Plan Review Details - Permit 17041228
Plan Review Stops For Permit 17041228
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-05 Cont ID  
Sent By cthroop Date 2017-07-05 Time 07:49 Rev Time 0.00
Received By cthroop Date 2017-07-05 Time 07:42 Sent To  
Notes
2017-07-05 07:51:54BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. 2ND REQUEST - PROVIDE ENERGY SUBMITTAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By cthroop Date 2017-05-25 Time 10:30 Rev Time 0.00
Received By cthroop Date 2017-05-25 Time 07:49 Sent To  
Notes
2017-05-25 10:36:16BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENERGY SUBMITTAL.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENTS.
 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 5. PALM BEACH COUNTY IMPACT FEES REQUIRED.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 12:50 Rev Time 0.00
Received By jleahy Date 2017-05-18 Time 12:50 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-06-30 Cont ID  
Sent By fmittner Date 2017-06-30 Time 11:35 Rev Time 0.00
Received By fmittner Date 2017-06-30 Time 11:35 Sent To  
Notes
2017-06-30 11:35:44COA NOT COMPLETE. AWAITING RESPONSE FROM KELLY YATES
 ARCHITECT.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By fmittner Date 2017-05-05 Time 13:49 Rev Time 0.00
Received By fmittner Date 2017-05-05 Time 13:49 Sent To  
Notes
2017-05-05 13:51:42ADDITION REQUIRES SUBMITTAL OF CERTIFICATE OF
 APPROPRIATENESS (COA) SINCE PROPERTY IS LOCATED WITHIN
 THE VEDADO-HILLCREST HISTORIC DISTRICT. FHM LEFT
 MESSAGE WITH APPLICANT. QUESTIONS, PLEASE CONTACT
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT 822-1457 OR [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-05 Cont ID  
Sent By cthroop Date 2017-07-05 Time 07:49 Rev Time 0.00
Received By cthroop Date 2017-06-12 Time 13:37 Sent To  
Notes
2017-06-13 13:38:03R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-25 Cont ID  
Sent By cthroop Date 2017-05-25 Time 10:28 Rev Time 0.00
Received By cthroop Date 2017-04-27 Time 12:55 Sent To  
Notes
2017-04-28 12:56:05R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By cthroop Date 2017-05-25 Time 10:28 Rev Time 0.00
Received By cthroop Date 2017-05-25 Time 07:49 Sent To  
Notes
2017-05-25 10:29:49BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-14 Cont ID  
Sent By hmoser Date 2017-06-14 Time 14:54 Rev Time 0.00
Received By hmoser Date 2017-06-14 Time 14:54 Sent To  
Notes
2017-06-14 14:59:20PLAN DENIED
 PROVIDE DUCT SIZE ON ALL DUCT BOTH SYSTEMS.
 PER SECTION 107 FBC 2014
 NO PHONE NUMBER ON APPLICATION FOR CONTRACTOR.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By hmoser Date 2017-05-24 Time 13:14 Rev Time 0.00
Received By hmoser Date 2017-05-24 Time 12:53 Sent To  
Notes
2017-05-24 13:14:51PLAN DENIED
 THERE ARE NO DUCT SIZE ON MASTER BATH SIDE OF ADDITION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By gjohnson Date 2017-05-17 Time 13:48 Rev Time 0.00
Received By gjohnson Date 2017-05-17 Time 11:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-30 Cont ID  
Sent By fmittner Date 2017-06-30 Time 11:35 Rev Time 0.00
Received By fmittner Date 2017-06-30 Time 11:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By fmittner Date 2017-05-05 Time 13:51 Rev Time 0.00
Received By fmittner Date 2017-05-05 Time 13:51 Sent To B
Notes
2017-05-05 13:52:38NEEDS LOT COVERAGE AND FAR CALCULATIONS SUBMITTED ALONG
 WITH TWO CURRENT SURVEYS.