Plan Review Details - Permit 17040945
Plan Review Stops For Permit 17040945
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By rmcdouga Date 2017-07-27 Time 18:58 Rev Time 0.00
Received By rmcdouga Date 2017-07-27 Time 18:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By rmcdouga Date 2017-04-27 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2017-04-27 Time 09:28 Sent To  
Notes
2017-04-27 09:28:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE WIND DESIGN DATA AND SPECIFY HOW THE
 GENERATOR WILL BE ANCHORED TO THE 8" SLAB TO RESIST
 LATERAL FORCES. SPECIFY THE ANCHOR TYPE, SIZE AND
 LOCATIONS. FBC 1603.1.4 & 1609.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By jleahy Date 2017-07-27 Time 17:02 Rev Time 0.00
Received By jleahy Date 2017-07-27 Time 17:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By jleahy Date 2017-05-04 Time 07:40 Rev Time 0.00
Received By jleahy Date 2017-05-04 Time 07:40 Sent To FIRE
Notes
2017-05-04 07:43:58JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED LOAD CALCULATION, RISER DIAGRAM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-26 Cont ID  
Sent By pleduc Date 2017-07-26 Time   Rev Time 0.00
Received By pleduc Date 2017-07-25 Time 16:53 Sent To E
Notes
2017-07-26 08:47:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) INSTALL, INSPECT AND TEST PER NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS 2010 EDITION
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By pleduc Date 2017-05-04 Time   Rev Time 0.00
Received By pleduc Date 2017-05-04 Time 13:33 Sent To PC
Notes
2017-05-04 15:08:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE A SCOPE OF WORK. DOES THIS GENERATOR
 SUPPLY BACKUP POWER TO ANY LIFE SAFETY EQUIPMENT, I.E.
 FIRE ALARM, EMERGENCY LIGHTING?
  
 PROVIDE DETAILS AND COMPLAINCE WITH NFPA 110.
  
  
  
 2) THIS APPEARS TO BE FUELED BY NATURAL GAS. THERE IS
 NO INDICATION OF ANY RELATED WORK.
  
 PLEASE CLARUTY AND OR PROVIDE ALL APPLICABLE DRAWINGS,
 SPECS AND NFPA CODE COMPLIANCE.
  
  
  
 3) PLEASE PROVIDE THE ACTUAL DEMNSIONS TO THE NEAREST
 BUILDING AND OPENINGS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-27 Cont ID  
Sent By rmcdouga Date 2017-07-27 Time 18:58 Rev Time 0.00
Received By rmcdouga Date 2017-07-24 Time 11:29 Sent To  
Notes
2017-07-25 11:29:38RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-04 Cont ID  
Sent By pleduc Date 2017-05-04 Time   Rev Time 0.00
Received By pleduc Date 2017-04-21 Time 12:59 Sent To  
Notes
2017-04-24 12:59:47ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-04-26 Cont ID  
Sent By njwira Date 2017-04-26 Time 16:19 Rev Time 0.00
Received By njwira Date 2017-04-25 Time 15:49 Sent To  
Notes
***NONE***