Plan Review Details - Permit 17041264
Plan Review Stops For Permit 17041264
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By jwitmer Date 2017-05-17 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2017-05-17 Time 11:39 Sent To  
Notes
2017-05-17 12:12:26 
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 09:07 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-30 Cont ID  
Sent By jpearson Date 2017-05-30 Time 14:48 Rev Time 0.00
Received By jpearson Date 2017-05-30 Time 14:48 Sent To  
Notes
2017-05-30 14:55:381. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE OF
 WORK AND VALUE LISTED. FBC 105.1, FBC 109.3
 2. EMERGENCY AND EXIT LIGHTING SHALL BE FED FROM THE
 BRANCH CIRCUIT OF THE NORMAL LIGHTING IN THE AREA.
 PROVIDE CORRECTION SHOWING CIRCUITS FOR THESE ITEMS.
 NEC 700.12(F)
 3. CIRCUIT FOR NEW PROJECTOR AND SCREEN IS NOT
 INDICATED OR INCLUDED IN PANEL SCHEDULE. PROVIDE
 CORRECTION WITH CONDUCTOR AND BREAKER SIZING. NEC
 408.4, NEC 210.19

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-02 Cont ID  
Sent By scaldero Date 2017-05-02 Time 09:58 Rev Time 0.00
Received By scaldero Date 2017-05-02 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 09:07 Rev Time 0.00
Received By jpearson Date 2017-06-14 Time 16:36 Sent To  
Notes
2017-06-16 09:08:32PLACED IN "TO BE PROCESSED" BOX
2017-06-14 16:36:36RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-30 Cont ID  
Sent By jpearson Date 2017-05-30 Time 14:56 Rev Time 0.00
Received By jpearson Date 2017-05-30 Time 14:56 Sent To  
Notes
2017-04-28 14:58:53C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-17 Cont ID  
Sent By jwitmer Date 2017-05-17 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2017-05-17 Time 11:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-15 Cont ID  
Sent By ccole Date 2017-06-15 Time 09:55 Rev Time 0.00
Received By ccole Date 2017-06-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By ccole Date 2017-05-03 Time 09:02 Rev Time 0.00
Received By ccole Date 2017-05-03 Time 09:02 Sent To  
Notes
2017-05-03 09:09:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041264
 5/2/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES INVOLVED IN THE
 ALTERATION- SEE TABLE 403.3 FBC-14 MECHANICAL. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 2) SHOW COMPLIANCE WITH C403.2.7.5 FBC-14 ENERGY
 CONSERVATION CODE FOR AIR DISTRIBUTION, AND DUCT SYSTEM
 SIZING.
  
 3) SUBMIT A MECHANICAL SUB-PERMIT APPLICATION FOR
 ALTMAN BROTHERS, OR PROVIDE A SHOP DRAWING STAMP ON THE
 PLANS FROM THE ARCHITECT OF RECORD- PLEASE SEE SECTION
 105.3.1.2 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  