| Plan Review Stops For Permit 17040945 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-07-27 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-07-27 |
Time |
18:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-04-27 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-04-27 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2017-04-27 09:28:48 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE WIND DESIGN DATA AND SPECIFY HOW THE | | | GENERATOR WILL BE ANCHORED TO THE 8" SLAB TO RESIST | | | LATERAL FORCES. SPECIFY THE ANCHOR TYPE, SIZE AND | | | LOCATIONS. FBC 1603.1.4 & 1609.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-07-27 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-07-27 |
Time |
17:02 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-04 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-04 |
Time |
07:40 |
Sent To |
FIRE |
|
| Notes |
| 2017-05-04 07:43:58 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED LOAD CALCULATION, RISER DIAGRAM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-07-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-07-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-07-25 |
Time |
16:53 |
Sent To |
E |
|
| Notes |
| 2017-07-26 08:47:56 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) INSTALL, INSPECT AND TEST PER NFPA 110, STANDARD FOR | | | EMERGENCY AND STANDBY POWER SYSTEMS 2010 EDITION | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-05-04 |
Time |
13:33 |
Sent To |
PC |
|
| Notes |
| 2017-05-04 15:08:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) PLEASE PROVIDE A SCOPE OF WORK. DOES THIS GENERATOR | | | SUPPLY BACKUP POWER TO ANY LIFE SAFETY EQUIPMENT, I.E. | | | FIRE ALARM, EMERGENCY LIGHTING? | | | | | | PROVIDE DETAILS AND COMPLAINCE WITH NFPA 110. | | | | | | | | | | | | 2) THIS APPEARS TO BE FUELED BY NATURAL GAS. THERE IS | | | NO INDICATION OF ANY RELATED WORK. | | | | | | PLEASE CLARUTY AND OR PROVIDE ALL APPLICABLE DRAWINGS, | | | SPECS AND NFPA CODE COMPLIANCE. | | | | | | | | | | | | 3) PLEASE PROVIDE THE ACTUAL DEMNSIONS TO THE NEAREST | | | BUILDING AND OPENINGS. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-07-27 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-07-24 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2017-07-25 11:29:38 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-04-21 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2017-04-24 12:59:47 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-04-26 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-04-26 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-04-25 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|