Plan Review Details - Permit 17041082
Plan Review Stops For Permit 17041082
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 07:14 Sent To I
Notes
2018-01-08 08:00:46APPROVED WITH EXCEPTIONS
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR ROOF
 COVERING MATERIALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By rmcdouga Date 2017-07-17 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2017-07-17 Time 18:05 Sent To M
Notes
2017-07-17 19:00:28APPROVED WITH EXCEPTIONS
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR ROOF
 COVERING MATERIALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-16 Cont ID  
Sent By rmcdouga Date 2017-05-16 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2017-05-16 Time 15:48 Sent To  
Notes
2017-05-16 16:04:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLORIDA LICENSED ENGINEER THAT SIGNED AND DATED
 THE PLANS DID NOT AFFIX HIS SEAL TO THE PLANS AS
 REQUIRED BY FAC 61G15-23.002.
  
 2) THERE ARE NO NOTES THAT CORRESPOND TO THE ITEMS THAT
 ARE TAGGED WITH EN-# ON THE DRAWINGS. PROVIDE TWO SETS
 OF A SCHEDULE TO INDICATE WHAT EACH OF THESE TAGS MEAN.
 FBC 107.2.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-20 Cont ID  
Sent By jleahy Date 2017-06-20 Time 07:16 Rev Time 0.00
Received By jleahy Date 2017-06-20 Time 07:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 14:56 Rev Time 0.00
Received By jleahy Date 2017-05-17 Time 14:56 Sent To  
Notes
2017-05-17 14:57:16JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NO ELECTRICAL WORK SHOWN ON PLANS PLEASE SUBMIT A FLOOR
 PLAN SHOWING ELECTRICAL WORK TO BE DONE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2017-12-20 Time 14:37 Sent To  
Notes
2017-12-21 14:37:39R18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-18 Time   Rev Time 0.00
Received By cpuell Date 2017-06-05 Time 14:48 Sent To  
Notes
2017-06-05 14:48:28R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-17 Time 14:57 Rev Time 0.00
Received By jleahy Date 2017-04-25 Time 14:45 Sent To  
Notes
2017-04-26 14:45:12R06

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-02 Cont ID  
Sent By ccole Date 2018-01-02 Time 10:45 Rev Time 0.00
Received By ccole Date 2018-01-02 Time 10:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-18 Cont ID  
Sent By ccole Date 2017-07-18 Time 12:31 Rev Time 0.00
Received By ccole Date 2017-07-18 Time 12:31 Sent To  
Notes
2017-07-18 12:45:022ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17041082
 7/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) PROVIDE AN AHRI CERTIFICATE FOR THE NEW SYSTEM-
 SECTION R101.4.7.
  
 3) AS PREVIOUSLY REQUESTED PROVIDE COMBUSTION AIR
 CALCULATIONS AND A VENTING PLAN FOR THE GAS DRYER.
  
 4) EXHAUST VENTILATION IS REQUIRED FOR THE KITCHEN PER
 TABLE M1507.4 FBC-14 RESIDENTIAL. PLEASE INDICATE IF A
 NEW EXHAUST HOOD AND DUCT WILL BE INSTALLED AND PROVIDE
 DETAILS ON THE PLANS.
  
 5) PROVIDE A MEANS OF RETURN AIR FROM BEDROOM #2 TO THE
 AIR HANDLER- SECTION M1602.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 17:13 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 17:13 Sent To  
Notes
2017-05-10 17:22:591ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17041082
 5/10/17
  
 1) NO MECHANICAL PLANS OR SPECIFICATIONS HAVE BEEN
 SUBMITTED. IN ORDER TO DO A COMPREHENSIVE REVIEW PLEASE
 PROVIDE THE FOLLOWING:
  
 A) AC DUCT LAYOUT PLAN
 B) AC EQUIPMENT SCHEDULE
 C) KITCHEN AND BATH EXHAUST PLANS
 D) COMBUSTION AIR CALCULATIONS, AND VENTING DETAILS FOR
 THE GAS DRYER
 E) ENGINEERING FOR TIE DOWN OF THE AC CONDENSER.
 F) CONDENSATE DISPOSAL DETAILS FOR THE AHU.
 G) MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER,
 THE RANGE, AND THE RANGE HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-19 Cont ID  
Sent By gjohnson Date 2017-06-19 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2017-06-19 Time 16:19 Sent To  
Notes
2017-06-19 17:07:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. S-1 EX NOTES EN-6 STATES EXISTING WATER HEATER TO
 REMAIN,DN-16 STATES REMOVE EXISTING WATER HEATER, SHT.
 S-2 PN-20 STATES NEW GAS WATER HEATER PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 15:55 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 15:55 Sent To  
Notes
2017-05-11 15:57:211ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. FIXTURES ONLY NO PIPING UNDER THIS PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  