Plan Review Details - Permit 17041268
Plan Review Stops For Permit 17041268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By cthroop Date 2017-05-05 Time 15:05 Rev Time 0.00
Received By cthroop Date 2017-05-05 Time 15:05 Sent To  
Notes
2017-05-05 15:08:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY LOCATION OF BARRIER AND GATES ON SURVEY.
 2. R4502.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED WITH A BARRIER
 COMPLYING WITH SECTIONS R4501.17.1.1 THROUGH
 R4501.17.1.14.
  
 R4501.17.1.1
 THE TOP OF THE BARRIER SHALL BE AT LEAST 48 INCHES
 (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE
 BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. THE
 MAXIMUM VERTICAL CLEARANCE BETWEEN GRADE AND THE BOTTOM
 OF THE BARRIER SHALL BE 2 INCHES (51 MM) MEASURED ON
 THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE
 SWIMMING POOL. WHERE THE TOP OF THE POOL STRUCTURE IS
 ABOVE GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR
 MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE THE BARRIER
 IS MOUNTED ON TOP OF THE POOL STRUCTURE, THE MAXIMUM
 VERTICAL CLEARANCE BETWEEN THE TOP OF THE POOL
 STRUCTURE AND THE BOTTOM OF THE BARRIER SHALL BE 4
 INCHES (102 MM).
  
 R4501.17.1.2
 THE BARRIER MAY NOT HAVE ANY GAPS, OPENINGS,
 INDENTATIONS, PROTRUSIONS, OR STRUCTURAL COMPONENTS
 THAT COULD ALLOW A YOUNG CHILD TO CRAWL UNDER, SQUEEZE
 THROUGH, OR CLIMB OVER THE BARRIER AS HEREIN DESCRIBED
 BELOW. ONE END OF A REMOVABLE CHILD BARRIER SHALL NOT
 BE REMOVABLE WITHOUT THE AID OF TOOLS. OPENINGS IN ANY
 BARRIER SHALL NOT ALLOW PASSAGE OF A 4-INCH-DIAMETER
 (102 MM) SPHERE.
  
 R4501.17.1.3
 SOLID BARRIERS WHICH DO NOT HAVE OPENINGS SHALL NOT
 CONTAIN INDENTATIONS OR PROTRUSIONS EXCEPT FOR NORMAL
 CONSTRUCTION TOLERANCES AND TOOLED MASONRY JOINTS.
  
 R4501.17.1.4
 WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND
 VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF
 THE HORIZONTAL MEMBERS IS LESS THAN 45 INCHES (1143
 MM), THE HORIZONTAL MEMBERS SHALL BE LOCATED ON THE
 SWIMMING POOL SIDE OF THE FENCE. SPACING BETWEEN
 VERTICAL MEMBERS SHALL NOT EXCEED 1 3/4 INCHES (44 MM)
 IN WIDTH. WHERE THERE ARE DECORATIVE CUTOUTS WITHIN
 VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT
 EXCEED 1 3/4 INCHES (44 MM) IN WIDTH.
  
 R4501.17.1.5
 WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND
 VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF
 THE HORIZONTAL MEMBERS IS 45 INCHES (1143 MM) OR MORE,
 SPACING BETWEEN VERTICAL MEMBERS SHALL NOT EXCEED 4
 INCHES (102 MM). WHERE THERE ARE DECORATIVE CUTOUTS
 WITHIN VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS
 SHALL NOT EXCEED 1 3/4 INCHES (44 MM) IN WIDTH.
  
 R4501.17.1.6
 MAXIMUM MESH SIZE FOR CHAIN LINK FENCES SHALL BE A 21/4
 INCH SQUARE (57 MM) UNLESS THE FENCE IS PROVIDED WITH
 SLATS FASTENED AT THE TOP OR BOTTOM WHICH REDUCE THE
 OPENINGS TO NO MORE THAN 1 3/4 INCHES (44 MM).
  
 R4501.17.1.7
 WHERE THE BARRIER IS COMPOSED OF DIAGONAL MEMBERS, THE
 MAXIMUM OPENING FORMED BY THE DIAGONAL MEMBERS SHALL BE
 NO MORE THAN 13/4 INCHES (44 MM).
  
 R4501.17.1.8
 ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED
 WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL
 SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED
 NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE
 GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON
 EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE
 REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY
 OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE
 ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM
 THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM.
  
 R4501.17.1.9
 WHERE A WALL OF A DWELLING SERVES AS PART OF THE
 BARRIER, ONE OF THE FOLLOWING SHALL APPLY:
  
 1. ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM
 THE HOME TO THE POOL SHALL BE EQUIPPED WITH AN EXIT
 ALARM COMPLYING WITH UL 2017 THAT HAS A MINIMUM SOUND
 PRESSURE RATING OF 85 DBA AT 10 FEET (3048 MM). ANY
 DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 INCHES
 (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE
 ALARMS ARE NOT REQUIRED FOR EACH DOOR OR WINDOW IF
 SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS
 BROKEN AT ANY OPENING.
  
 EXCEPTIONS:
  
 A. SCREENED OR PROTECTED WINDOWS HAVING A BOTTOM SILL
 HEIGHT OF 48 INCHES (1219 MM) OR MORE MEASURED FROM THE
 INTERIOR FINISHED FLOOR AT THE POOL ACCESS LEVEL.
  
 B. WINDOWS FACING THE POOL ON FLOOR ABOVE THE FIRST
 STORY.
  
 C. SCREENED OR PROTECTED PASS-THROUGH KITCHEN WINDOWS
 42 INCHES (1067 MM) OR HIGHER WITH A COUNTER BENEATH.
  
 2. ALL DOORS PROVIDING DIRECT ACCESS FROM THE HOME TO
 THE POOL MUST BE EQUIPPED WITH A SELF-CLOSING,
 SELF-LATCHING DEVICE WITH POSITIVE MECHANICAL
 LATCHING/LOCKING INSTALLED A MINIMUM OF 54 INCHES (1372
 MM) ABOVE THE THRESHOLD, WHICH IS APPROVED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 R4501.17.1.10
 WHERE AN ABOVE-GROUND POOL STRUCTURE IS USED AS A
 BARRIER OR WHERE THE BARRIER IS MOUNTED ON TOP OF THE
 POOL STRUCTURE, AND THE MEANS OF ACCESS IS A LADDER OR
 STEPS, THE LADDER OR STEPS EITHER SHALL BE CAPABLE OF
 BEING SECURED, LOCKED OR REMOVED TO PREVENT ACCESS, OR
 THE LADDER OR STEPS SHALL BE SURROUNDED BY A BARRIER
 WHICH MEETS THE REQUIREMENTS OF SECTIONS R4501.17.1.1
 THROUGH R4501.17.1.9 AND SECTIONS R4501.17.1.12 THROUGH
 R4501.17.1.14. WHEN THE LADDER OR STEPS ARE SECURED,
 LOCKED OR REMOVED, ANY OPENING CREATED SHALL NOT ALLOW
 THE PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE.
  
 R4501.17.1.11
 STANDARD SCREEN ENCLOSURES WHICH MEET THE REQUIREMENTS
 OF SECTION R4501.17 MAY BE UTILIZED AS PART, OR ALL, OF
 THE ?BARRIER? AND SHALL BE CONSIDERED A ?NONDWELLING?
 WALL. REMOVABLE CHILD BARRIERS SHALL HAVE ONE END OF
 THE BARRIER NONREMOVABLE WITHOUT THE AID OF TOOLS.
  
 R4501.17.1.12
 THE BARRIER MUST BE PLACED AROUND THE PERIMETER OF THE
 POOL AND MUST BE SEPARATE FROM ANY FENCE, WALL, OR
 OTHER ENCLOSURE SURROUNDING THE YARD UNLESS THE FENCE,
 WALL, OR OTHER ENCLOSURE OR PORTION THEREOF IS SITUATED
 ON THE PERIMETER OF THE POOL, IS BEING USED AS PART OF
 THE BARRIER, AND MEETS THE BARRIER REQUIREMENTS OF THIS
 SECTION.
  
 R4501.17.1.13
 REMOVABLE CHILD BARRIERS MUST BE PLACED SUFFICIENTLY
 AWAY FROM THE WATER?S EDGE TO PREVENT A YOUNG CHILD OR
 MEDICALLY FRAIL ELDERLY PERSON WHO MAY MANAGE TO
 PENETRATE THE BARRIER FROM IMMEDIATELY FALLING INTO THE
 WATER. SUFFICIENTLY AWAY FROM THE WATER?S EDGE SHALL
 MEAN NO LESS THAN 20 INCHES (508 MM) FROM THE BARRIER
 TO THE WATER?S EDGE. DWELLING OR NONDWELLING WALLS
 INCLUDING SCREEN ENCLOSURES, WHEN USED AS PART OR ALL
 OF THE ?BARRIER? AND MEETING THE OTHER BARRIER
 REQUIREMENTS, MAY BE AS CLOSE TO THE WATER?S EDGE AS
 PERMITTED BY THIS CODE.
  
 R4501.17.1.14
 A WALL OF A DWELLING MAY SERVE AS PART OF THE BARRIER
 IF IT DOES NOT CONTAIN ANY DOOR OR WINDOW THAT OPENS TO
 PROVIDE DIRECT ACCESS FROM THE HOME TO THE SWIMMING
 POOL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-05 Cont ID  
Sent By cthroop Date 2017-05-05 Time 15:05 Rev Time 0.00
Received By cthroop Date 2017-04-27 Time 10:06 Sent To  
Notes
2017-04-28 10:06:59ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By njwira Date 2017-05-02 Time 17:15 Rev Time 0.00
Received By njwira Date 2017-04-28 Time 15:00 Sent To B
Notes
2017-05-02 17:15:505/2/17- FAILED
  
 WHERE IS THE BARRIER GOING?
 WHAT MATERIAL IS THE BARRIER?
 HOW TALL IS THE BARRIER
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING