Plan Review Details - Permit 17040923
| Plan Review Stops For Permit 17040923 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-05-03 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-05-03 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-05-03 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2017-05-03 10:10:55 | PLEASE ADDRESS MECH. COMMENTS AND PROVIDE A REVISED | | | LOAD CALCULATION OF THE ELECTRICAL SERVICE AS THIS IS A | | | SIGNIFICANT LOAD BEING ADDED TO EXISTING SERVICE. ALSO | | | A RECEPTACLE FOR SERVICE MUST BE INSTALLED AT THE | | | CONDENSOR LOCATION IF ONE IS NOT EXISTING. FBC 107.3.5 | | | | | | V. PEREZ | | | *6717 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-05-03 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-05-03 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-05-03 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2017-04-21 10:34:12 | ROUTED TO MECHANICAL INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-05-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-05-01 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-05-01 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2017-05-01 09:54:53 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17040923 | | | 5/1/17 | | | | | | 1) THE PALM BEACH COUNTY PROPERTY APPRAISER'S REPORT | | | INDICATES THE EXISTING RESIDENCE IS NON-CONDITIONED, | | | THEREFORE THE INSTALLATION OF A NEW CENTRAL AC SYSTEM | | | REQUIRES THE RESIDENCE TO BE IN COMPLIANCE WITH THE | | | FLORIDA ENERGY CONSERVATION CODE 2014. PLEASE SEE | | | SECTION R101.4.5 AND SUBMIT ENERGY CALCULATIONS. | | | COMPLIANCE SUBMITTAL INFORMATION CAN BE FOUND UNDER | | | SECTION R101.5. | | | | | | 2) SUBMIT A CUT SHEET FROM DAIKIN THAT INDICATES THE | | | SENSIBLE, LATENT, AND COOLING CAPACITIES OF THE NEW | | | 4-TON SYSTEM IN AN EFFORT TO VERIFY THE HANDWRITTEN | | | DATA LISTED ON THE AC CALCULATION SHEET. | | | | | | 3) THE 8X8 RETURN TRANSFERS IN THE BEDROOM DOORS ARE | | | UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL- 50 | | | SQ. INCHES PER 100 CFMS REQUIRED. | | | | | | 4) THE 24X24 MAIN AC RETURN GRILL IS UNDERSIZED- | | | TYPICAL RULE OF THUMB IS 200 SQ. INCHES PER TON. A | | | 4-TON SYSTEM WITH NO OUTSIDE AIR REQUIRES 800 SQ. | | | INCHES. | | | | | | 5) PROVIDE DETAILS FOR ANCHORING THE CONDENSER TO THE | | | NEW EXTERIOR MOUNTING PAD- SECTION M1401.4 FBC-14 | | | RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|