Plan Review Details - Permit 17041192
Plan Review Stops For Permit 17041192
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By pleduc Date 2017-05-15 Time   Rev Time 0.00
Received By pleduc Date 2017-05-15 Time 09:40 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 15:58 Sent To M
Notes
2017-04-28 16:00:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4
 BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A
 PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
 24.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-12 Time 15:59 Sent To  
Notes
2017-05-12 15:59:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 11:09 Rev Time 0.00
Received By ccole Date 2017-04-26 Time 13:04 Sent To  
Notes
2017-04-27 13:04:51ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-17 Cont ID  
Sent By ccole Date 2017-05-17 Time 12:15 Rev Time 0.00
Received By ccole Date 2017-05-17 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 11:09 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 11:09 Sent To  
Notes
2017-05-10 11:17:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041192
 5/10/17
  
 RESULTS: DENIED.
  
 1) THE NOTES, LEGENDS, AND DETAILS ON THE PLANS HAVE
 PRINT THAT IS TOO FAINT AND NOT LEGIBLE. PLEASE PROVIDE
 CLEAR, LEGIBLE PLANS- SECTION 107.1 WPB AMENDMENTS TO
 THE FBC.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  