Plan Review Details - Permit 17041277
Plan Review Stops For Permit 17041277
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-01-09 Cont ID  
Sent By jwitmer Date 2018-01-09 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2018-01-08 Time 09:39 Sent To  
Notes
2018-01-08 12:32:342014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041277
 ADD: 2115 MERCER AVE.
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 5TH REVIEW
 DATE: MON. JAN. 08/ 2018
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCT APPROVAL: ROOFING PRODUCTS AND
 ASSEMBLIES
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-12-07 Cont ID  
Sent By jwitmer Date 2017-12-07 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2017-12-07 Time 07:16 Sent To  
Notes
2017-12-07 14:22:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041277
 ADD: 2115 MERCER AVE.
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: THURS. DEC. 07/ 2017
 ACTION: DENIED
  
 1-3A) COMPLIED.
  
 3B) 4TH REQUEST. THIS REVIEW AGAIN NO SOILS REPORT WAS
 SUBMITTED. SOILS REPORTS NEED TO BE ORIGINAL SIGNED AND
 SEALED REPORTS. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5-7) COMPLIED.
  
 8) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCT APPROVAL: ROOFING PRODUCTS AND
 ASSEMBLIES
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 10) 4TH REQUEST. SEMI-COMPLIED. THE SHEET A11 DETAIL #
 1 SHOWS A HANDRAIL/ GUARDRAIL COMBINATION, THIS IS
 ALLOWED WHEN IN A R2 AND OR R3 DWELLING UNIT. PLEASE
 NOTE THESE ARE EXTERIOR STAIRS AND THE GUARDRAIL WILL
 NEED TO BE IN COMPLIANCE WITH 2014 FBC-B 1013.3 THE TOP
 OF THE GUARDRAIL IS TO BE 42 INCHES TALL. SEE THE 2014
 FBC-B 1013.3 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS
 THAN 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS
 FOLLOWS: (1.) FROM THE ADJACENT WALKING SURFACES;
  
 11-12) COMPLIED.
  
 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY,COLLATE AND STAPLE PLANS
 INTO SETS OF PLANS! A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-03 Cont ID  
Sent By jwitmer Date 2017-11-03 Time 14:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-11-17 07:53:05E-MAIL SENT TO SKIP:
 GOOD MORNING SKIP,
 I'VE SPOKEN WITH JOE CANNON IN REGARDS TO FLOOR SOUND
 UNDERLAYMENT. PLEASE REVIEW THE ATTACHMENT (PROFLEX
 RCU-500) AND THE REFERENCED STANDARDS, I HAVE ATTACHED
 THE STANDARD REFERENCE SHEETS FROM OUR CODE BOOK , THE
 DELTA IIC STANDARD REFERENCE IN THE PROFLEX DOCUMENT
 ASTM E 2179-03 IS NOT A STANDARD REFERENCE IN THE 2014
 FBC-B REFERENCED STANDARDS. WE DO NOT RECONIZE THIS
 STANDARD, IT IS NOT A RECONIZED STANDARD IN THE ICC
 CODES EITHER. NOTE THE PROFLEX RTU-500 ONLY RECEIVES A
 50 IIC ON A 6 INCH CONCRETE SLAB.
  
 ATTACHMENT: PROFLEX RCU-500. PDF
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2017-11-03 14:14:402014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041277
 ADD: 2115 MERCER AVE.
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: FRI. NOV. 03/ 2017
 ACTION: DENIED
  
 1) COVERSHEET A-1:
  
 1) COMPLIED.
  
 2.) 3RD REQUEST/ SEMI COMPLIED. THE COVERSHEET NOW
 INDICATES THE OCCUPANCY TYPE AS R-4, UP TO 90 DAYS, 16
 RESIDENTS AT ANY GIVEN TIME AND 2 STAFF MEMBERS, FULLY
 R13 SPRINKLERED BUILDING. WHAT WE ARE HAVING A PROBLEM
 WITH ON ALL THE FLOOR PLANS AND NEW LIFE SAFETY SHEETS
 A16 & A17 ALL SHOW 19 BEDS NOT THE MAXIMUM OF 16
 PERSONS. THE CODE STATES THERE WE DO NOT COUNT STAFF
 NOR DOES THE CODE REQUIRE STAFF TO SLEEP OVER. IT WOULD
 APPEAR ROOM 1C NEEDS TO BE DEFINED AS TO USAGE, WHO
 WILL USE THIS APARTMENT? IF THIS ROOM IS FOR STAFF
 INDICATE AS SUCH.
 FOR THIS REVIEW IT IS GOING TO BE ASSUMED UNIT 1C IS A
 STAFF ROOM, STAY R-4/ AND FAIR HOUSING, NOT
 ACCESSIBILITY. THIS NEEDS TO BE DEFINED ON THE PLANS.
 IF THIS IS TO BE A PATIENT SLEEPING QUARTERS THEN THE
 OCCUPANT LOAD IS 19 OVER THE ALLOWABLE R4 OCCUPANCY AND
 BECOMES A I-1 OCCUPANCY SEE FBC-B 308.3.
  
 2ND REVIEW COMMENTS. OCCUPANCY TYPE 301.1 SHORT TERM
 FACILITY OR LONG TERM FACILITY. . OCCUPANCY TYPE 301.1
 SHORT TERM FACILITY OR LONG TERM FACILITY. PLEASE NOTE
 ON THE COVERSHEET THERE IS A NOTE STATING THIS IS A
 SHORT TERM FACILITY. WHEN DEFINING SHORT TERM THE
 BUILDING CODE USES 30 DAYS OR LESS FOR SHORT TERM
 (TRANSIENT), LONGER STAYS ARE (NON-TRANSIENT). IT
 APPEARS THIS USAGE IS MORE OF A R2(WITH MORE THAN 16
 OCCUPANTS) FACILITY AN ALCOHOL AND OR DRUG REHAB CENTER
 WITH CONGREGATE CARE FACILITIES, (A BUILDING OR PART
 THERE OF THAT CONTAINS SLEEPING UNITS WHERE THE
 RESIDENTS SHARE BATHROOMS AND OR KITCHEN FACILITIES.
 THE OTHER ISSUE IS WITH THE UNITS CONTAINING 2 BEDROOMS
 AND 2 OCCUPANTS PER BEDROOM AND SHARED BATHROOMS AND OR
 KITCHEN FACILITIES THE UNIT ALSO RESEMBLES DORMITORIES!
 PLEASE DECLARE OCCUPANCY AND USAGE. 2014 FBC-B 302.1
 CLASSIFICATION.
  
 3A) COMPLIED. MINIMUM TYPE OF CONSTRUCTION (TABLE 503)
  
 3B) 3RD REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3C) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT
 ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2
 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 4) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5) COMPLIED.
  
 6) 3RD REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B
 SECTION 420 IS ACHIEVED.
 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL
 COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH
 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE.
  
 6A)3RD REQUEST. PLEASE PROVIDE WHERE THERE IS A WALL
 SCHEDULE, CUT SECTION THROUGH THE BEDROOM RATED WALLS
 SHOWING COMPLIANCE WITH FBC-B 420.2.RATED WALLS BETWEEN
 BEDROOMS AND OPENING PROTECTIVES. . 420.2 SEPARATION
 WALLS. WALLS SEPARATING DWELLING UNITS IN THE SAME
 BUILDING, WALLS SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND WALLS SEPARATING DWELLING OR SLEEPING
 UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE
 SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS
 IN ACCORDANCE WITH SECTION 708.
  
 6B) 3RD REQUEST. THE RESPONSE INDICATES ON SHEET A-11
 INDICATES THE USE OF THE HAMBRO FLOOR SYSTEM AND UL
 LISTING G525. PLEASE PROVIDE THE ASSEMBLY ON THE SET OF
 PLANS SO THE INSPECTOR CAN VERIFY THE COMPONENTS THAT
 MAKE UP THE ASSEMBLY. THE FLOOR SYSTEM WILL NEED TO BE
 2 HOUR FIRE RATED ASSEMBLY FROM BOTH SIDES OF THE
 ASSEMBLY SINCE THE ASSEMBLY IS NOT SYMMETRIC. PLEASE
 REVIEW TABLE 707.3.10 FOR THE 2 HOUR RATING. THE
 RESPONSE LETTER INDICATES FBC-B 711.3 ALLOWS FOR THE
 ASSEMBLY TO BE ? HOUR. PLEASE REVIEW THE EXCEPTION IS
 FOR NFPA 13 SYSTEM UNDER 903.3.1.1. THE FIRE PROTECTION
 PLANS INDICATE FIRE SPRINKLERS DESIGNED TO NFPA
 903.3.1.2 OR NFPA 13R.
  
 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 6C) SEMI-COMPLIED. THE SUBMITTED FIRE SPRINKLER PLANS
 SUBMITTED ARE COLOR PHOTOCOPIED SIGNATURES. [F] 420.4
 AUTOMATIC SPRINKLER SYSTEM. GROUP R OCCUPANCIES SHALL
 BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 903.2.8. GROUP I-1
 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.2.6. QUICKRESPONSE OR RESIDENTIAL AUTOMATIC
 SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 903.3.2.
  
 6D)3RD REQUEST. SEMI-COMPLIED. THE LIFE SAFETY PLAN
 A-16 THE 1ST FLOOR SHOWS A LAYOUT OF SMOKE ALARM
 DEVICES, PULL STATIONS AND EXIT LIGHTS EMERGENCY
 LIGHTS. SHEET A16 THE 1ST FLOOR IS MISSING SMOKE
 DETECTORS OUTSIDE UNIT 1B BEDROOM HALLWAY & SHEET A17
 THE 2ND FLOOR SHOWS NO SMOKE DETECTORS EITHER INSIDE OR
 OUTSIDE OF THE BEDROOM UNITS. 2014 FBC-B 907.1.1
 CONSTRUCTION DOCUMENTS.
 [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. FIRE
 ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED IN
 GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE WITH
 SECTIONS 907.2.6, 907.2.8 AND 907.2.9, RESPECTIVELY.
 SINGLE-OR MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE WITH SECTION 907.2.11.
  
 7) COMPLIED.
  
 8) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 10) 3RD ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR
 HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW
 THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3),
 CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6),
 GUARDS 1013.3, OPENING LIMITATIONS (1013.4),
 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS
 SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF
 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL
 THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS
 SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50
 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
  
 PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF
 MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR
 GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF
 PLANS.
  
 11) 3RD ROUND OF COMMENTS. THE RESPONSE INDICATES THE
 UNDERLAYMENT CRITERIA ARE FOUND ON SHEET A-5.
 PLEASE PROVIDE THE ACTUAL TEST REPORTS FOR SOUND
 UNDERLAYMENT USING THE HAMBRO SYSTEM WITH 3 INCH
 CONCRETE SLAB. PLEASE ALSO NOTE THAT FOR EACH FLOORING
 TYPE, TILE. AND WOOD SEPARATE TEST ARE REQUIRED.
  
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR
 SYSTEM/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 11A)3RD REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11B)3RD REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C) 3RD REQUEST. TYPE V CONSTRUCTION: FBC-B-2014 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO
 SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By jwitmer Date 2017-09-27 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2017-09-27 Time 15:00 Sent To  
Notes
2017-09-27 16:50:092014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041277
 ADD: 2115 MERCER AVE.
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. SEPT. 27/ 2017
 ACTION: DENIED
  
 1) COVERSHEET A-1:
  
 1A) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF
 WORK INDICATES NEW BUILDINGS, TWO STORIES WHEREAS THE
 TITLE BLOCK INDICATES THIS IS AN INTERIOR REMODEL.
 DISCREPANCY IN THE DESCRIPTION OF WORK. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B)SEMI-COMPLIED. THIS REVIEW THERE IS A INDEX WITHIN
 THE COVERSHEET. NEED A UPDATED CODE ANALYSIS FOR THE
 BUILDING INFORMATION. WITHOUT THE OCCUPANCY TYPE BEING
 DECLARED AND THE MINIMUM BUILDING TYPE DECLARED IT IS
 ONLY ASSUMPTIONS, A THOROUGH REVIEW CANNOT BE
 ACCOMPLISHED. THE DESIGNER OF RECORD HAS NOT PROVIDED A
 CODE ANALYSIS, PROVIDING THE OCCUPANCY TYPE, USAGE,
 (ALCOHOL AND OR DRUG CENTER, GROUP HOME), THE TYPE OF
 MINIMUM CONSTRUCTION REQUIRED, OR IF FIRE SPRINKLERED.
 NOTE FIRE SPRINKLER PLANS FOR R13 SYSTEM SUBMITTED.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 2. OCCUPANCY TYPE 301.1 SHORT TERM FACILITY OR LONG
 TERM FACILITY. . OCCUPANCY TYPE 301.1 SHORT TERM
 FACILITY OR LONG TERM FACILITY. PLEASE NOTE ON THE
 COVERSHEET THERE IS A NOTE STATING THIS IS A SHORT TERM
 FACILITY. WHEN DEFINING SHORT TERM THE BUILDING CODE
 USES 30 DAYS OR LESS FOR SHORT TERM (TRANSIENT), LONGER
 STAYS ARE (NON-TRANSIENT). IT APPEARS THIS USAGE IS
 MORE OF A R2(WITH MORE THAN 16 OCCUPANTS) FACILITY AN
 ALCOHOL AND OR DRUG REHAB CENTER WITH CONGREGATE CARE
 FACILITIES, (A BUILDING OR PART THERE OF THAT CONTAINS
 SLEEPING UNITS WHERE THE RESIDENTS SHARE BATHROOMS AND
 OR KITCHEN FACILITIES. THE OTHER ISSUE IS WITH THE
 UNITS CONTAINING 2 BEDROOMS AND 2 OCCUPANTS PER BEDROOM
 AND SHARED BATHROOMS AND OR KITCHEN FACILITIES THE UNIT
 ALSO RESEMBLES DORMITORIES! PLEASE DECLARE OCCUPANCY
 AND USAGE. 2014 FBC-B 302.1 CLASSIFICATION.
  
 3) MINIMUM TYPE OF CONSTRUCTION (TABLE 503)
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 10) FL. ACCESSIBILITY CODE OR FAIR HOUSING, VERTICAL
 ACCESSIBILITY?
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 FAIR HOUSING REQUIREMENTS
  
 11. NO FINISH SCHEDULE!!!!INTERIOR REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 12.2ND REQUEST. SPECIAL SYSTEMS:
 ELEVATORS
 LIFTS
 FLORIDA ACCESSIBILITY (SHORT TERM/ TRANSIENT) VERSES
 FAIR HOUSING (LONG TERM/ NON-TRANSIENT).
  
  
  
 1C) THE PLANS DO NOT INDICATE IF THE CONCEPT FOR THIS
 PROJECT TO BE CONSIDERED 1 BUILDING (TOTAL SQUARE FOOT,
 FOOT PRINT OR IF THEY ARE TRYING TO COMPLY UNDER THE
 BUILDINGS ON THE SAME LOT, SECTION 503.1.2.
  
 1D) COMPLIED. R13 FIRE SPRINKLER PLANS.
  
 1E) NEW COMMENT. SHEET A2.1 DESIGN LIVE LOADS PLANS
 INDICATE: STAIRS & CORRIDORS 60 PSF CORRECT.
 2014 FBC-B TABLE 1607.1(30) STAIRS 100 PSF,
 2014 FBC-B TABLE 1607.1(25) PUBLIC ROOMS & CORRIDORS
 100 PSF
  
  
 1F) COMPLIED.
  
 2) 2ND REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT
 ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2
 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 4) 2ND REQUEST. ART IN PUBLIC PLACES. THE CITY OF WEST
 PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT
 THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT
 FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5) COMPLIED.
  
 6) 2ND REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B
 SECTION 420 IS ACHIEVED.
 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL
 COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH
 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE.
  
 6A)2ND REQUEST. RATED WALLS BETWEEN BEDROOMS. 420.2
 SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS IN
 THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN
 THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708.
  
 6B) 2ND REQUEST. 420.3 HORIZONTAL SEPARATION. FLOOR
 ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 6C) COMPLIED. [F] 420.4 AUTOMATIC SPRINKLER SYSTEM.
 GROUP R OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE
 EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 903.2.6. QUICKRESPONSE OR
 RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.2.
  
 6D) [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS.
 FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED
 IN GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE
 WITH SECTIONS 907.2.6, 907.2.8 AND 907.2.9,
 RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE ALARMS
 SHALL BE IN ACCORDANCE WITH SECTION 907.2.11.
  
 7A) 2ND REQUEST. THE COVERSHEET NOW INDICATES WIND
 DESIGN. THE COVERSHEET UNDER THE WIND DESIGN INDICATES
 A BASIC WIND SPEED OF 160 MPH, THEN 2 LINES DOWN A WIND
 SPEED IN 3 SECOND GUST OF 140 MPH. THEN ON SHEET A2.1
 WIND SPEED OF 170 MPH. PLEASE SEE THE 2014 FBC-B FIGURE
 1609A FOR BUILDINGS WITH A RISK CATEGORY II. THE FIGURE
 SHOWS THE CITY OF WEST PALM BEACH IN A WIND ZONE OF 170
 VULT/ 3 SECOND GUST. THE WIND SPEED CONVERSION TABLE
 1609.3.1 INDICATES FOR 170 VULT THE CONVERSION TO VASD
 WILL BE 132 VASD/ 3 SECOND GUST. PLEASE CORRECT.
 1ST ROUND OF COMMENTS. SHEET A8 & A9 SHOW PRESSURES FOR
 COMPONENTS AND CLADDING, BUT THERE IS NO WIND DESIGN
 CRITERIA TO KNOW IF THESE PRESSURES ARE ACCURATE. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) 2ND REQUEST, UNTIL THE WIND DESIGN PRESSURES ARE IN
 DESIGN PRESSURES (VASD) THE PRODUCT APPROVALS SUBMITTED
 CANNOT BE CHECKED FOR CODE COMPLIANCE UNTIL THE WIND
 DESIGN IS FINALIZED.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 10) 2ND ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR
 HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW
 THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3),
 CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6),
 GUARDS 1013.3, OPENING LIMITATIONS (1013.4),
 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS
 SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF
 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL
 THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS
 SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50
 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
  
 PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF
 MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR
 GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF
 PLANS.
  
 11) 2ND ROUND OF COMMENTS. THE PLANS DO NOT INDICATE
 WHAT THE 2ND FLOOR FINISHES WILL BE? PLEASE SHOW
 COMPLIANCE WITH:
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR
 SYSTEM/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO
 SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2017-05-10 Time 14:30 Sent To  
Notes
2017-05-12 11:38:552014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041277
 ADD: 2115 MERCER AVE.
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. MAY 12/ 2017
 ACTION: DENIED
  
 1) COVERSHEET A-1:
  
 1A) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF
 WORK INDICATES NEW BUILDINGS, TWO STORIES WHEREAS THE
 TITLE BLOCK INDICATES THIS IS AN INTERIOR REMODEL.
 DISCREPANCY IN THE DESCRIPTION OF WORK. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE COVERSHEET APPEARS TO BE THE CODE ANALYSIS FOR
 THE BUILDING INFORMATION. THERE IS NO INDEX SHEET
 LISTING WHERE THIS INFORMATION CAN BE FOUND. WITHOUT
 THE OCCUPANCY TYPE BEING DECLARED AND THE MINIMUM
 BUILDING TYPE DECLARED IT IS ONLY ASSUMPTIONS, A
 THOROUGH REVIEW CANNOT BE ACCOMPLISHED.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY TYPE 301.1 SHORT TERM FACILITY OR LONG
 TERM FACILITY
 3) MINIMUM TYPE OF CONSTRUCTION (TABLE 503)
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 NO LIFE SAFETY SHEET!!!!!!!
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 10) FL. ACCESSIBILITY CODE OR FAIR HOUSING, VERTICAL
 ACCESSIBILITY?
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 FAIR HOUSING REQUIREMENTS
  
 11. NO FINISH SCHEDULE!!!!INTERIOR REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 12. SPECIAL SYSTEMS:
 ELEVATORS
 ESCALATORS
 LIFTS
  
  
  
 1C) THE PLANS DO NOT INDICATE IF THE CONCEPT FOR THIS
 PROJECT TO BE CONSIDERED 1 BUILDING (TOTAL SQUARE FOOT,
 FOOT PRINT OR IF THEY ARE TRYING TO COMPLY UNDER THE
 BUILDINGS ON THE SAME LOT, SECTION 503.1.2.
  
 1D) FIRE SPRINKLER PLANS WILL BE REQUIRED FOR EITHER AN
 I OCCUPANCY (903.2.6) OR AN R OCCUPANCY (903.2.8.)
 W. P. B. ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER
 DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH
 INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR
 MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR
 CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA
 STATUTES, MAY DESIGN A FIRE
 SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN
 THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF
 THE ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR
 DELETION OF NOT MORE THAN 49 HEADS, NOT WITHSTANDING
 THE SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM.
  
 1E) UNDER THE HEADING BUILDING CALCULATIONS THE PLANS
 INDICATE A 2 STORY 4 UNIT FOOTPRINT WHEREAS SHEET A-3
 ONLY SHOWS 3 UNITS ON THE GROUND FLOOR AND 2 UNITS ON
 THE SECOND STORY. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED, IT APPEARS THIS MAYBE A TYPO.
  
 1F) DISCREPANCY IN THE COVERSHEET. BUILDING CALCULATION
 VERSES SHEET A-3. THE COVERSHEET INDICATES A 1 STORY
 LAUNDRY AND OFFICE VERSES SHEET A-3 SHOWS FOR THE SAME
 BUILDING AN EXERCISE ROOM AND LAUNDRY. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS. 2014 FBC-ENERGY
 CODE. C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 4) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5) SHEET A4: UNITS 1A, 1B, 2D & 2E ALL SHOW WHAT
 APPEARS TO BE EITHER A DIVIDER OR PONY WALL (HALF
 WALL).
 THE PLANS DO NOT HAVE A DETAIL OF THIS AREA, AND THERE
 IS NO FURNITURE PLAN SHOWING IF THERE IS 2 BEDS OR 4
 BEDS IN EACH OF THE IDENTIFIED BEDROOMS. AGAIN THE
 OCCUPANT LOAD CANNOT BE IDENTIFIED NOR CAN THE PLUMBING
 FIXTURE COUNT. FBC-B TABLE 1004.1.2.
  
 6) PLEASE SHOW HOW COMPLIANCE WITH FBC-B SECTION 420 IS
 ACHIEVED.
 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL
 COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH
 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE.
  
 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS
 IN THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND WALLS SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708.
  
 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R
 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.6. QUICKRESPONSE OR
 RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.2.
  
 [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. FIRE
 ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED IN
 GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE WITH
 SECTIONS 907.2.6, 907.2.8 AND 907.2.9, RESPECTIVELY.
 SINGLE-OR MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE WITH SECTION 907.2.11.
  
 7) SHEET A8 & A9 SHOW PRESSURES FOR COMPONENTS AND
 CLADDING, BUT THERE IS NO WIND DESIGN CRITERIA TO KNOW
 IF THESE PRESSURES ARE ACCURATE. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) 2010/ 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 9) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 10) PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF
 MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR
 GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF
 PLANS.
  
 11) THE PLANS DO NOT INDICATE WHAT THE 2ND FLOOR
 FINISHES WILL BE? PLEASE SHOW COMPLIANCE WITH:
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR
 SYSTEM/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO
 SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-12-29 Cont ID  
Sent By jpearson Date 2017-12-29 Time 07:45 Rev Time 0.00
Received By jpearson Date 2017-12-29 Time 07:45 Sent To  
Notes
2017-12-29 07:45:03NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS,
 STAMPED NEW SET.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-12-07 Cont ID  
Sent By jpearson Date 2017-12-07 Time 07:24 Rev Time 0.00
Received By jpearson Date 2017-12-07 Time 07:24 Sent To B
Notes
2017-12-07 07:24:53NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS,
 STAMPED NEW SET.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-12 Cont ID  
Sent By jpearson Date 2017-11-12 Time 08:43 Rev Time 0.00
Received By jpearson Date 2017-11-12 Time 08:43 Sent To  
Notes
2017-11-12 08:43:41NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS,
 STAMPED NEW SET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-19 Cont ID  
Sent By jpearson Date 2017-09-19 Time 12:33 Rev Time 0.00
Received By jpearson Date 2017-09-19 Time 12:33 Sent To  
Notes
2017-09-19 12:33:50NO CHANGE TO PREVIOUSLY APPORVED ELECTRICAL PLANS,
 STAMPED NEW SET.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 14:08 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 14:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By Mgonzale Date 2017-10-04 Time   Rev Time 1.00
Received By mgonzale Date 2017-10-04 Time   Sent To I
Notes
2017-10-04 16:12:14PLANS ARE UNDER REVIEW THRU ENGINEERING,
 [email protected] (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By mgonzale Date 2017-05-18 Time   Rev Time 1.00
Received By   Date 2017-05-18 Time   Sent To I
Notes
2017-05-18 15:49:16SEPARATE ENGINEERING SUBMITTAL WILL BE REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2017-12-21 Cont ID  
Sent By pleduc Date 2017-12-21 Time   Rev Time 0.00
Received By pleduc Date 2017-12-21 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-12-01 Cont ID  
Sent By pleduc Date 2017-12-01 Time   Rev Time 0.00
Received By pleduc Date 2017-12-01 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-06 Cont ID  
Sent By pleduc Date 2017-11-06 Time   Rev Time 0.00
Received By pleduc Date 2017-11-06 Time 12:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-06 Cont ID  
Sent By pleduc Date 2017-09-06 Time   Rev Time 0.00
Received By pleduc Date 2017-09-06 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By pleduc Date 2017-05-04 Time   Rev Time 0.00
Received By pleduc Date 2017-05-03 Time 16:21 Sent To  
Notes
2017-05-04 12:36:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE ARE INCORRECT REFERENCES TO
 CURRENT EDITIONS OF THE NFPA 1 & 101; 2015.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE CORRECT.
  
  
 2) A LIFE SAFETY REVIEW SHEET WAS NOT PROVIDED
 INDICATING COMPLIANCE WITH ANY LIFE SAFETY OCCUPANCY
 CHAPTER OF NFPA 101. IT APPEARS THAT THE OCCUPANCY MAY
 BE CHAPTER IS NFPA 101, CHAPTER 30, NEW APARTMENT
 BUILDINGS. CHAPTER 32 RESIDENTIAL BOARD AND CARE, OR
 CHAPTER 26 LODGING AND ROOMING HOUSES.
  
 IT APPEARS THAT THERE ARE TWO SEPARATE SLEEPING AREAS
 PER BEDROOM.
  
 PLEASE REVIEW AND PROVIDE DETAILS AS TO THE USE AND
 FUNCTION OF THESE APARTMENTS AND THE APPLICABLE NFPA
 101 OCCUPANCY CHAPTER AND ALL LIFE SAFETY FEATURES
 REQUIREMENTS OF THAT CHAPTER.
  
  
  
 3) SHEET A 4 - A METAL GATE IS INDICATED IN THE PATH OF
 EXIT TRAVLE. BUT NO DETAIL PROVIDED AS TO THE EXIT
 HARDWARE IN COMPLINACE WITH NFPA 101, CHAPTER 7, MEANS
 OF EGRESS.
  
 30.2.2.2 DOORS.
 30.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 30.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 30.2.2.2.2.1, 30.2.2.2.2.2, 30.2.2.2.2.3, OR
 30.2.2.2.2.4.
 30.2.2.2.2.1* NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
  
 7.2.1.4 SWING AND FORCE TO OPEN.
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR PIVOTED-SWINGING TYPE, AND SHALL BE
 INSTALLED TO BE CAPABLE OF SWINGING FROM ANYPOSITION TO
 THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT IS
 INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS:
 (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN
 CHAPTER 24, SHALL BE PERMITTED.
 (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE
 OCCUPANCIES, AS PROVIDED IN CHAPTERS 32 AND 33, SHALL
 BE PERMITTED.
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTAL-SLIDING OR VERTICAL-ROLLING SECURITY GRILLES
 OR DOOR ASSEMBLIES THAT ARE PART OF THE REQUIRED MEANS
 OF EGRESS SHALL BE PERMITTED, PROVIDED THAT ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN THE FULLY OPEN POSITION DURING THE PERIOD OF
 OCCUPANCY BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT
 LESS THAN 1 IN. (25 MM) HIGH ON A CONTRASTING
 BACKGROUND THAT READS AS FOLLOWS: THIS DOOR TO REMAIN
 OPEN WHEN THE BUILDING IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE SPACE WITHOUT THE USE OF ANY SPECIAL
 KNOWLEDGE OR EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR ASSEMBLIES.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
  
 PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS.
  
  
  
  
 4) SHEET A 5 - STAIRS, HARDRAILS AND RAILINGS ARE
 INDICATED; HOWEVER NO DETAILS ARE PROVIDED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF
 SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2,
 UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2.
  
 7.2.2.3 STAIR DETAILS.
 7.2.2.3.1 CONSTRUCTION.
 7.2.2.3.1.1 ALL STAIRS SERVING AS REQUIRED MEANS OF
 EGRESS SHALL BE OF PERMANENT FIXED CONSTRUCTION, UNLESS
 THEY ARE STAIRS SERVING SEATING THAT IS DESIGNED TO BE
 REPOSITIONED IN ACCORDANCE WITH CHAPTERS 12 AND 13.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5
 OR 7.2.2.4.1.6.
  
 PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS
  
  
  
 5) SEET A 6 & 7 - THERE ARE NO EXIT SIGNS IN ANY EXIT
 CORRIDOR.
  
 NFPA 101, CAPTER 30, NEW APARTMENT BUILDINGS
  
 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL
 BUILDINGS REQUIRING MORE THAN ONE EXIT.
  
  
  
  
 6) SHEET 6 & 7 - THE SUBMITTAL DOES NOT INDICATED EXITS
 LEADING TO A PUBLIC WAY.
  
 30.2.7 DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL
 COMPLY WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
  
 PLEASE PROVIDE A DETAIL INDICATING COMPLIANCE WITH THE
 REQUIREMENTS.
  
  
  
  
 7) NO SHEET SUBMITTALS - THERE ARE NO FIRE SPRINKLER
 DOCUMENTS WITH THIS SUBMITTAL.
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
  
 PLEASE REVIEW AND PROVIDES APPLICABLE SIGNED AND SEALED
 EOR PLAN SHEETS OR WRITTEN NARRATIVE DOCUMENT
 CONTAINING THE SAME INFO. SHOP DRAWINGS CAN THEN BE
 PRODUCED, PREPARED AND SUBITTED SEPARATELY BY A FIRE
 SPRINKLER CONTRACTOR.
  
  
  
 8) SHEET A 8 - LIGHTWEIGHT TRUSS FLOORS AND TRUSSES ARE
 INDICATED.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 10) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A
 COMPLETE REVIEW OF THE LIFE SAFETY FEATURES AND
 PROTECTION OF THIS PROJECT.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2018-01-05 Cont ID  
Sent By gjohnson Date 2018-01-05 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2018-01-05 Time 15:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2017-12-16 Cont ID  
Sent By gjohnson Date 2017-12-16 Time 12:37 Rev Time 0.00
Received By gjohnson Date 2017-12-16 Time 12:37 Sent To  
Notes
2017-12-16 12:40:424TH REVIEW
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PREVIOUS GAS COMMENTS: NOT COMPLIED I SUGGEST A MEETING
 TO BE SCHEDULED TO GO OVER COMMENTS PRIOR TO NEXT
 SUBMITTAL.
  
  
  
 2. THE TANKLESS WATER HEATER SHALL BE MOUNTED 4' AWAY
 FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE
 INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC
 107.2.1
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER
 FBC FG 408.4
  
 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT
 SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH
 APPLIANCE . WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. THE FIRST SECTION OF PE PIPE AFTER METER IS SHOWN AS
 3' 10" ON THE RISER AND 25' 8" ON THE FLOOR PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE SIZING TABLES LISTED ON THE PLAN SHT. A-3.1 ARE
 .5 PSI SYSTEMS IN THE CODE BOOK BUT ARE SHOWN AS 2 PSI
 ON THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. THE GENERAL NOTES ON SHT P-3.1 REFERENCES LP GAS
 RISER SHOWS NATURAL GAS PLEASE CLARIFY AND REMOVE
 INCORRECT NOTES. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 13:14 Rev Time 0.00
Received By gjohnson Date 2017-11-16 Time 13:14 Sent To  
Notes
2017-11-16 13:27:393RD REVIEW
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PREVIOUS GAS COMMENTS: NOT COMPLIED
  
  
  
 2. THE TANKLESS WATER HEATER SHALL BE MOUNTED 4' AWAY
 FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE
 INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC
 107.2.1
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER
 FBC FG 408.4
  
 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT
 SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH
 APPLIANCE . WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. THE FIRST SECTION OF PE PIPE AFTER METER IS SHOWN AS
 3' 10" ON THE RISER AND 25' 8" ON THE FLOOR PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE SIZING TABLES LISTED ON THE PLAN SHT. A-3.1 ARE
 .5 PSI SYSTEMS IN THE CODE BOOK BUT ARE SHOWN AS 2 PSI
 ON THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. THE GENERAL NOTES ON SHT P-3.1 REFERENCES LP GAS
 RISER SHOWS NATURAL GAS PLEASE CLARIFY AND REMOVE
 INCORRECT NOTES. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 10:24 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 10:24 Sent To  
Notes
2017-09-27 10:28:082ND REVIEW
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC
 FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @
 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE.
  
 2. THE TANKLES WATER HEATER SHALL BE MOUNTED 4' AWAY
 FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE
 INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC
 107.2.1
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER
 FBC FG 408.4
  
 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT
 SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH
 APPLIANCE . WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By gjohnson Date 2017-05-17 Time 10:21 Rev Time 0.00
Received By gjohnson Date 2017-05-17 Time 10:21 Sent To  
Notes
2017-05-17 10:32:351ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC
 FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @
 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-01-09 Cont ID  
Sent By jwitmer Date 2018-01-09 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 14:39 Sent To  
Notes
2017-12-20 14:39:39C31

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-16 Cont ID  
Sent By gjohnson Date 2017-12-16 Time 12:41 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 15:30 Sent To  
Notes
2017-11-30 15:32:15C31

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 13:27 Rev Time 0.00
Received By gjohnson Date 2017-10-27 Time 09:16 Sent To  
Notes
2017-10-31 09:16:30C37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-05 Cont ID  
Sent By shill Date 2017-10-05 Time 06:21 Rev Time 0.00
Received By shill Date 2017-08-31 Time 10:54 Sent To  
Notes
2017-09-01 10:54:29C02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-19 Cont ID  
Sent By lmarchan Date 2017-05-19 Time 10:01 Rev Time 0.00
Received By lmarchan Date 2017-04-27 Time 15:15 Sent To  
Notes
2017-04-28 15:16:04C18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-01-16 Cont ID  
Sent By skennedy Date 2018-01-16 Time 11:33 Rev Time 0.00
Received By skennedy Date 2018-01-16 Time 11:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-12-18 Cont ID  
Sent By shill Date 2017-12-18 Time 09:07 Rev Time 0.00
Received By shill Date 2017-12-07 Time 07:16 Sent To  
Notes
2017-12-07 14:43:12IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2017-05-10 Time 14:30 Sent To  
Notes
2017-05-12 11:38:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-12-28 Cont ID  
Sent By ccole Date 2017-12-28 Time 11:08 Rev Time 0.00
Received By ccole Date 2017-12-28 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-12-11 Cont ID  
Sent By ccole Date 2017-12-11 Time 16:22 Rev Time 0.00
Received By ccole Date 2017-12-11 Time 16:22 Sent To  
Notes
2017-12-11 16:32:464TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17041277
 12/11/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED ENERGY CALCULATIONS HAVE NOT BEEN PROVIDED
 FOR UNITS 1A, 1B, 1C, 2D, & 2E. THE PREVIOUS SUBMITTALS
 WERE VOIDED.
  
 2) THE FLOOR PLAN DRAWING INDICATES 3.0 TON AC SYSTEMS
 FOR ALL UNITS, HOWEVER THE SCHEDULE INDICATES 2.5 TON
 SYSTEMS FOR UNITS 1A, 1B, 1C, & 2D. PLEASE NOTE THAT
 THE REVISED AC CALCULATIONS INDICATE A 3.0 SYSTEM FOR
 1B.
  
 3) 3RD REQUEST FOR WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE EXTERIOR CONDENSERS.
  
 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS- SEE SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-07 Cont ID  
Sent By ccole Date 2017-11-07 Time 14:22 Rev Time 0.00
Received By ccole Date 2017-11-07 Time 13:41 Sent To  
Notes
2017-11-07 14:30:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041277
 11/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS 1-7 WERE NOT ADDRESSED AND
 STILL EXIST WITH THE EXCEPTION OF COMMENT #6 WHICH IS
 RESCINDED BASED ON SECTION R403.2.2 FBC-14 ENERGY
 CONSERVATION.
 I HAVE REPRINTED THE COMMENTS BELOW. PLEASE PROVIDE A
 NARRATIVE RESPONSE TO HELP EXPEDITE THE REVIEW.
  
 PLEASE NOTE THAT THE FIRE-RESISTANCE RATINGS OF WALLS
 AND CEILINGS IN THE PROPOSED OCCUPOANCY HAVE STILL NOT
 BEEN COMPLETELY ESTABLISHED IN THE ARCHITECTURAL AND
 LIFE SAFETY PLANS, AND CURRENTLY NO FIRE DAMPERS ARE
 SHOWN ON THE PLANS TO PROTECT DUCTS THAT ARE
 PENETRATING BOTH THE VERTICAL AND HORIZONTAL
 ASSEMBLIES. WHEN THE PLANS ARE REVISED IN ACCORDANCE
 WITH THE BUILDING REVIEW COMMENTS, THESE ISSUES WILL BE
 ADDRESSED.
  
 1) THE ENERGY CALCULATION FORM R405-2014 INDICATES 2.5
 TON SYSTEMS FOR UNITS 1A AND 1B HOWEVER THE SCHEDULE ON
 SHEET A-41 INDICATE 3.0 TON SYSTEMS. A) THE CALCS
 INDICATE A 2.0 TON SYSTEM FOR THE OFFICE/LAUNDRY BUT
 THE SCHEDULE INDICATES A 1.5 TON SYSTEM.
  
 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES
 INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F
 ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD
 WHICH SPECIFIES 91 AND 45 DEGREES.
  
 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE
 PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE
 INDICATING SW FOR ALL OF THE UNITS-. UNITS 1A AND 2D
 APPEAR TO BE FACING NORTH, AND 1B, 1C, 2E, AND THE
 OFFICE/LAUNDRY APPEAR TO BE FACING SOUTH.
  
 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR
 CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS.
  
 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT
 SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY
 RATINGS, AND ELECTRICAL HEATING DATA.
  
 6) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND SECTION 602 FBC-14 MECHANICAL. NOTE-
 THIS COMMENT IS RESCINDED.
  
 7) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE EXTERIOR CONDENSERS.
  
 8) NEW COMMENT: CLARIFY HOW THE EXHAUST FAN IN THE
 LAUNDRY ROOM WAS SIZED AND PROVIDE AN EQUIPMENT
 SCHEDULE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-09-19 Cont ID  
Sent By ccole Date 2017-09-19 Time 16:55 Rev Time 0.00
Received By ccole Date 2017-09-19 Time 16:55 Sent To  
Notes
2017-09-19 17:08:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041277
 9/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATION FORM R405-2014 INDICATES 2.5
 TON SYSTEMS FOR UNITS 1A AND 1B HOWEVER THE SCHEDULE ON
 SHEET A-14 INDICATE 3.0 TON SYSTEMS. A) THE CALCS
 INDICATE A 2.0 TON SYSTEM FOR THE OFFICE/LAUNDRY BUT
 THE SCHEDULE INDICATES A 1.5 TON SYSTEM.
  
 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES
 INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F
 ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD
 WHICH SPECIFIES 91 AND 45 DEGREES.
  
 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE
 PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE
 INDICATING SW FOR ALL OF THE UNITS-. UNITS 1A AND 2D
 APPEAR TO BE FACING NORTH, AND 1B, 1C, 2E, AND THE
 OFFICE/LAUNDRY APPEAR TO BE FACING SOUTH.
  
 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR
 CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS.
  
 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT
 SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY
 RATINGS, AND ELECTRICAL HEATING DATA.
  
 6) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND SECTION 602 FBC-14 MECHANICAL.
  
 7) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE EXTERIOR CONDENSERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By ccole Date 2017-05-02 Time 16:33 Rev Time 0.00
Received By ccole Date 2017-05-02 Time 16:33 Sent To  
Notes
2017-05-02 16:44:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041277
 5/2/17
  
 1) THE MECHANICAL PLANS ARE INCOMPLETE. PLEASE PROVIDE
 THE FOLLOWING:
  
 A) AC COOLING HEATING CALCULATIONS- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 B) ENERGY CALCULATIONS- SECTIONS C101.3, C101.5, AND
 C401.2 FBC-14 ENERGY CONSERVATION.
 C) MINIMUM VENTIALTION CALCULATIONS FOR ALL OCCUPIED
 ROOMS AND SPACES. PROVIDE A TABLE THAT INCLUDES THE
 REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR- TABLE 403.3
 FBC-14 MECHANICAL.
 D) EXHAUST VENTILATION CALCULATIONS FOR THE RESTROOMS-
 TABLE 403.3
 E) COMBUSTION AIR CALCULATIONS AND VENTING PLANS FOR
 THE GAS DRYERS - SECTION 304 AND 501.1 FBC-14 ENERGY
 CONSERVATION.
 F) COMPLETE DUCT LAYOUT AND AIR DISTRIBUTION PLANS
 SHOWING DUCT SIZES, DIFFUSER AND RETURN GRILL SIZES,
 TRANSFER GRILLS OR DUCTS WHERE REQUIRED, AND CFM'S AT
 EACH DEVICE.
 G) COMPLETE AC EQUIPMENT SCHEDULES THAT INDICATE THE
 MAKES AND MODELS OF THE COMPONENTS, COOLING AND HEATING
 CAPACITIES, SUPPLY CFMS, EFFICIENCY RATINGS, AND
 ELECTRICAL DATA.
 H) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 EXTERIOR CONDENSERS.
  
 2) SHEET A-4.1: THE PLAN APPEARS TO SHOW AIR HANDLERS
 IN THE ATTIC SPACES ABOVE THE HALLWAY IN THE MAIN
 BUILDING, AND IN THE OFFICE WHICH IS PROHIBITED PER
 SECTION C403.2.7.6 FBC-14 ENERGY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-01-05 Cont ID  
Sent By gjohnson Date 2018-01-05 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2018-01-04 Time 06:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-12-16 Cont ID  
Sent By gjohnson Date 2017-12-16 Time 12:29 Rev Time 0.00
Received By gjohnson Date 2017-12-16 Time 12:29 Sent To  
Notes
2017-12-16 12:33:044TH REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH I SUGGEST A MEETING BE SCHEDULED TO GO
 OVER COMMENTS BEFORE RESUBMITTAL. PLEASE CONNACT ME AT
 561-805-6711
  
 2. PARTIALLY COMPLIED THIS OCCUPANCY SHALL COMPLY WTH
 FHA PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 THAT WAS USED TO COMPLY WITH FHA ALSO SHOW WHICH DESIGN
 SPECIFICATION IS USED FOR THE BATHROOMS A OR B . PER
 WPB AMEND TO FBC 107.2.1
  
 3. THE BATHROOM IN THE OFFICE IS A COMMON AREA AND
 SHALL COMPLY WITH THE FHA AND ANSI 4.22
  
 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 2ND REVIEW PREVIOUS COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE FIXTURES IN
 THE BATHROOMS SHALL COMPLY WITH FHA
  
 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO
 BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM
 GROUP. PER FBC PL 912.1
  
 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN
 UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE
 CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES.
 PER FBC PL 1003.6
  
 NEW COMMENT:
  
 1. PLEASE LABEL SOIL STACKS ON THE FLOOR PLAN TO MATCH
 RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 12:26 Rev Time 0.00
Received By gjohnson Date 2017-11-16 Time 12:26 Sent To  
Notes
2017-11-16 12:43:392ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 3RD REQUEST NOT COMPLIED A NARRATIVE
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A
 DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE
 FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
 2. PARTIALLY COMPLIED THIS OCCUPANCY SHALL COMPLY WTH
 FHA PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 THAT WAS USED TO COMPLY WITH FHA ALSO SHOW WHICH DESIGN
 SPECIFICATION IS USED FOR THE BATHROOMS A OR B . PER
 WPB AMEND TO FBC 107.2.1
  
 3. THE BATHROOM IN THE OFFICE IS A COMMON AREA AND
 SHALL COMPLY WITH THE FHA AND ANSI 4.22
  
 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 2ND REVIEW PREVIOUS COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE FIXTURES IN
 THE BATHROOMS SHALL COMPLY WITH FHA
  
 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO
 BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM
 GROUP. PER FBC PL 912.1
  
 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN
 UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE
 CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES.
 PER FBC PL 1003.6
  
 NEW COMMENT:
  
 1. PLEASE LABEL SOIL STACKS ON THE FLOOR PLAN TO MATCH
 RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 09:46 Rev Time 0.00
Received By gjohnson Date 2017-09-26 Time 18:55 Sent To  
Notes
2017-09-27 09:51:012ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST NOT COMPLIED A NARRATIVE
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A
 DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE
 FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
 2. THE PLAN DOES NOT INDICATE WHAT TYPE OF OCCUPANCY
 THIS PROJECT IS IF IT IS GOING TO BE MULTI FAMILY
 RESIDENTIAL AN R3 OR R4 THE GROUND FLOOR UNIT WILL HAVE
 TO COMPLY WITH THE FHA DESIGN MANUAL. PLEASE PROVIDE
 TYPE OF OCCUPANCY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE BATHROOM IN THE EXERCISE ROOM IS A COMMON AREA
 AND SHALL COMPLY WITH THE FBC ACC 603,604, 606, 609
  
 4. THE TRANSFER SHOWER IN BATHROOM #1 IN UNIT 1A AND 1B
 SHAL BE 36" X 36". PER FBC ACC 608.2.1
  
 5. THE GRAB BARS FOR THE ROLL IN SHOWER IN BATHROOM #1
 IN UNIT 1C SHALL COMPLY WITH. PER FBC ACC 608.3.2
  
 6. SHOW IN ALL ACCESSIBLE BATHROOMS THE CLEAR FLOOR
 SPACE FOR THE TOILET , LAVATORY AND SHOWER. PER FBC ACC
 608.2.1 ,608.2.2.1 ,606.2,604.3.1
  
 7. SHOW HEIGHT DIMENSIONS FOR SHOWER SEATS AND
 CONTROLS. PER FBC ACC 608.5.1 , 610.3 , 608.5.2 ,
 610.3.2, 610.3.1
  
 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 NEW COMMENTS:
  
 1. GRAB BARS SHALL BE ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE SIDE
 WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON
 THE CONTROL WALL 15 INCHES (380 MM) MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. PER
 FBC ACC 608.5.1
  
 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO
 BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM
 GROUP. PER FBC PL 912.1
  
 4. SHT. A-3.1 PLEASE EXPAND RISER DIAGRAM IN THE AREA
 OF S-5 AND S-4 THE LINES ARE DRAWN ON TOP OF EACH OTHER
 I CAN NOT DETERMINE WHAT IS FIRST FLOOR OR 2ND OR WHICH
 BATHROOM GROUP IS WHICH PLEASE CLARIFY. WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN
 UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE
 CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES.
 PER FBC PL 1003.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-15 Cont ID  
Sent By gjohnson Date 2017-05-15 Time 14:54 Rev Time 0.00
Received By gjohnson Date 2017-05-15 Time 09:29 Sent To  
Notes
2017-05-15 15:23:241ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ON THE APPLICATION DESCRIPTION OF WORK IT STATES A
 NEW BUILDING BUT ON THE PLANS IN THE TITLE BLOCK IT
 STATES IT IS AN INTERIOR REMODEL PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. THE PLAN DOES NOT INDICATE WHAT TYPE OF OCCUPANCY
 THIS PROJECT IS IF IT IS GOING TO BE MULTI FAMILY
 RESIDENTIAL THE GROUND FLOOR UNIT WILL HAVE TO COMPLY
 WITH THE FHA DESIGN MANUAL. PLEASE PROVIDE TYPE OF
 OCCUPANCY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE BATHROOM IN THE EXERCISE ROOM IS A COMMON AREA
 AND SHALL COMPLY WITH THE FBC ACC 603,604, 606, 609
  
 4. THE TRANSFER SHOWER IN BATHROOM #1 IN UNIT 1A AND 1B
 SHAL BE 36" X 36". PER FBC ACC 608.2.1
  
 5. THE GRAB BARS FOR THE ROLL IN SHOWER IN BATHROOM #1
 IN UNIT 1C SHALL COMPLY WITH. PER FBC ACC 608.3.2
  
 6. SHOW IN ALL ACCESSIBLE BATHROOMS THE CLEAR FLOOR
 SPACE FOR THE TOILET , LAVATORY AND SHOWER. PER FBC ACC
 608.2.1 ,608.2.2.1 ,606.2,604.3.1
  
 7. SHOW HEIGHT DIMENSIONS FOR SHOWER SEATS AND
 CONTROLS. PER FBC ACC 608.5.1 , 610.3 , 608.5.2 ,
 610.3.2, 610.3.1
  
 8. PLEASE LABEL THE SOILSTACKS ON PLAN VIEW TO COINCIDE
 WITH TAGS ON RISER DIAGRAM. PER WPB AMEND TO FBC
 107.2.1,
  
 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
  
 REVIEW NOT COMPLETE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2017-12-19 Time   Rev Time 0.00
Received By pgreilic Date 2017-12-19 Time 09:24 Sent To  
Notes
2017-12-14 11:23:48 
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2017-11-09 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-08 Time 10:58 Sent To  
Notes
2017-11-09 13:17:141.) PROVIDE CORRECT BIKE RACK DETAIL, CONTACT PLANNING
 AND ZONING IF YOU ARE UNABLE TO LOCATE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-09-15 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-14 Time 16:38 Sent To  
Notes
2017-09-15 14:12:36*REPEAT COMMENT*
  
 INCONSISTENCIES WITH APPROVED SITE PLAN I.E. SIDEWALKS,
 BIKE RACKS. CONTACT PLANNING AND ZONING FOR APPROVED
 SITE PLAN (DATED 10/18/16; RECEIVED BY PLANNING STAFF
 ON 10/24/2016; APPROVED 11/3/2016)
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-05-18 Time   Rev Time 0.00
Received By pgreilic Date 2017-05-17 Time 16:29 Sent To  
Notes
2017-05-18 12:18:11INCONSISTENCIES WITH APPROVED SITE PLAN I.E. SIDEWALKS,
 BIKE RACKS. CONTACT PLANNING AND ZONING FOR APPROVED
 SITE PLAN (DATED 10/18/16; RECEIVED BY PLANNING STAFF
 ON 10/24/2016; APPROVED 11/3/2016)
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]