| 2017-05-04 15:43:22 | PERMIT #17041097 |
| | |
| | THIS OFFICE HAS REVIEWED THE INFORMATIO PROVIDED BY THE |
| | APPLICANT, VIA EMAIL, AS WELL AS THE INTENDED LOCATION |
| | (THE PARKING AREA BETWEEN THE TWO WAREHOUSES LISTED AS |
| | 432 25TH STREET) . AT THIS TIME, OUR POSITION REMAINS |
| | UNCHANGED REGARDING THE DENIAL OF THE EVENT APPLICATION |
| | FOR NON-COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA |
| | FIRE PREVENTION CODE FOR ASSEMBLY OCCUPANCIES, AS |
| | LISTED BELOW. |
| | |
| | PER NFPA 101, CHAPTER 12 - NEW ASSEMBLY OCCUPANCIES |
| | 12.2.4.4 ?? A FENCED OUTDOOR ASSEMBLY OCCUPANCY SHALL |
| | HAVE NOT LESS THAN TWO REMOTE MEANS OF EGRESS FROM THE |
| | ENCLOSURE IN ACCORDANCE WITH 7.5.1.3. |
| | 12.2.8 MEANS OF EGRESS, OTHER THAN FOR PRIVATE PARTY |
| | TENTS NOT EXCEEDING 1200 FT2, SHALL BE ILLUMINATED IN |
| | ACCORDANCE WITH SECTION 7.8. |
| | 12.2.9.1 ?? EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.9. |
| | |
| | PER NFPA 101, CHAPTER 7 - MEANS OF EGRESS |
| | 7.5.1.3.1 ?? WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| | THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| | SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| | OTHER EMERGENCY CONDITION. |
| | 7.5.1.3.2* ?? WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| | DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| | LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| | LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| | ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED |
| | IN 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| | |
| | ADDITIONALLY, THE FOLLOWING QUESTIONS AND/OR DETAILS |
| | HAVE NOT BEEN ADDRESSED BY NEITHER THE SUBMITTED HAND |
| | DRAWING NOR THE EMAIL BELOW. |
| | |
| | 1) HOW WILL THE OCCUPANT LOAD OF 250 PERSONS (AS |
| | PROVIDED IN THE APPLICATION BY THE APPLICANT) BE |
| | ENFORCED? |
| | |
| | 2) ASSEMBLY OCCUPANCIES ARE REQUIRED TO HAVE ONE |
| | PROPERLY TRAINED (1) CROWD MANAGER FOR EVERY 250 |
| | PERSONS. |
| | |
| | 3) THE INFORMATION BELOW, AS WELL AS THE DRAWING |
| | SUBMITTED WITH THE INITIAL APPLICATION INDICATES THAT |
| | THIS PROPERTY HAS 2 DOORS AND/OR GATES AT THE FRONT OF |
| | THE PROPERTY. A REVIEW OF THE PROPERTY SHOWS 1 MANUAL |
| | GATE DOOR, APPROXIMATELY, 10-15 FEET IN WIDTH. THE |
| | DETAILS PROVIDED ARE INACCURATE. |
| | |
| | 4) WILL THERE BE ANY ACCESS TO THE INTERIOR OF THE |
| | NEIGHBORING WAREHOUSE SPACES BY STAFF OR THE GENERAL |
| | PUBLIC? HOW WILL THIS BE MONITORED? |
| | |
| | 5) HOW IS THE ELECTRICAL SERVICE TO THE MUSIC STAGE AND |
| | THE FOOD TENT BEING SUPPLIED? |
| | |
| | 6) THE FOOD TENT IS LABELED AS "FINGER FOODS". |
| | ADDITIONAL DETAILS REQUIRED? WILL THERE BE ANY COOKING |
| | AND/OR WARMING OF FOODS? IF SO, HOW WILL THIS BE |
| | ACCOMPLISHED? |
| | |
| | 7) EMERGENCY NOTIFICATION IS REQUIRED, EVEN FOR OUTDOOR |
| | EVENTS. HOW WILL THIS BE ACCOMPLISHED IN A MANNER THAT |
| | IS IMMEDIATE, EFFICIENT, AND EFFECTIVE FOR THIS TYPE OF |
| | EVENT? |
| | |
| | 8) DETAILS REGARDING QUANTITY AND LOCATION OF FIRE |
| | EXTINGUISHERS HAS NOT BEEN PROVIDED. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASST. FIRE MARSHAL |
| | WPBFR |
| | [email protected] |
| | 561-804-4751 |