Plan Review Details - Permit 17041024
Plan Review Stops For Permit 17041024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By cthroop Date 2017-06-13 Time 09:28 Rev Time 0.00
Received By cthroop Date 2017-06-12 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By cthroop Date 2017-05-12 Time 12:39 Rev Time 0.00
Received By cthroop Date 2017-05-12 Time 07:27 Sent To E
Notes
2017-05-12 12:42:54BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENTS.
 3. SELECT WHICH DOORS AND WINDOWS WILL BE INSTALLED
 FROM PRODUCT APPROVALS SUBMITTED.
 4. PROVIDE LANDING AT NEW DOOR OPENING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By jpearson Date 2017-06-06 Time 08:00 Rev Time 0.00
Received By jpearson Date 2017-06-06 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By jleahy Date 2017-05-12 Time 13:17 Rev Time 0.00
Received By jleahy Date 2017-05-12 Time 13:17 Sent To  
Notes
2017-05-12 13:23:52JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CABANA WILL NEED A SEPARATE MEANS OF DISCONNECT AND A
 GROUNDING SYSTEM AT THE CABANA BUILDING.
 SUBMIT A RISER DIAGRAM AND PANEL SCHEDULE FOR THE
 CIRCUITS IN THE CABANA.
 SEE 225.30, 225.39, 250.32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-13 Cont ID  
Sent By cthroop Date 2017-06-13 Time 09:28 Rev Time 0.00
Received By cthroop Date 2017-05-19 Time 10:19 Sent To  
Notes
2017-05-22 10:19:11R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-12 Cont ID  
Sent By jleahy Date 2017-05-12 Time 13:24 Rev Time 0.00
Received By jleahy Date 2017-04-24 Time 13:36 Sent To  
Notes
2017-04-25 13:37:00R01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-06-05 Cont ID  
Sent By ccole Date 2017-06-05 Time 14:33 Rev Time 0.00
Received By ccole Date 2017-06-05 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 16:38 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 16:35 Sent To  
Notes
2017-05-10 17:00:281ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17041024
 5/10/17
  
 1) CLARIFY HOW THE BATHROOM WILL BE VENTILATED-
 NATURALLY OR MECHANICALLY- SEE SECTION R303.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By gjohnson Date 2017-06-05 Time 15:46 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 13:52 Sent To  
Notes
2017-05-11 14:31:381ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE KITCHEN SINK SHALL CONNECT TO BUILDING DRAIN
 DOWN STREAM OF BATHROOM GROUP ONLY FIXTURES IN BATHROOM
 GROUP CAN CONNECT TOGETHER. PER FBC RES P3108.1
 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO
 BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL
 BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL
 EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE
 DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN
 SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH
 BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH
 WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO
 THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 2. YOU SHALL HAVE MIN OF ONE VENT TO OUTDOORS. FBC RES
 P3102.1 REQUIRED VENT EXTENSION.
 THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE
 AT LEAST ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS.
  
 3. THE STUDOR VENTS ARE SHOWN ON THE RISER BELOW THE
 FIXTURE BRANCH THEY SHALL BE 4" ABOVE .PER FBC RES
 P3114.4 LOCATION.
 INDIVIDUAL AND BRANCH AIR ADMITTANCE VALVES SHALL BE
 LOCATED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE
 HORIZONTAL BRANCH DRAIN OR FIXTURE DRAIN BEING VENTED.
  
 4. PLEASE SHOW LOCATION OF WATER HEATER. PER WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-06-12 Cont ID  
Sent By njwira Date 2017-06-12 Time 16:38 Rev Time 0.00
Received By njwira Date 2017-06-12 Time 16:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By njwira Date 2017-05-24 Time 13:59 Rev Time 0.00
Received By njwira Date 2017-05-24 Time 11:00 Sent To  
Notes
2017-05-24 14:00:265/24/17- FAILED
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED
 EXISTING STRUCTURE NO CHANGES PASS
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By njwira Date 2017-05-08 Time 16:13 Rev Time 0.00
Received By njwira Date 2017-05-08 Time 16:13 Sent To  
Notes
2017-05-08 16:13:555/8/17- FAILED
  
 REQUIRES TWO(2)SURVEYS SHOWING SETBACKS
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING