Plan Review Details - Permit 17041175
Plan Review Stops For Permit 17041175
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-25 Cont ID  
Sent By jwitmer Date 2017-05-25 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2017-05-25 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By jwitmer Date 2017-05-03 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-05-03 Time 16:47 Sent To  
Notes
2017-05-03 17:24:54BUILDING PLAN REVIEW
 W. P. B. REVISION: 17041175
 W. P. B. PERMIT: 16060610
 ADD: 1045 CHARLOTTE AVE.
 CONT: REPUBLIC CONSTRUCTION CORP.
 TEL: 561-801-0697
 E-MAIL: ??????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 03/2017
 ACTION: DENIED
  
 1) SHEET A-02 THE MENS SHOWERS ARE SHOWN TO BE 2 FOOT
 10 INCHES DEEP. THE ACCESSIBLE TRANSFER TYPE SHOWER THE
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES. SEE
 608.2.1.
  
 2) SHEET A-02 WITH THE NEW LAYOUT IN THE MENS LOCKER
 ROOM THERE ARE 2 BENCHES SHOWN. PLEASE PROVIDE
 COMPLIANCE WITH AT LEAST ONE BENCH FOR 2014 ACCESS.
 CODE 903.3 SIZE, 903.4, BACK SUPPORT, 903.6 HEIGHT,
 903.6 STRUCTURAL STRENGTH & 903.7 WET LOCATIONS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 17:22 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By vperez Date 2017-05-04 Time 11:25 Rev Time 0.00
Received By vperez Date 2017-05-04 Time 11:25 Sent To  
Notes
2017-05-04 11:25:52PLEASE ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL
 APPROVAL. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By pleduc Date 2017-05-24 Time   Rev Time 0.00
Received By pleduc Date 2017-05-24 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By pleduc Date 2017-05-04 Time   Rev Time 0.00
Received By pleduc Date 2017-05-04 Time 13:31 Sent To  
Notes
2017-05-04 14:31:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET E 1 - THERE DOES NOT APPEARS TO BE A EXIT SIGN
 IN THE WOMENS RESTROOM.
  
 PLEASE REVIEW AND/OR CORRECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-19 Time 13:33 Sent To  
Notes
2017-05-22 13:33:32B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-05 Time 08:03 Rev Time 0.00
Received By shill Date 2017-04-26 Time 16:47 Sent To  
Notes
2017-05-11 08:03:26CLOSED STOP (CUSTOMER IS AWARE AS THEY CHECKED OUT ONE
 SET OF PLANS ON 5/5)
2017-04-27 14:59:23B20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-25 Cont ID  
Sent By ccole Date 2017-05-25 Time 09:54 Rev Time 0.00
Received By ccole Date 2017-05-25 Time 09:01 Sent To  
Notes
2017-05-25 09:56:05MECHANICAL PROVISOS:
 5/25/17
  
 1) ENGINEER'S LETTERS FROM BACH DESIGN ENGINEERS AND
 TRANE REQUIRED FOR INSTALLATION OF OAU-1 ON THE INSIDE
 OF THE BUILDING.
 2) SUBMIT FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOAS FOR THE ROOFTOP FANS AND SIDEWALL LOUVERS WITH
 SHOP DRAWING APPROVAL SIGNATURES BY THE EOR.
  
 CCOLE
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By ccole Date 2017-05-02 Time 08:54 Rev Time 0.00
Received By ccole Date 2017-05-02 Time 07:48 Sent To  
Notes
2017-05-02 08:57:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041175
 5/2/17
  
 1) THE EXHAUST SYSTEM REQUIRES INSTALLATION OF AN
 ENERGY RECOVERY VENTILATOR- SEE SECTION & TABLE
 C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE REVISE THE
 PLAN ACCORDINGLY.
  
 2) PLEASE PROVIDE EXHAUST VENTILATION CALULATIONS FOR
 THE BAQTHROOMS AND LOCKER ROOMS- TABLE 403.3 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 16:41 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By gjohnson Date 2017-05-02 Time 15:15 Rev Time 0.00
Received By gjohnson Date 2017-05-02 Time 11:42 Sent To  
Notes
2017-05-02 15:28:101ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT A-02 SHOWS DEPTH OF ACCESSIBLE SHOWER AT 2'10"
 IT SHALL BE 3'. PER FBC ACC 608.2.1
  
 2. SHT A-04 SHOWER CONTROLS SHALL COMPLY WITH FBC ACC
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING. PLEASE REMOVE DETAIL
 SHOWING 27" MAX FROM CENTER OF CONTROLS TO FRONT OF
 SHOWER. IT SHALL BE 15"
  
 3. SHT. P-2 THE SANITARY RISER THE BRANCH DRAIN FOR THE
 LAVATORY SHALL CONNECT BETWEEN THE LAST TO WATER
 CLOSETS NOT THE END OF THE BRANCH. PER FBC PL 914.2
 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  