ACTION: BUILDING PROVISO | | | | | | 1) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B | | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31(D) ROOFING PRODUCT APPROVAL: ROOFING PRODUCTS AND | | | ASSEMBLIES | | | | | | 2) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2017-12-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-12-07 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-07 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2017-12-07 14:22:10 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17041277 | | | ADD: 2115 MERCER AVE. | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 4TH REVIEW | | | DATE: THURS. DEC. 07/ 2017 | | | ACTION: DENIED | | | | | | 1-3A) COMPLIED. | | | | | | 3B) 4TH REQUEST. THIS REVIEW AGAIN NO SOILS REPORT WAS | | | SUBMITTED. SOILS REPORTS NEED TO BE ORIGINAL SIGNED AND | | | SEALED REPORTS. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 4) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT | | | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR | | | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH | | | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE | | | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5-7) COMPLIED. | | | | | | 8) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B | | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31(D) ROOFING PRODUCT APPROVAL: ROOFING PRODUCTS AND | | | ASSEMBLIES | | | | | | 9) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 10) 4TH REQUEST. SEMI-COMPLIED. THE SHEET A11 DETAIL # | | | 1 SHOWS A HANDRAIL/ GUARDRAIL COMBINATION, THIS IS | | | ALLOWED WHEN IN A R2 AND OR R3 DWELLING UNIT. PLEASE | | | NOTE THESE ARE EXTERIOR STAIRS AND THE GUARDRAIL WILL | | | NEED TO BE IN COMPLIANCE WITH 2014 FBC-B 1013.3 THE TOP | | | OF THE GUARDRAIL IS TO BE 42 INCHES TALL. SEE THE 2014 | | | FBC-B 1013.3 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS | | | THAN 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS | | | FOLLOWS: (1.) FROM THE ADJACENT WALKING SURFACES; | | | | | | 11-12) COMPLIED. | | | | | | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & | | | REPLACE ANY PAGES AS NECESSARY,COLLATE AND STAPLE PLANS | | | INTO SETS OF PLANS! A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-11-03 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-11-17 07:53:05 | E-MAIL SENT TO SKIP: | | | GOOD MORNING SKIP, | | | I'VE SPOKEN WITH JOE CANNON IN REGARDS TO FLOOR SOUND | | | UNDERLAYMENT. PLEASE REVIEW THE ATTACHMENT (PROFLEX | | | RCU-500) AND THE REFERENCED STANDARDS, I HAVE ATTACHED | | | THE STANDARD REFERENCE SHEETS FROM OUR CODE BOOK , THE | | | DELTA IIC STANDARD REFERENCE IN THE PROFLEX DOCUMENT | | | ASTM E 2179-03 IS NOT A STANDARD REFERENCE IN THE 2014 | | | FBC-B REFERENCED STANDARDS. WE DO NOT RECONIZE THIS | | | STANDARD, IT IS NOT A RECONIZED STANDARD IN THE ICC | | | CODES EITHER. NOTE THE PROFLEX RTU-500 ONLY RECEIVES A | | | 50 IIC ON A 6 INCH CONCRETE SLAB. | | | | | | ATTACHMENT: PROFLEX RCU-500. PDF | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | 2017-11-03 14:14:40 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17041277 | | | ADD: 2115 MERCER AVE. | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 3RD REVIEW | | | DATE: FRI. NOV. 03/ 2017 | | | ACTION: DENIED | | | | | | 1) COVERSHEET A-1: | | | | | | 1) COMPLIED. | | | | | | 2.) 3RD REQUEST/ SEMI COMPLIED. THE COVERSHEET NOW | | | INDICATES THE OCCUPANCY TYPE AS R-4, UP TO 90 DAYS, 16 | | | RESIDENTS AT ANY GIVEN TIME AND 2 STAFF MEMBERS, FULLY | | | R13 SPRINKLERED BUILDING. WHAT WE ARE HAVING A PROBLEM | | | WITH ON ALL THE FLOOR PLANS AND NEW LIFE SAFETY SHEETS | | | A16 & A17 ALL SHOW 19 BEDS NOT THE MAXIMUM OF 16 | | | PERSONS. THE CODE STATES THERE WE DO NOT COUNT STAFF | | | NOR DOES THE CODE REQUIRE STAFF TO SLEEP OVER. IT WOULD | | | APPEAR ROOM 1C NEEDS TO BE DEFINED AS TO USAGE, WHO | | | WILL USE THIS APARTMENT? IF THIS ROOM IS FOR STAFF | | | INDICATE AS SUCH. | | | FOR THIS REVIEW IT IS GOING TO BE ASSUMED UNIT 1C IS A | | | STAFF ROOM, STAY R-4/ AND FAIR HOUSING, NOT | | | ACCESSIBILITY. THIS NEEDS TO BE DEFINED ON THE PLANS. | | | IF THIS IS TO BE A PATIENT SLEEPING QUARTERS THEN THE | | | OCCUPANT LOAD IS 19 OVER THE ALLOWABLE R4 OCCUPANCY AND | | | BECOMES A I-1 OCCUPANCY SEE FBC-B 308.3. | | | | | | 2ND REVIEW COMMENTS. OCCUPANCY TYPE 301.1 SHORT TERM | | | FACILITY OR LONG TERM FACILITY. . OCCUPANCY TYPE 301.1 | | | SHORT TERM FACILITY OR LONG TERM FACILITY. PLEASE NOTE | | | ON THE COVERSHEET THERE IS A NOTE STATING THIS IS A | | | SHORT TERM FACILITY. WHEN DEFINING SHORT TERM THE | | | BUILDING CODE USES 30 DAYS OR LESS FOR SHORT TERM | | | (TRANSIENT), LONGER STAYS ARE (NON-TRANSIENT). IT | | | APPEARS THIS USAGE IS MORE OF A R2(WITH MORE THAN 16 | | | OCCUPANTS) FACILITY AN ALCOHOL AND OR DRUG REHAB CENTER | | | WITH CONGREGATE CARE FACILITIES, (A BUILDING OR PART | | | THERE OF THAT CONTAINS SLEEPING UNITS WHERE THE | | | RESIDENTS SHARE BATHROOMS AND OR KITCHEN FACILITIES. | | | THE OTHER ISSUE IS WITH THE UNITS CONTAINING 2 BEDROOMS | | | AND 2 OCCUPANTS PER BEDROOM AND SHARED BATHROOMS AND OR | | | KITCHEN FACILITIES THE UNIT ALSO RESEMBLES DORMITORIES! | | | PLEASE DECLARE OCCUPANCY AND USAGE. 2014 FBC-B 302.1 | | | CLASSIFICATION. | | | | | | 3A) COMPLIED. MINIMUM TYPE OF CONSTRUCTION (TABLE 503) | | | | | | 3B) 3RD REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 3C) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT | | | ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2 | | | APPLICATION. | | | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE | | | FOLLOWING: | | | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. | | | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND | | | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY | | | WITH EITHER SECTION C406.2, C406.3 OR C406.4. | | | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, | | | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE | | | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 | | | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. | | | | | | 4) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT | | | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR | | | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH | | | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE | | | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5) COMPLIED. | | | | | | 6) 3RD REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B | | | SECTION 420 IS ACHIEVED. | | | 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL | | | COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH | | | 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE. | | | | | | 6A)3RD REQUEST. PLEASE PROVIDE WHERE THERE IS A WALL | | | SCHEDULE, CUT SECTION THROUGH THE BEDROOM RATED WALLS | | | SHOWING COMPLIANCE WITH FBC-B 420.2.RATED WALLS BETWEEN | | | BEDROOMS AND OPENING PROTECTIVES. . 420.2 SEPARATION | | | WALLS. WALLS SEPARATING DWELLING UNITS IN THE SAME | | | BUILDING, WALLS SEPARATING SLEEPING UNITS IN THE SAME | | | BUILDING AND WALLS SEPARATING DWELLING OR SLEEPING | | | UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE | | | SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS | | | IN ACCORDANCE WITH SECTION 708. | | | | | | 6B) 3RD REQUEST. THE RESPONSE INDICATES ON SHEET A-11 | | | INDICATES THE USE OF THE HAMBRO FLOOR SYSTEM AND UL | | | LISTING G525. PLEASE PROVIDE THE ASSEMBLY ON THE SET OF | | | PLANS SO THE INSPECTOR CAN VERIFY THE COMPONENTS THAT | | | MAKE UP THE ASSEMBLY. THE FLOOR SYSTEM WILL NEED TO BE | | | 2 HOUR FIRE RATED ASSEMBLY FROM BOTH SIDES OF THE | | | ASSEMBLY SINCE THE ASSEMBLY IS NOT SYMMETRIC. PLEASE | | | REVIEW TABLE 707.3.10 FOR THE 2 HOUR RATING. THE | | | RESPONSE LETTER INDICATES FBC-B 711.3 ALLOWS FOR THE | | | ASSEMBLY TO BE ? HOUR. PLEASE REVIEW THE EXCEPTION IS | | | FOR NFPA 13 SYSTEM UNDER 903.3.1.1. THE FIRE PROTECTION | | | PLANS INDICATE FIRE SPRINKLERS DESIGNED TO NFPA | | | 903.3.1.2 OR NFPA 13R. | | | | | | 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES | | | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR | | | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME | | | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR | | | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO | | | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS | | | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. | | | | | | 6C) SEMI-COMPLIED. THE SUBMITTED FIRE SPRINKLER PLANS | | | SUBMITTED ARE COLOR PHOTOCOPIED SIGNATURES. [F] 420.4 | | | AUTOMATIC SPRINKLER SYSTEM. GROUP R OCCUPANCIES SHALL | | | BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER | | | SYSTEM IN ACCORDANCE WITH SECTION 903.2.8. GROUP I-1 | | | OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.2.6. QUICKRESPONSE OR RESIDENTIAL AUTOMATIC | | | SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE WITH | | | SECTION 903.3.2. | | | | | | 6D)3RD REQUEST. SEMI-COMPLIED. THE LIFE SAFETY PLAN | | | A-16 THE 1ST FLOOR SHOWS A LAYOUT OF SMOKE ALARM | | | DEVICES, PULL STATIONS AND EXIT LIGHTS EMERGENCY | | | LIGHTS. SHEET A16 THE 1ST FLOOR IS MISSING SMOKE | | | DETECTORS OUTSIDE UNIT 1B BEDROOM HALLWAY & SHEET A17 | | | THE 2ND FLOOR SHOWS NO SMOKE DETECTORS EITHER INSIDE OR | | | OUTSIDE OF THE BEDROOM UNITS. 2014 FBC-B 907.1.1 | | | CONSTRUCTION DOCUMENTS. | | | [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. FIRE | | | ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED IN | | | GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE WITH | | | SECTIONS 907.2.6, 907.2.8 AND 907.2.9, RESPECTIVELY. | | | SINGLE-OR MULTIPLE-STATION SMOKE ALARMS SHALL BE IN | | | ACCORDANCE WITH SECTION 907.2.11. | | | | | | 7) COMPLIED. | | | | | | 8) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B | | | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31(D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | 9) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 10) 3RD ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR | | | HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW | | | THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3), | | | CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6), | | | GUARDS 1013.3, OPENING LIMITATIONS (1013.4), | | | 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS | | | SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF | | | 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. | | | 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL | | | THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS | | | SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50 | | | POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. | | | | | | PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF | | | MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR | | | GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF | | | PLANS. | | | | | | 11) 3RD ROUND OF COMMENTS. THE RESPONSE INDICATES THE | | | UNDERLAYMENT CRITERIA ARE FOUND ON SHEET A-5. | | | PLEASE PROVIDE THE ACTUAL TEST REPORTS FOR SOUND | | | UNDERLAYMENT USING THE HAMBRO SYSTEM WITH 3 INCH | | | CONCRETE SLAB. PLEASE ALSO NOTE THAT FOR EACH FLOORING | | | TYPE, TILE. AND WOOD SEPARATE TEST ARE REQUIRED. | | | | | | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR | | | SYSTEM/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | 11A)3RD REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE | | | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS | | | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 11B)3RD REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 11C) 3RD REQUEST. TYPE V CONSTRUCTION: FBC-B-2014 720.2 | | | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE | | | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF | | | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE | | | THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & | | | REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO | | | SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-09-27 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-09-27 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2017-09-27 16:50:09 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17041277 | | | ADD: 2115 MERCER AVE. | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: WED. SEPT. 27/ 2017 | | | ACTION: DENIED | | | | | | 1) COVERSHEET A-1: | | | | | | 1A) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF | | | WORK INDICATES NEW BUILDINGS, TWO STORIES WHEREAS THE | | | TITLE BLOCK INDICATES THIS IS AN INTERIOR REMODEL. | | | DISCREPANCY IN THE DESCRIPTION OF WORK. 107.2.1.3 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 1B)SEMI-COMPLIED. THIS REVIEW THERE IS A INDEX WITHIN | | | THE COVERSHEET. NEED A UPDATED CODE ANALYSIS FOR THE | | | BUILDING INFORMATION. WITHOUT THE OCCUPANCY TYPE BEING | | | DECLARED AND THE MINIMUM BUILDING TYPE DECLARED IT IS | | | ONLY ASSUMPTIONS, A THOROUGH REVIEW CANNOT BE | | | ACCOMPLISHED. THE DESIGNER OF RECORD HAS NOT PROVIDED A | | | CODE ANALYSIS, PROVIDING THE OCCUPANCY TYPE, USAGE, | | | (ALCOHOL AND OR DRUG CENTER, GROUP HOME), THE TYPE OF | | | MINIMUM CONSTRUCTION REQUIRED, OR IF FIRE SPRINKLERED. | | | NOTE FIRE SPRINKLER PLANS FOR R13 SYSTEM SUBMITTED. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | | | | 2. OCCUPANCY TYPE 301.1 SHORT TERM FACILITY OR LONG | | | TERM FACILITY. . OCCUPANCY TYPE 301.1 SHORT TERM | | | FACILITY OR LONG TERM FACILITY. PLEASE NOTE ON THE | | | COVERSHEET THERE IS A NOTE STATING THIS IS A SHORT TERM | | | FACILITY. WHEN DEFINING SHORT TERM THE BUILDING CODE | | | USES 30 DAYS OR LESS FOR SHORT TERM (TRANSIENT), LONGER | | | STAYS ARE (NON-TRANSIENT). IT APPEARS THIS USAGE IS | | | MORE OF A R2(WITH MORE THAN 16 OCCUPANTS) FACILITY AN | | | ALCOHOL AND OR DRUG REHAB CENTER WITH CONGREGATE CARE | | | FACILITIES, (A BUILDING OR PART THERE OF THAT CONTAINS | | | SLEEPING UNITS WHERE THE RESIDENTS SHARE BATHROOMS AND | | | OR KITCHEN FACILITIES. THE OTHER ISSUE IS WITH THE | | | UNITS CONTAINING 2 BEDROOMS AND 2 OCCUPANTS PER BEDROOM | | | AND SHARED BATHROOMS AND OR KITCHEN FACILITIES THE UNIT | | | ALSO RESEMBLES DORMITORIES! PLEASE DECLARE OCCUPANCY | | | AND USAGE. 2014 FBC-B 302.1 CLASSIFICATION. | | | | | | 3) MINIMUM TYPE OF CONSTRUCTION (TABLE 503) | | | | | | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING COMPONENTS: | | | FIRE-RESISTANT SEPARATIONS | | | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION | | | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS | | | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE | | | RESISTANCE | | | | | | 10) FL. ACCESSIBILITY CODE OR FAIR HOUSING, VERTICAL | | | ACCESSIBILITY? | | | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: | | | SITE REQUIREMENTS | | | ACCESSIBLE ROUTE | | | VERTICAL ACCESSIBILITY | | | TOILET AND BATHING FACILITIES | | | DRINKING FOUNTAINS | | | EQUIPMENT | | | SPECIAL OCCUPANCY REQUIREMENTS | | | FAIR HOUSING REQUIREMENTS | | | | | | 11. NO FINISH SCHEDULE!!!!INTERIOR REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING: | | | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) | | | LIGHT AND VENTILATION | | | SANITATION | | | | | | 12.2ND REQUEST. SPECIAL SYSTEMS: | | | ELEVATORS | | | LIFTS | | | FLORIDA ACCESSIBILITY (SHORT TERM/ TRANSIENT) VERSES | | | FAIR HOUSING (LONG TERM/ NON-TRANSIENT). | | | | | | | | | | | | 1C) THE PLANS DO NOT INDICATE IF THE CONCEPT FOR THIS | | | PROJECT TO BE CONSIDERED 1 BUILDING (TOTAL SQUARE FOOT, | | | FOOT PRINT OR IF THEY ARE TRYING TO COMPLY UNDER THE | | | BUILDINGS ON THE SAME LOT, SECTION 503.1.2. | | | | | | 1D) COMPLIED. R13 FIRE SPRINKLER PLANS. | | | | | | 1E) NEW COMMENT. SHEET A2.1 DESIGN LIVE LOADS PLANS | | | INDICATE: STAIRS & CORRIDORS 60 PSF CORRECT. | | | 2014 FBC-B TABLE 1607.1(30) STAIRS 100 PSF, | | | 2014 FBC-B TABLE 1607.1(25) PUBLIC ROOMS & CORRIDORS | | | 100 PSF | | | | | | | | | 1F) COMPLIED. | | | | | | 2) 2ND REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. | | | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY | | | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 3) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT | | | ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2 | | | APPLICATION. | | | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE | | | FOLLOWING: | | | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. | | | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND | | | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY | | | WITH EITHER SECTION C406.2, C406.3 OR C406.4. | | | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, | | | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE | | | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 | | | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. | | | | | | 4) 2ND REQUEST. ART IN PUBLIC PLACES. THE CITY OF WEST | | | PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT | | | THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT | | | FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER | | | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE | | | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY | | | WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH | | | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE | | | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5) COMPLIED. | | | | | | 6) 2ND REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B | | | SECTION 420 IS ACHIEVED. | | | 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL | | | COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH | | | 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE. | | | | | | 6A)2ND REQUEST. RATED WALLS BETWEEN BEDROOMS. 420.2 | | | SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS IN | | | THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN | | | THE SAME BUILDING AND WALLS SEPARATING DWELLING OR | | | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO | | | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE | | | PARTITIONS IN ACCORDANCE WITH SECTION 708. | | | | | | 6B) 2ND REQUEST. 420.3 HORIZONTAL SEPARATION. FLOOR | | | ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME | | | BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS | | | IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING | | | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES | | | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE | | | CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH | | | SECTION 711. | | | | | | 6C) COMPLIED. [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. | | | GROUP R OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH | | | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH | | | SECTION 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE | | | EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM | | | IN ACCORDANCE WITH SECTION 903.2.6. QUICKRESPONSE OR | | | RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN | | | ACCORDANCE WITH SECTION 903.3.2. | | | | | | 6D) [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. | | | FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED | | | IN GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE | | | WITH SECTIONS 907.2.6, 907.2.8 AND 907.2.9, | | | RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE ALARMS | | | SHALL BE IN ACCORDANCE WITH SECTION 907.2.11. | | | | | | 7A) 2ND REQUEST. THE COVERSHEET NOW INDICATES WIND | | | DESIGN. THE COVERSHEET UNDER THE WIND DESIGN INDICATES | | | A BASIC WIND SPEED OF 160 MPH, THEN 2 LINES DOWN A WIND | | | SPEED IN 3 SECOND GUST OF 140 MPH. THEN ON SHEET A2.1 | | | WIND SPEED OF 170 MPH. PLEASE SEE THE 2014 FBC-B FIGURE | | | 1609A FOR BUILDINGS WITH A RISK CATEGORY II. THE FIGURE | | | SHOWS THE CITY OF WEST PALM BEACH IN A WIND ZONE OF 170 | | | VULT/ 3 SECOND GUST. THE WIND SPEED CONVERSION TABLE | | | 1609.3.1 INDICATES FOR 170 VULT THE CONVERSION TO VASD | | | WILL BE 132 VASD/ 3 SECOND GUST. PLEASE CORRECT. | | | 1ST ROUND OF COMMENTS. SHEET A8 & A9 SHOW PRESSURES FOR | | | COMPONENTS AND CLADDING, BUT THERE IS NO WIND DESIGN | | | CRITERIA TO KNOW IF THESE PRESSURES ARE ACCURATE. 2014 | | | FBC-B 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | | 1609.3.1. | | | | | | 7.2. RISK CATEGORY. | | | | | | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. | | | HEIGHT AND EXPOSURE. | | | | | | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | | | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | | M2). | | | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING. | | | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. | | | | | | 8) 2ND REQUEST, UNTIL THE WIND DESIGN PRESSURES ARE IN | | | DESIGN PRESSURES (VASD) THE PRODUCT APPROVALS SUBMITTED | | | CANNOT BE CHECKED FOR CODE COMPLIANCE UNTIL THE WIND | | | DESIGN IS FINALIZED. | | | | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 9) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH | | | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, | | | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, | | | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING | | | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND | | | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED | | | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING | | | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE | | | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN | | | THE TESTS. | | | | | | 10) 2ND ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR | | | HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW | | | THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3), | | | CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6), | | | GUARDS 1013.3, OPENING LIMITATIONS (1013.4), | | | 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS | | | SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF | | | 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. | | | 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL | | | THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS | | | SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50 | | | POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. | | | | | | PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF | | | MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR | | | GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF | | | PLANS. | | | | | | 11) 2ND ROUND OF COMMENTS. THE PLANS DO NOT INDICATE | | | WHAT THE 2ND FLOOR FINISHES WILL BE? PLEASE SHOW | | | COMPLIANCE WITH: | | | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR | | | SYSTEM/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2 | | | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE | | | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF | | | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE | | | THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & | | | REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO | | | SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-05-12 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-10 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2017-05-12 11:38:55 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17041277 | | | ADD: 2115 MERCER AVE. | | | CONT: ERETZOR CONSTRUCTION LLC | | | TEL: 954-937-7041 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: FRI. MAY 12/ 2017 | | | ACTION: DENIED | | | | | | 1) COVERSHEET A-1: | | | | | | 1A) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF | | | WORK INDICATES NEW BUILDINGS, TWO STORIES WHEREAS THE | | | TITLE BLOCK INDICATES THIS IS AN INTERIOR REMODEL. | | | DISCREPANCY IN THE DESCRIPTION OF WORK. 107.2.1.3 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 1B) THE COVERSHEET APPEARS TO BE THE CODE ANALYSIS FOR | | | THE BUILDING INFORMATION. THERE IS NO INDEX SHEET | | | LISTING WHERE THIS INFORMATION CAN BE FOUND. WITHOUT | | | THE OCCUPANCY TYPE BEING DECLARED AND THE MINIMUM | | | BUILDING TYPE DECLARED IT IS ONLY ASSUMPTIONS, A | | | THOROUGH REVIEW CANNOT BE ACCOMPLISHED. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | 2. OCCUPANCY TYPE 301.1 SHORT TERM FACILITY OR LONG | | | TERM FACILITY | | | 3) MINIMUM TYPE OF CONSTRUCTION (TABLE 503) | | | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING COMPONENTS: | | | FIRE-RESISTANT SEPARATIONS | | | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION | | | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS | | | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE | | | RESISTANCE | | | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | | SCHEMATIC FIRE SPRINKLERS | | | STANDPIPES | | | PRE-ENGINEERED SYSTEMS | | | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL | | | INCLUDE THE FOLLOWING REQUIREMENTS: | | | OCCUPANT LOAD AND EGRESS CAPACITIES | | | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | NO LIFE SAFETY SHEET!!!!!!! | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | SPECIFIC OCCUPANCY REQUIREMENTS | | | 10) FL. ACCESSIBILITY CODE OR FAIR HOUSING, VERTICAL | | | ACCESSIBILITY? | | | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: | | | SITE REQUIREMENTS | | | ACCESSIBLE ROUTE | | | VERTICAL ACCESSIBILITY | | | TOILET AND BATHING FACILITIES | | | DRINKING FOUNTAINS | | | EQUIPMENT | | | SPECIAL OCCUPANCY REQUIREMENTS | | | FAIR HOUSING REQUIREMENTS | | | | | | 11. NO FINISH SCHEDULE!!!!INTERIOR REQUIREMENTS SHALL | | | INCLUDE THE FOLLOWING: | | | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) | | | LIGHT AND VENTILATION | | | SANITATION | | | 12. SPECIAL SYSTEMS: | | | ELEVATORS | | | ESCALATORS | | | LIFTS | | | | | | | | | | | | 1C) THE PLANS DO NOT INDICATE IF THE CONCEPT FOR THIS | | | PROJECT TO BE CONSIDERED 1 BUILDING (TOTAL SQUARE FOOT, | | | FOOT PRINT OR IF THEY ARE TRYING TO COMPLY UNDER THE | | | BUILDINGS ON THE SAME LOT, SECTION 503.1.2. | | | | | | 1D) FIRE SPRINKLER PLANS WILL BE REQUIRED FOR EITHER AN | | | I OCCUPANCY (903.2.6) OR AN R OCCUPANCY (903.2.8.) | | | W. P. B. ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER | | | DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH | | | INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR | | | MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR | | | CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA | | | STATUTES, MAY DESIGN A FIRE | | | SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN | | | THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF | | | THE ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR | | | DELETION OF NOT MORE THAN 49 HEADS, NOT WITHSTANDING | | | THE SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM. | | | | | | 1E) UNDER THE HEADING BUILDING CALCULATIONS THE PLANS | | | INDICATE A 2 STORY 4 UNIT FOOTPRINT WHEREAS SHEET A-3 | | | ONLY SHOWS 3 UNITS ON THE GROUND FLOOR AND 2 UNITS ON | | | THE SECOND STORY. 107.2.1.3 ADDITIONAL INFORMATION | | | REQUIRED, IT APPEARS THIS MAYBE A TYPO. | | | | | | 1F) DISCREPANCY IN THE COVERSHEET. BUILDING CALCULATION | | | VERSES SHEET A-3. THE COVERSHEET INDICATES A 1 STORY | | | LAUNDRY AND OFFICE VERSES SHEET A-3 SHOWS FOR THE SAME | | | BUILDING AN EXERCISE ROOM AND LAUNDRY. 107.2.1.3 | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 2) 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE | | | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL | | | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO | | | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING | | | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | GEOTECHNICAL INVESTIGATION BE CONDUCTED. | | | | | | 3) PLEASE SUBMIT ENERGY CALCULATIONS. 2014 FBC-ENERGY | | | CODE. C401.2 APPLICATION. | | | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE | | | FOLLOWING: | | | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. | | | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND | | | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY | | | WITH EITHER SECTION C406.2, C406.3 OR C406.4. | | | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, | | | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE | | | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 | | | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. | | | | | | 4) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH | | | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES | | | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH | | | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND | | | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR | | | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS | | | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR CONTACT INFORMATION PLEASE CONTACT: | | | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR | | | 822-1515 E-MAIL: [email protected] | | | | | | 5) SHEET A4: UNITS 1A, 1B, 2D & 2E ALL SHOW WHAT | | | APPEARS TO BE EITHER A DIVIDER OR PONY WALL (HALF | | | WALL). | | | THE PLANS DO NOT HAVE A DETAIL OF THIS AREA, AND THERE | | | IS NO FURNITURE PLAN SHOWING IF THERE IS 2 BEDS OR 4 | | | BEDS IN EACH OF THE IDENTIFIED BEDROOMS. AGAIN THE | | | OCCUPANT LOAD CANNOT BE IDENTIFIED NOR CAN THE PLUMBING | | | FIXTURE COUNT. FBC-B TABLE 1004.1.2. | | | | | | 6) PLEASE SHOW HOW COMPLIANCE WITH FBC-B SECTION 420 IS | | | ACHIEVED. | | | 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL | | | COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH | | | 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE. | | | | | | 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS | | | IN THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS | | | IN THE SAME BUILDING AND WALLS SEPARATING DWELLING OR | | | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO | | | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE | | | PARTITIONS IN ACCORDANCE WITH SECTION 708. | | | | | | 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES | | | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR | | | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME | | | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR | | | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO | | | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS | | | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. | | | | | | [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R | | | OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED | | | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN | | | ACCORDANCE WITH SECTION 903.2.6. QUICKRESPONSE OR | | | RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN | | | ACCORDANCE WITH SECTION 903.3.2. | | | | | | [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. FIRE | | | ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED IN | | | GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE WITH | | | SECTIONS 907.2.6, 907.2.8 AND 907.2.9, RESPECTIVELY. | | | SINGLE-OR MULTIPLE-STATION SMOKE ALARMS SHALL BE IN | | | ACCORDANCE WITH SECTION 907.2.11. | | | | | | 7) SHEET A8 & A9 SHOW PRESSURES FOR COMPONENTS AND | | | CLADDING, BUT THERE IS NO WIND DESIGN CRITERIA TO KNOW | | | IF THESE PRESSURES ARE ACCURATE. 2014 FBC-B 1603.1.4 | | | WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | | 1609.3.1. | | | | | | 7.2. RISK CATEGORY. | | | | | | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. | | | HEIGHT AND EXPOSURE. | | | | | | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | | | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ | | | M2). | | | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING. | | | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. | | | | | | 8) 2010/ 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL | | | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | 9) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH | | | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, | | | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, | | | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING | | | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND | | | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED | | | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING | | | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE | | | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN | | | THE TESTS. | | | | | | 10) PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF | | | MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR | | | GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF | | | PLANS. | | | | | | 11) THE PLANS DO NOT INDICATE WHAT THE 2ND FLOOR | | | FINISHES WILL BE? PLEASE SHOW COMPLIANCE WITH: | | | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR | | | SYSTEM/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2 | | | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE | | | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF | | | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE | | | THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & | | | REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO | | | SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2017-12-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-29 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-29 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2017-12-29 07:45:03 | NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS, | | | STAMPED NEW SET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-12-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-07 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-07 |
Time |
07:24 |
Sent To |
B |
|
| Notes |
| 2017-12-07 07:24:53 | NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS, | | | STAMPED NEW SET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-11-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-12 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-12 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2017-11-12 08:43:41 | NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS, | | | STAMPED NEW SET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-19 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-19 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2017-09-19 12:33:50 | NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS, | | | STAMPED NEW SET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-05-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-17 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-17 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2017-10-04 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2017-10-04 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2017-10-04 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-10-04 16:12:14 | PLANS ARE UNDER REVIEW THRU ENGINEERING, | | | [email protected] (561) 494-1085 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-05-18 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2017-05-18 |
Time |
|
Rev Time |
1.00 |
| Received By |
|
Date |
2017-05-18 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-05-18 15:49:16 | SEPARATE ENGINEERING SUBMITTAL WILL BE REQUIRED. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-21 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-01 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-11-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-06 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-09-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-09-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-09-06 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-03 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2017-05-04 12:36:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 1 - THERE ARE INCORRECT REFERENCES TO | | | CURRENT EDITIONS OF THE NFPA 1 & 101; 2015. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | | | | PLEASE CORRECT. | | | | | | | | | 2) A LIFE SAFETY REVIEW SHEET WAS NOT PROVIDED | | | INDICATING COMPLIANCE WITH ANY LIFE SAFETY OCCUPANCY | | | CHAPTER OF NFPA 101. IT APPEARS THAT THE OCCUPANCY MAY | | | BE CHAPTER IS NFPA 101, CHAPTER 30, NEW APARTMENT | | | BUILDINGS. CHAPTER 32 RESIDENTIAL BOARD AND CARE, OR | | | CHAPTER 26 LODGING AND ROOMING HOUSES. | | | | | | IT APPEARS THAT THERE ARE TWO SEPARATE SLEEPING AREAS | | | PER BEDROOM. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS AS TO THE USE AND | | | FUNCTION OF THESE APARTMENTS AND THE APPLICABLE NFPA | | | 101 OCCUPANCY CHAPTER AND ALL LIFE SAFETY FEATURES | | | REQUIREMENTS OF THAT CHAPTER. | | | | | | | | | | | | 3) SHEET A 4 - A METAL GATE IS INDICATED IN THE PATH OF | | | EXIT TRAVLE. BUT NO DETAIL PROVIDED AS TO THE EXIT | | | HARDWARE IN COMPLINACE WITH NFPA 101, CHAPTER 7, MEANS | | | OF EGRESS. | | | | | | 30.2.2.2 DOORS. | | | 30.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE | | | PERMITTED. | | | 30.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH | | | 30.2.2.2.2.1, 30.2.2.2.2.2, 30.2.2.2.2.3, OR | | | 30.2.2.2.2.4. | | | 30.2.2.2.2.1* NO DOOR IN ANY MEANS OF EGRESS SHALL BE | | | LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. | | | | | | 7.2.1.4 SWING AND FORCE TO OPEN. | | | 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY | | | DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE | | | SIDE-HINGED OR PIVOTED-SWINGING TYPE, AND SHALL BE | | | INSTALLED TO BE CAPABLE OF SWINGING FROM ANYPOSITION TO | | | THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT IS | | | INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS: | | | (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN | | | CHAPTER 24, SHALL BE PERMITTED. | | | (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE | | | OCCUPANCIES, AS PROVIDED IN CHAPTERS 32 AND 33, SHALL | | | BE PERMITTED. | | | (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, | | | HORIZONTAL-SLIDING OR VERTICAL-ROLLING SECURITY GRILLES | | | OR DOOR ASSEMBLIES THAT ARE PART OF THE REQUIRED MEANS | | | OF EGRESS SHALL BE PERMITTED, PROVIDED THAT ALL OF THE | | | FOLLOWING CRITERIA ARE MET: | | | (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN | | | SECURED IN THE FULLY OPEN POSITION DURING THE PERIOD OF | | | OCCUPANCY BY THE GENERAL PUBLIC. | | | (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE | | | SHALL BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT | | | LESS THAN 1 IN. (25 MM) HIGH ON A CONTRASTING | | | BACKGROUND THAT READS AS FOLLOWS: THIS DOOR TO REMAIN | | | OPEN WHEN THE BUILDING IS OCCUPIED. | | | (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE | | | CLOSED POSITION WHEN THE SPACE IS OCCUPIED. | | | (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM | | | WITHIN THE SPACE WITHOUT THE USE OF ANY SPECIAL | | | KNOWLEDGE OR EFFORT. | | | (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT | | | MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED | | | WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR | | | DOOR ASSEMBLIES. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER | | | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE | | | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | | | | | | | PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS. | | | | | | | | | | | | | | | 4) SHEET A 5 - STAIRS, HARDRAILS AND RAILINGS ARE | | | INDICATED; HOWEVER NO DETAILS ARE PROVIDED. | | | | | | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS | | | | | | 7.2.2 STAIRS. | | | 7.2.2.1 GENERAL. | | | 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF | | | EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF | | | SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2, | | | UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2. | | | | | | 7.2.2.3 STAIR DETAILS. | | | 7.2.2.3.1 CONSTRUCTION. | | | 7.2.2.3.1.1 ALL STAIRS SERVING AS REQUIRED MEANS OF | | | EGRESS SHALL BE OF PERMANENT FIXED CONSTRUCTION, UNLESS | | | THEY ARE STAIRS SERVING SEATING THAT IS DESIGNED TO BE | | | REPOSITIONED IN ACCORDANCE WITH CHAPTERS 12 AND 13. | | | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | | 7.2.2.4.1 HANDRAILS. | | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | | BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 | | | OR 7.2.2.4.1.6. | | | | | | PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS | | | | | | | | | | | | 5) SEET A 6 & 7 - THERE ARE NO EXIT SIGNS IN ANY EXIT | | | CORRIDOR. | | | | | | NFPA 101, CAPTER 30, NEW APARTMENT BUILDINGS | | | | | | 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. | | | | | | 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL | | | BUILDINGS REQUIRING MORE THAN ONE EXIT. | | | | | | | | | | | | | | | 6) SHEET 6 & 7 - THE SUBMITTAL DOES NOT INDICATED EXITS | | | LEADING TO A PUBLIC WAY. | | | | | | 30.2.7 DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL | | | COMPLY WITH SECTION 7.7. | | | | | | 7.7 DISCHARGE FROM EXITS. | | | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE | | | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT | | | DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH | | | 7.7.1.4. | | | | | | PLEASE PROVIDE A DETAIL INDICATING COMPLIANCE WITH THE | | | REQUIREMENTS. | | | | | | | | | | | | | | | 7) NO SHEET SUBMITTALS - THERE ARE NO FIRE SPRINKLER | | | DOCUMENTS WITH THIS SUBMITTAL. | | | | | | 30.3.5 EXTINGUISHMENT REQUIREMENTS. | | | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY | | | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM | | | INSTALLED IN ACCORDANCE WITH 30.3.5.2. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION | | | ENGINEERING | | | DOCUMENTS. | | | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED | | | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE | | | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND | | | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), | | | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND | | | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE | | | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. | | | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE | | | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND | | | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES | | | AND STANDARDS, WHERE AVAILABLE. | | | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A | | | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION | | | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | | ENGINEERING DOCUMENTS. | | | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE | | | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT | | | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE | | | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND | | | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT | | | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM | | | ENGINEERING DOCUMENTS. | | | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED | | | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE | | | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL | | | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. | | | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION | | | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM | | | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT | | | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED | | | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER | | | OF RECORD FOR THE FIRE PROTECTION SYSTEM. | | | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, | | | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY | | | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN | | | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, | | | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. | | | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER | | | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION | | | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED | | | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE | | | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR | | | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE | | | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION | | | SYSTEM ENGINEERING DOCUMENTS. | | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED | | | 4-2-2000, 6-26-01 | | | | | | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION | | | SYSTEMS. | | | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT | | | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, | | | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE | | | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE | | | WATER MAINS AND DEDICATED FIRE PROTECTION WATER | | | SOURCES. | | | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION | | | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL | | | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN | | | APPLICABLE: | | | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER | | | SUPPLY AS DEFINED BY 633.021(18) F.S. | | | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE | | | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING | | | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND | | | CONCLUSIONS. | | | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA. | | | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, | | | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR | | | EACH SEPARATE 42 HAZARD OCCUPANCY. | | | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS | | | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR | | | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE | | | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM | | | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY | | | DEMANDING DESIGN AREA. | | | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE | | | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO | | | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, | | | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH | | | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND | | | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF | | | SERVICE. | | | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE | | | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF | | | WATER. | | | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF | | | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER | | | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION | | | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE | | | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY | | | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY | | | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND | | | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE | | | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE | | | MEASURES. | | | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND | | | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS | | | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. | | | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD | | | AND INTERIOR FIRE PROTECTION COMPONENTS. | | | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE | | | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL | | | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING | | | APPROVAL AND DOCUMENTATION. | | | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE | | | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE | | | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL | | | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE | | | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. | | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED | | | 4-2-2000, 6-26-01, 7-12-05 | | | | | | | | | PLEASE REVIEW AND PROVIDES APPLICABLE SIGNED AND SEALED | | | EOR PLAN SHEETS OR WRITTEN NARRATIVE DOCUMENT | | | CONTAINING THE SAME INFO. SHOP DRAWINGS CAN THEN BE | | | PRODUCED, PREPARED AND SUBITTED SEPARATELY BY A FIRE | | | SPRINKLER CONTRACTOR. | | | | | | | | | | | | 8) SHEET A 8 - LIGHTWEIGHT TRUSS FLOORS AND TRUSSES ARE | | | INDICATED. | | | | | | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR | | | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. | | | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT | | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES | | | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A | | | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND | | | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. | | | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO | | | THE LEFT OF THE MAIN ENTRY DOOR. | | | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | | MARKED WITH THE LETTER "R". | | | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | | SHALL BE MARKED WITH THE LETTER "F". | | | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | | | | | | | | | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 10) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A | | | COMPLETE REVIEW OF THE LIFE SAFETY FEATURES AND | | | PROTECTION OF THIS PROJECT. | | | | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-05 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-05 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2017-12-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-12-16 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-12-16 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2017-12-16 12:40:42 | 4TH REVIEW | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PREVIOUS GAS COMMENTS: NOT COMPLIED I SUGGEST A MEETING | | | TO BE SCHEDULED TO GO OVER COMMENTS PRIOR TO NEXT | | | SUBMITTAL. | | | | | | | | | | | | 2. THE TANKLESS WATER HEATER SHALL BE MOUNTED 4' AWAY | | | FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE | | | INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC | | | 107.2.1 | | | | | | 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER | | | FBC FG 408.4 | | | | | | 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT | | | SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH | | | APPLIANCE . WPB AMEND TO FBC 107.2.1 | | | | | | NEW COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE AFTER METER IS SHOWN AS | | | 3' 10" ON THE RISER AND 25' 8" ON THE FLOOR PLAN PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE SIZING TABLES LISTED ON THE PLAN SHT. A-3.1 ARE | | | .5 PSI SYSTEMS IN THE CODE BOOK BUT ARE SHOWN AS 2 PSI | | | ON THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. THE GENERAL NOTES ON SHT P-3.1 REFERENCES LP GAS | | | RISER SHOWS NATURAL GAS PLEASE CLARIFY AND REMOVE | | | INCORRECT NOTES. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-16 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-16 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2017-11-16 13:27:39 | 3RD REVIEW | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PREVIOUS GAS COMMENTS: NOT COMPLIED | | | | | | | | | | | | 2. THE TANKLESS WATER HEATER SHALL BE MOUNTED 4' AWAY | | | FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE | | | INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC | | | 107.2.1 | | | | | | 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER | | | FBC FG 408.4 | | | | | | 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT | | | SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH | | | APPLIANCE . WPB AMEND TO FBC 107.2.1 | | | | | | NEW COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE AFTER METER IS SHOWN AS | | | 3' 10" ON THE RISER AND 25' 8" ON THE FLOOR PLAN PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE SIZING TABLES LISTED ON THE PLAN SHT. A-3.1 ARE | | | .5 PSI SYSTEMS IN THE CODE BOOK BUT ARE SHOWN AS 2 PSI | | | ON THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. THE GENERAL NOTES ON SHT P-3.1 REFERENCES LP GAS | | | RISER SHOWS NATURAL GAS PLEASE CLARIFY AND REMOVE | | | INCORRECT NOTES. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-27 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-27 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2017-09-27 10:28:08 | 2ND REVIEW | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC | | | FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @ | | | 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE. | | | | | | 2. THE TANKLES WATER HEATER SHALL BE MOUNTED 4' AWAY | | | FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE | | | INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC | | | 107.2.1 | | | | | | 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER | | | FBC FG 408.4 | | | | | | 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT | | | SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH | | | APPLIANCE . WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-05-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-17 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-17 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2017-05-17 10:32:35 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC | | | FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @ | | | 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-09 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-12-19 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-12-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-12-16 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-29 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-16 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-27 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-05 |
Time |
06:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-31 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-05-19 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-04-27 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-01-16 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-01-16 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2017-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-12-18 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-12-07 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2017-12-07 14:43:12 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-05-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-05-12 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-05-10 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2017-05-12 11:38:05 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2017-12-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-28 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-28 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2017-12-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-11 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-11 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2017-12-11 16:32:46 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041277 | | | 12/11/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REVISED ENERGY CALCULATIONS HAVE NOT BEEN PROVIDED | | | FOR UNITS 1A, 1B, 1C, 2D, & 2E. THE PREVIOUS SUBMITTALS | | | WERE VOIDED. | | | | | | 2) THE FLOOR PLAN DRAWING INDICATES 3.0 TON AC SYSTEMS | | | FOR ALL UNITS, HOWEVER THE SCHEDULE INDICATES 2.5 TON | | | SYSTEMS FOR UNITS 1A, 1B, 1C, & 2D. PLEASE NOTE THAT | | | THE REVISED AC CALCULATIONS INDICATE A 3.0 SYSTEM FOR | | | 1B. | | | | | | 3) 3RD REQUEST FOR WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE EXTERIOR CONDENSERS. | | | | | | 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR | | | HANDLERS- SEE SECTION 307. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-07 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-07 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2017-11-07 14:30:39 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041277 | | | 11/7/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THE 1ST REVIEW COMMENTS 1-7 WERE NOT ADDRESSED AND | | | STILL EXIST WITH THE EXCEPTION OF COMMENT #6 WHICH IS | | | RESCINDED BASED ON SECTION R403.2.2 FBC-14 ENERGY | | | CONSERVATION. | | | I HAVE REPRINTED THE COMMENTS BELOW. PLEASE PROVIDE A | | | NARRATIVE RESPONSE TO HELP EXPEDITE THE REVIEW. | | | | | | PLEASE NOTE THAT THE FIRE-RESISTANCE RATINGS OF WALLS | | | AND CEILINGS IN THE PROPOSED OCCUPOANCY HAVE STILL NOT | | | BEEN COMPLETELY ESTABLISHED IN THE ARCHITECTURAL AND | | | LIFE SAFETY PLANS, AND CURRENTLY NO FIRE DAMPERS ARE | | | SHOWN ON THE PLANS TO PROTECT DUCTS THAT ARE | | | PENETRATING BOTH THE VERTICAL AND HORIZONTAL | | | ASSEMBLIES. WHEN THE PLANS ARE REVISED IN ACCORDANCE | | | WITH THE BUILDING REVIEW COMMENTS, THESE ISSUES WILL BE | | | ADDRESSED. | | | | | | 1) THE ENERGY CALCULATION FORM R405-2014 INDICATES 2.5 | | | TON SYSTEMS FOR UNITS 1A AND 1B HOWEVER THE SCHEDULE ON | | | SHEET A-41 INDICATE 3.0 TON SYSTEMS. A) THE CALCS | | | INDICATE A 2.0 TON SYSTEM FOR THE OFFICE/LAUNDRY BUT | | | THE SCHEDULE INDICATES A 1.5 TON SYSTEM. | | | | | | 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES | | | INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F | | | ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD | | | WHICH SPECIFIES 91 AND 45 DEGREES. | | | | | | 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE | | | PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE | | | INDICATING SW FOR ALL OF THE UNITS-. UNITS 1A AND 2D | | | APPEAR TO BE FACING NORTH, AND 1B, 1C, 2E, AND THE | | | OFFICE/LAUNDRY APPEAR TO BE FACING SOUTH. | | | | | | 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR | | | CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS. | | | | | | 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT | | | SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY | | | RATINGS, AND ELECTRICAL HEATING DATA. | | | | | | 6) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN | | | COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND SECTION 602 FBC-14 MECHANICAL. NOTE- | | | THIS COMMENT IS RESCINDED. | | | | | | 7) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION | | | OF THE EXTERIOR CONDENSERS. | | | | | | 8) NEW COMMENT: CLARIFY HOW THE EXHAUST FAN IN THE | | | LAUNDRY ROOM WAS SIZED AND PROVIDE AN EQUIPMENT | | | SCHEDULE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-09-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-19 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-19 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2017-09-19 17:08:06 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041277 | | | 9/19/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATION FORM R405-2014 INDICATES 2.5 | | | TON SYSTEMS FOR UNITS 1A AND 1B HOWEVER THE SCHEDULE ON | | | SHEET A-14 INDICATE 3.0 TON SYSTEMS. A) THE CALCS | | | INDICATE A 2.0 TON SYSTEM FOR THE OFFICE/LAUNDRY BUT | | | THE SCHEDULE INDICATES A 1.5 TON SYSTEM. | | | | | | 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES | | | INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F | | | ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD | | | WHICH SPECIFIES 91 AND 45 DEGREES. | | | | | | 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE | | | PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE | | | INDICATING SW FOR ALL OF THE UNITS-. UNITS 1A AND 2D | | | APPEAR TO BE FACING NORTH, AND 1B, 1C, 2E, AND THE | | | OFFICE/LAUNDRY APPEAR TO BE FACING SOUTH. | | | | | | 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR | | | CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS. | | | | | | 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT | | | SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY | | | RATINGS, AND ELECTRICAL HEATING DATA. | | | | | | 6) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN | | | COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND SECTION 602 FBC-14 MECHANICAL. | | | | | | 7) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION | | | OF THE EXTERIOR CONDENSERS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-02 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-02 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2017-05-02 16:44:06 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041277 | | | 5/2/17 | | | | | | 1) THE MECHANICAL PLANS ARE INCOMPLETE. PLEASE PROVIDE | | | THE FOLLOWING: | | | | | | A) AC COOLING HEATING CALCULATIONS- SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | B) ENERGY CALCULATIONS- SECTIONS C101.3, C101.5, AND | | | C401.2 FBC-14 ENERGY CONSERVATION. | | | C) MINIMUM VENTIALTION CALCULATIONS FOR ALL OCCUPIED | | | ROOMS AND SPACES. PROVIDE A TABLE THAT INCLUDES THE | | | REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR- TABLE 403.3 | | | FBC-14 MECHANICAL. | | | D) EXHAUST VENTILATION CALCULATIONS FOR THE RESTROOMS- | | | TABLE 403.3 | | | E) COMBUSTION AIR CALCULATIONS AND VENTING PLANS FOR | | | THE GAS DRYERS - SECTION 304 AND 501.1 FBC-14 ENERGY | | | CONSERVATION. | | | F) COMPLETE DUCT LAYOUT AND AIR DISTRIBUTION PLANS | | | SHOWING DUCT SIZES, DIFFUSER AND RETURN GRILL SIZES, | | | TRANSFER GRILLS OR DUCTS WHERE REQUIRED, AND CFM'S AT | | | EACH DEVICE. | | | G) COMPLETE AC EQUIPMENT SCHEDULES THAT INDICATE THE | | | MAKES AND MODELS OF THE COMPONENTS, COOLING AND HEATING | | | CAPACITIES, SUPPLY CFMS, EFFICIENCY RATINGS, AND | | | ELECTRICAL DATA. | | | H) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | | EXTERIOR CONDENSERS. | | | | | | 2) SHEET A-4.1: THE PLAN APPEARS TO SHOW AIR HANDLERS | | | IN THE ATTIC SPACES ABOVE THE HALLWAY IN THE MAIN | | | BUILDING, AND IN THE OFFICE WHICH IS PROHIBITED PER | | | SECTION C403.2.7.6 FBC-14 ENERGY COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-05 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-04 |
Time |
06:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2017-12-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-12-16 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-12-16 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2017-12-16 12:33:04 | 4TH REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN | | | COMPLIED WITH I SUGGEST A MEETING BE SCHEDULED TO GO | | | OVER COMMENTS BEFORE RESUBMITTAL. PLEASE CONNACT ME AT | | | 561-805-6711 | | | | | | 2. PARTIALLY COMPLIED THIS OCCUPANCY SHALL COMPLY WTH | | | FHA PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT | | | THAT WAS USED TO COMPLY WITH FHA ALSO SHOW WHICH DESIGN | | | SPECIFICATION IS USED FOR THE BATHROOMS A OR B . PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BATHROOM IN THE OFFICE IS A COMMON AREA AND | | | SHALL COMPLY WITH THE FHA AND ANSI 4.22 | | | | | | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | 2ND REVIEW PREVIOUS COMMENTS: | | | | | | 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE FIXTURES IN | | | THE BATHROOMS SHALL COMPLY WITH FHA | | | | | | 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO | | | BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM | | | GROUP. PER FBC PL 912.1 | | | | | | 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN | | | UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE | | | CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES. | | | PER FBC PL 1003.6 | | | | | | NEW COMMENT: | | | | | | 1. PLEASE LABEL SOIL STACKS ON THE FLOOR PLAN TO MATCH | | | RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-16 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-16 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2017-11-16 12:43:39 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 3RD REQUEST NOT COMPLIED A NARRATIVE | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A | | | DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE | | | FOUND WILL HELP EXPEDITE THE REVIEW. | | | | | | | | | 2. PARTIALLY COMPLIED THIS OCCUPANCY SHALL COMPLY WTH | | | FHA PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT | | | THAT WAS USED TO COMPLY WITH FHA ALSO SHOW WHICH DESIGN | | | SPECIFICATION IS USED FOR THE BATHROOMS A OR B . PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BATHROOM IN THE OFFICE IS A COMMON AREA AND | | | SHALL COMPLY WITH THE FHA AND ANSI 4.22 | | | | | | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | 2ND REVIEW PREVIOUS COMMENTS: | | | | | | 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE FIXTURES IN | | | THE BATHROOMS SHALL COMPLY WITH FHA | | | | | | 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO | | | BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM | | | GROUP. PER FBC PL 912.1 | | | | | | 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN | | | UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE | | | CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES. | | | PER FBC PL 1003.6 | | | | | | NEW COMMENT: | | | | | | 1. PLEASE LABEL SOIL STACKS ON THE FLOOR PLAN TO MATCH | | | RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-27 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-26 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2017-09-27 09:51:01 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 2ND REQUEST NOT COMPLIED A NARRATIVE | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A | | | DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE | | | FOUND WILL HELP EXPEDITE THE REVIEW. | | | | | | | | | 2. THE PLAN DOES NOT INDICATE WHAT TYPE OF OCCUPANCY | | | THIS PROJECT IS IF IT IS GOING TO BE MULTI FAMILY | | | RESIDENTIAL AN R3 OR R4 THE GROUND FLOOR UNIT WILL HAVE | | | TO COMPLY WITH THE FHA DESIGN MANUAL. PLEASE PROVIDE | | | TYPE OF OCCUPANCY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BATHROOM IN THE EXERCISE ROOM IS A COMMON AREA | | | AND SHALL COMPLY WITH THE FBC ACC 603,604, 606, 609 | | | | | | 4. THE TRANSFER SHOWER IN BATHROOM #1 IN UNIT 1A AND 1B | | | SHAL BE 36" X 36". PER FBC ACC 608.2.1 | | | | | | 5. THE GRAB BARS FOR THE ROLL IN SHOWER IN BATHROOM #1 | | | IN UNIT 1C SHALL COMPLY WITH. PER FBC ACC 608.3.2 | | | | | | 6. SHOW IN ALL ACCESSIBLE BATHROOMS THE CLEAR FLOOR | | | SPACE FOR THE TOILET , LAVATORY AND SHOWER. PER FBC ACC | | | 608.2.1 ,608.2.2.1 ,606.2,604.3.1 | | | | | | 7. SHOW HEIGHT DIMENSIONS FOR SHOWER SEATS AND | | | CONTROLS. PER FBC ACC 608.5.1 , 610.3 , 608.5.2 , | | | 610.3.2, 610.3.1 | | | | | | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | NEW COMMENTS: | | | | | | 1. GRAB BARS SHALL BE ABOVE THE FINISH FLOOR MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 | | | | | | 2. SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE SIDE | | | WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES | | | MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON | | | THE CONTROL WALL 15 INCHES (380 MM) MAXIMUM FROM THE | | | CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. PER | | | FBC ACC 608.5.1 | | | | | | 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO | | | BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM | | | GROUP. PER FBC PL 912.1 | | | | | | 4. SHT. A-3.1 PLEASE EXPAND RISER DIAGRAM IN THE AREA | | | OF S-5 AND S-4 THE LINES ARE DRAWN ON TOP OF EACH OTHER | | | I CAN NOT DETERMINE WHAT IS FIRST FLOOR OR 2ND OR WHICH | | | BATHROOM GROUP IS WHICH PLEASE CLARIFY. WPB AMEND TO | | | FBC 107.3.5.1.3(13) | | | | | | 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN | | | UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE | | | CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES. | | | PER FBC PL 1003.6 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-05-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-05-15 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-05-15 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2017-05-15 15:23:24 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. ON THE APPLICATION DESCRIPTION OF WORK IT STATES A | | | NEW BUILDING BUT ON THE PLANS IN THE TITLE BLOCK IT | | | STATES IT IS AN INTERIOR REMODEL PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE PLAN DOES NOT INDICATE WHAT TYPE OF OCCUPANCY | | | THIS PROJECT IS IF IT IS GOING TO BE MULTI FAMILY | | | RESIDENTIAL THE GROUND FLOOR UNIT WILL HAVE TO COMPLY | | | WITH THE FHA DESIGN MANUAL. PLEASE PROVIDE TYPE OF | | | OCCUPANCY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BATHROOM IN THE EXERCISE ROOM IS A COMMON AREA | | | AND SHALL COMPLY WITH THE FBC ACC 603,604, 606, 609 | | | | | | 4. THE TRANSFER SHOWER IN BATHROOM #1 IN UNIT 1A AND 1B | | | SHAL BE 36" X 36". PER FBC ACC 608.2.1 | | | | | | 5. THE GRAB BARS FOR THE ROLL IN SHOWER IN BATHROOM #1 | | | IN UNIT 1C SHALL COMPLY WITH. PER FBC ACC 608.3.2 | | | | | | 6. SHOW IN ALL ACCESSIBLE BATHROOMS THE CLEAR FLOOR | | | SPACE FOR THE TOILET , LAVATORY AND SHOWER. PER FBC ACC | | | 608.2.1 ,608.2.2.1 ,606.2,604.3.1 | | | | | | 7. SHOW HEIGHT DIMENSIONS FOR SHOWER SEATS AND | | | CONTROLS. PER FBC ACC 608.5.1 , 610.3 , 608.5.2 , | | | 610.3.2, 610.3.1 | | | | | | 8. PLEASE LABEL THE SOILSTACKS ON PLAN VIEW TO COINCIDE | | | WITH TAGS ON RISER DIAGRAM. PER WPB AMEND TO FBC | | | 107.2.1, | | | | | | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | | | | REVIEW NOT COMPLETE | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-12-19 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-11-08 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2017-11-09 13:17:14 | 1.) PROVIDE CORRECT BIKE RACK DETAIL, CONTACT PLANNING | | | AND ZONING IF YOU ARE UNABLE TO LOCATE | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-09-14 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2017-09-15 14:12:36 | *REPEAT COMMENT* | | | | | | INCONSISTENCIES WITH APPROVED SITE PLAN I.E. SIDEWALKS, | | | BIKE RACKS. CONTACT PLANNING AND ZONING FOR APPROVED | | | SITE PLAN (DATED 10/18/16; RECEIVED BY PLANNING STAFF | | | ON 10/24/2016; APPROVED 11/3/2016) | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-05-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2017-05-17 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2017-05-18 12:18:11 | INCONSISTENCIES WITH APPROVED SITE PLAN I.E. SIDEWALKS, | | | BIKE RACKS. CONTACT PLANNING AND ZONING FOR APPROVED | | | SITE PLAN (DATED 10/18/16; RECEIVED BY PLANNING STAFF | | | ON 10/24/2016; APPROVED 11/3/2016) | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
|