Plan Review Details - Permit 17040913
Plan Review Stops For Permit 17040913
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-01 Cont ID  
Sent By jwitmer Date 2017-06-01 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2017-06-01 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By jwitmer Date 2017-05-04 Time 08:06 Rev Time 0.00
Received By jwitmer Date 2017-05-04 Time 07:27 Sent To  
Notes
2017-05-04 08:05:572014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040913
 ADD: 8993 OKEECHOBEE BLVD. SUITE # ???????
 CONT: LARREA AGUIRRE CONST. LLC
 TEL: 954-993-7301
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 4/ 2017
 ACTION: DENIED
  
 ***HOLD PERMIT NOT TO BE ISSUED*** NEEDS OWNER
 SIGNATURE ON APPLICATION!!!!
  
 1A) THE PERMIT APPLICATION AND PLANS, THE TITLEBLOCK
 DOES NOT GIVE THE SUITE NUMBER OF THE TENANT SPACE
 WHERE WORK IS TO COMMENCE UNDER THIS PERMIT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 1B) THE PERMIT APPLICATION VALUE IS LOW PROVIDE
 CONTRACT VALUE FOR THE TOTAL PROJECT. 108.3* BUILDING
 PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A1 DOOR 03 IS MISSING THE REQUIRED 18 INCHES
 ON THE LATCH SIDE OF THE DOOR.
 2014 FBC-ACCESS. 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 3) DISCREPANCY IN PLANS, SHEET A1 VERSES SHEET A3
 OCCUPANT LOADS. PLEASE REVIEW THE TABLES FOR OCCUPANCY,
 BUILDING CODE TABLE 1004.1.2 VERSES NFPA 101 TABLE
 7.3.1.2. THE SQ. FEET PER OCCUPANT ARE THE SAME BUT THE
 SQUARE FEET PER AREA ARE DIFFERENT. EXAMPLE PHYSICAL
 THERAPY EXERCISE AREA 848 SQ. FT. VERSES 939. THE TOTAL
 OCCUPANT LOAD 50 VERSES 44. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN PLANS.
  
 4) THE LIFE SAFETY PLAN DOES NOT IDENTIFY THE MINIMUM
 BUILDING TYPE?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (3.) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-05 Time 07:20 Rev Time 0.00
Received By jpearson Date 2017-07-05 Time 07:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-06-20 Cont ID  
Sent By jpearson Date 2017-06-20 Time 09:16 Rev Time 0.00
Received By jpearson Date 2017-06-20 Time 09:16 Sent To  
Notes
2017-06-20 09:21:54CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (3RD REVIEW):
  
 PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY:
  
 1. NO LIGHTING CONTROL SPECIFIED FOR WAITING ROOM AND
 RECEPTION AREA. C405.2 (PREVIOUS COMMENT #3)
 2. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2 (PREVIOUS COMMENT #4)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By jpearson Date 2017-06-05 Time 10:35 Rev Time 0.00
Received By jpearson Date 2017-06-05 Time 10:35 Sent To  
Notes
2017-06-05 10:50:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. INDICATE ON PLAN WHICH AREAS WILL BE WIRED PER THE
 REQUIREMENTS FOR HEALTH CARE FACILITIES. NEC 517.13
 2. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE WIRED
 TO THE NORMAL LIGHTING BRANCH CIRCUIT IN THE SAME AREA.
 PROVIDE CORRECTION. NEC 700.12(F)
 3. SHEET E-1, THERE IS A NOTE THAT STATES THE LIGHTING
 WILL BE PROVIDED WITH OCCUPANCY SENSORS, HOWEVER, THE
 PLAN SHOWS NORMAL SWITCHING. CLARIFY AND/OR CORRECT.
 FBC 107.2.1, FBC C405.2
 4. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 8.4.2.
 5. NOTE 14, SHEET E-1, STATES THAT ALL RECEPTACLES
 SHALL BE TAMPER-RESISTANT PER NEC 406.11. SECTION
 406.11 IS THE CODE REQUIREMENT FOR RECEPTACLE
 GROUNDING. ARE YOU REFERRING TO NEC 406.14 IN REFERENCE
 TO CHILD CARE FACILITIES? PLEASE CLARIFY AND/OR
 CORRECT. FBC 107.2.1, NEC 406.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-28 Cont ID  
Sent By jleahy Date 2017-04-28 Time 08:31 Rev Time 0.00
Received By jleahy Date 2017-04-27 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By scaldero Date 2017-06-05 Time 12:06 Rev Time 0.00
Received By scaldero Date 2017-06-05 Time 12:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-27 Cont ID  
Sent By scaldero Date 2017-04-27 Time 11:06 Rev Time 0.00
Received By scaldero Date 2017-04-27 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-05 Time 07:22 Rev Time 0.00
Received By jpearson Date 2017-06-29 Time 13:11 Sent To  
Notes
2017-06-30 13:12:08RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2017-06-20 Cont ID  
Sent By jpearson Date 2017-06-20 Time 09:27 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 12:56 Sent To  
Notes
2017-06-20 09:29:20PLACED IN LARGE DENIED BIN L, EMAILED CONTRACTOR.
2017-06-19 12:56:28RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-19 Cont ID  
Sent By lmarchan Date 2017-06-19 Time 12:55 Rev Time 0.00
Received By lmarchan Date 2017-05-25 Time 11:41 Sent To  
Notes
2017-05-26 11:41:20B34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-04 Cont ID  
Sent By jwitmer Date 2017-05-04 Time 08:06 Rev Time 0.00
Received By jwitmer Date 2017-04-20 Time 11:52 Sent To  
Notes
2017-04-21 11:52:40B34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-04 Cont ID  
Sent By jwitmer Date 2017-05-04 Time 08:06 Rev Time 0.00
Received By jwitmer Date 2017-05-04 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By ccole Date 2017-05-31 Time 17:38 Rev Time 0.00
Received By ccole Date 2017-05-31 Time 17:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-04-26 Cont ID  
Sent By ccole Date 2017-04-26 Time 09:32 Rev Time 0.00
Received By ccole Date 2017-04-26 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-05-02 Cont ID  
Sent By gjohnson Date 2017-05-02 Time 12:26 Rev Time 0.00
Received By gjohnson Date 2017-05-02 Time 10:02 Sent To  
Notes
***NONE***