Plan Review Details - Permit 17040820
Plan Review Stops For Permit 17040820
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-07-26 Cont ID  
Sent By shill Date 2017-07-24 Time 09:39 Rev Time 0.00
Received By shill Date 2017-07-24 Time 09:39 Sent To  
Notes
2017-07-26 11:32:587/26 - VALUE TOO LOW. REQUESTED CONTRACT FROM APPLICANT
 VIA EMAIL ON 7/24. AS I HAVE NOT RECEIVED A RESPONSE, I
 PUT THIS IN FAILED STATUS PENDING RECEIPT OF CONTRACT
 VIA EMAIL.
  
 [email protected]
 561-805-6724
  
2017-07-24 09:41:47****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. LS1 DOES NOT MATCH A2, REVISE.
  
 2. PARKING LOT PERMIT 17070006 IS REQUIRED TO BE ISSUED
 AND COMPLETED PRIOR TO FINAL INSPECTION. THE PARKING
 LOT WAS RESTRIPED WITHOUT A PERMIT AND DOES NOT COMPLY
 WITH FBC OR ADA. A CODE COMPLIANT ACCESSIBLE ROUTE IS
 REQUIRED PRIOR TO FINAL INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-10 Cont ID  
Sent By shill Date 2017-07-10 Time 16:32 Rev Time 0.00
Received By shill Date 2017-07-10 Time 16:32 Sent To  
Notes
2017-07-10 16:40:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR FLORIDA INTERNATIONAL
 ENGINEERING & TESTING LAB. REVISE TO INCLUDE, FS471,
 FAC61G15-23.002.
  
 2ND REVIEW, THIS WAS NOT PROPERLY ADDRESSED.
  
 THE TITLE BLOCK SHOULD INCLUDE THE ENGINEER'S NAME. THE
 TITLE BLOCK HAS "V.M.B. VENKATESAN" AS THE NAME, BUT
 DBPR RECORDS SHOW VENKATESAN AS THE FIRST NAME. IF THIS
 IS THE ENGINEER'S LAST NAME, CONTACT FBPE TO CORRECT.
 IF THIS IS THE ENGINEER'S FIRST NAME, REVISE TITLE
 BLOCK TO INCLUDE NAME AS LICENSED.
  
 THE TITLE BLOCK SHOULD INCLUDE THE BUSINESS LICENSE
 NUMBER. DBPR RECORDS INDICATE THAT THIS IS CA#27273.
  
 REVISE THE TITLE BLOCK FOR SHEETS WHICH ARE REVISED.
 FOR ALL OTHERS (WHICH HAVE BEEN REVIEWED, PASSED AND
 STAMPED), A STICKER OR HAND WRITTEN INFO IS RECOMMENDED
 TO AVOID ADDITIONAL REVIEWS.
  
 3RD REVIEW, TITLE BLOCK DOES NOT COMPLY. PLEASE FIX ALL
 SHEETS. THIS MAY BE DONE BY ADDING A STICKER TO EACH
 SHEET. THE APPLICABLE FLORIDA ADMINISTRATIVE CODE
 SECTION CAN BE SEEN AT WWW.FBPE.ORG.
  
 3-4. OK
  
 5. THE PARKING LOT DOES NOT COMPLY WITH THE FLORIDA
 BUILDING CODE OR ADA. THE ACCESSIBLE PARKING SPACE IS
 NOT LOCATED ON THE CLOSEST ROUTE. SUBMIT A PERMIT
 APPLICATION TO BRING THE PARKING LOT INTO COMPLIANCE.
 IT APPEARS THAT THE PARKING LOT WAS RESTRIPED SOME TIME
 BETWEEN 2009 AND 2011 WITHOUT A PERMIT.
  
 2ND REVIEW, A PAGE WAS ADDED TO THE PLAN. THIS IS TO BE
 ADDRESSED WITH A SEPARATE APPLICATION. PLEASE SUBMIT
 THAT PAGE WITH A PERMIT APPLICATION FOR REVIEW. PARKING
 LOT PERMIT APPLICATION IS TO BE SUBMITTED PRIOR TO
 ISSUANCE OF THIS RENOVATION PERMIT (NOW). FAILURE TO
 APPLY IMMEDIATELY WILL RESULT IN A VIOLATION ISSUED FOR
 THE WORK ALREADY DONE WITHOUT PERMIT. (A 4X FEE HOLD
 HAS BEEN ADDED BUT NO WRITTEN VIOLATION ISSUED AT THIS
 TIME.)
  
 3RD REVIEW, THE PARKING LOT PAGE IS STILL IN THIS
 PACKAGE. THE PERMIT APPLICATION SUBMITTED STATES THAT
 THE PLAN IS WITH THIS PERMIT. PLEASE SEE 2ND REVIEW -
 "SUBMIT THAT PAGE WITH A PERMIT APPLICATION FOR
 REVIEW."
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO: PRIOR TO FINAL
 INSPECTION, PARKING LOT PERMIT IS TO BE ISSUED AND
 COMPLETED (COMPLIANCE WITH ACCESSIBLE ROUTE REQUIREMENT
 FOR ALTERATIONS, FBC ACCESSIBILITY).
  
 6-7. OK
  
 8. REVISE PLAN TO PROVIDE INFORMATION ABOUT THE
 STOCKROOM AND THE STORAGE AREAS; WHAT WILL BE STORED IN
 THESE SPACES? FBC 107.
  
 9-10. OK
  
 11. THE UNNUMBERED SWING DOOR LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC A 404.2.4, SEE FIGURE
 404.2.4.1(A).
  
 2ND REVIEW, NOT ADDRESSED. THIS DOOR IS NOW LABELED
 DOOR 1.
 3RD REVIEW, NOT ADDRESSED. IT APPEARS THAT THE SIMPLEST
 SOLUTION IS TO REVERSE THE DOOR SWING. THERE ARE OTHER
 OPTIONS (DOOR OPENER, WIDEN THE CORRIDOR) - REVISE THE
 PLAN TO COMPLY WITH THIS ACCESSIBILITY REQUIREMENT.
  
 12-15. OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 14:05 Rev Time 0.00
Received By shill Date 2017-06-24 Time 13:56 Sent To  
Notes
2017-06-24 14:21:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR FLORIDA INTERNATIONAL
 ENGINEERING & TESTING LAB. REVISE TO INCLUDE, FS471,
 FAC61G15-23.002.
  
 2ND REVIEW, THIS WAS NOT PROPERLY ADDRESSED.
  
 THE TITLE BLOCK SHOULD INCLUDE THE ENGINEER'S NAME. THE
 TITLE BLOCK HAS "V.M.B. VENKATESAN" AS THE NAME, BUT
 DBPR RECORDS SHOW VENKATESAN AS THE FIRST NAME. IF THIS
 IS THE ENGINEER'S LAST NAME, CONTACT FBPE TO CORRECT.
 IF THIS IS THE ENGINEER'S FIRST NAME, REVISE TITLE
 BLOCK TO INCLUDE NAME AS LICENSED.
  
 THE TITLE BLOCK SHOULD INCLUDE THE BUSINESS LICENSE
 NUMBER. DBPR RECORDS INDICATE THAT THIS IS CA#27273.
  
 REVISE THE TITLE BLOCK FOR SHEETS WHICH ARE REVISED.
 FOR ALL OTHERS (WHICH HAVE BEEN REVIEWED, PASSED AND
 STAMPED), A STICKER OR HAND WRITTEN INFO IS RECOMMENDED
 TO AVOID ADDITIONAL REVIEWS.
  
 3-4. OK
  
 5. THE PARKING LOT DOES NOT COMPLY WITH THE FLORIDA
 BUILDING CODE OR ADA. THE ACCESSIBLE PARKING SPACE IS
 NOT LOCATED ON THE CLOSEST ROUTE. SUBMIT A PERMIT
 APPLICATION TO BRING THE PARKING LOT INTO COMPLIANCE.
 IT APPEARS THAT THE PARKING LOT WAS RESTRIPED SOME TIME
 BETWEEN 2009 AND 2011 WITHOUT A PERMIT.
  
 2ND REVIEW, A PAGE WAS ADDED TO THE PLAN. THIS IS TO BE
 ADDRESSED WITH A SEPARATE APPLICATION. PLEASE SUBMIT
 THAT PAGE WITH A PERMIT APPLICATION FOR REVIEW. PARKING
 LOT PERMIT APPLICATION IS TO BE SUBMITTED PRIOR TO
 ISSUANCE OF THIS RENOVATION PERMIT (NOW). FAILURE TO
 APPLY IMMEDIATELY WILL RESULT IN A VIOLATION ISSUED FOR
 THE WORK ALREADY DONE WITHOUT PERMIT. (A 4X FEE HOLD
 HAS BEEN ADDED BUT NO WRITTEN VIOLATION ISSUED AT THIS
 TIME.)
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO: PRIOR TO FINAL
 INSPECTION, PARKING LOT PERMIT IS TO BE ISSUED AND
 COMPLETED (COMPLIANCE WITH ACCESSIBLE ROUTE REQUIREMENT
 FOR ALTERATIONS, FBC ACCESSIBILITY).
  
 6-7. OK
  
 8. REVISE PLAN TO PROVIDE INFORMATION ABOUT THE
 STOCKROOM AND THE STORAGE AREAS; WHAT WILL BE STORED IN
 THESE SPACES? FBC 107.
  
 9-10. OK
  
 11. THE UNNUMBERED SWING DOOR LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC A 404.2.4, SEE FIGURE
 404.2.4.1(A).
  
 2ND REVIEW, NOT ADDRESSED. THIS DOOR IS NOW LABELED
 DOOR 1.
  
 12. OK
  
 NEW COMMENTS:
  
 13. THE HALLWAY, WHEN SCALED, IS LESS THAN 3', SEE FBC
 A 403.5.1.
  
 14. ENTRANCE TO THE BATHROOM DOES NOT MEET THE
 MANEUVERING CLEARANCE REQUIRED BY FBC A 404.2.4.2. SIDE
 APPROACH REQUIRES 42" MINIMUM.
  
 13. PLAN INCLUDES A DESCRIPTIVE NOTE ON EACH SHEET THAT
 STATES "BUILDING REPAIRS"; WHAT WILL BE REPAIRED? FBC
 107.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-26 Cont ID  
Sent By shill Date 2017-04-26 Time 17:34 Rev Time 0.00
Received By shill Date 2017-04-26 Time 17:33 Sent To  
Notes
2017-04-26 17:34:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLANS APPEAR TO BE PRINTED HALF SIZE. SEE SHEET A2,
 SCALE IS 1/4", BUT THIS DOES NOT CORRELATE WITH THE
 PLAN. FBC 107, PLANS TO BE LEGIBLE FOR PLAN REVIEW,
 INSPECTIONS, RECORD RETENTION. PRINT FULL SIZE PLANS
 FOR REVIEW.
  
 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR FLORIDA INTERNATIONAL
 ENGINEERING & TESTING LAB. REVISE TO INCLUDE, FS471,
 FAC61G15-23.002.
  
 3. SHEET A1 STATES THAT THIS SPACE IS 182 SQUARE FEET,
 REVISE AS THE SPACE APPEARS LARGER.
  
 4. SHEET A0 STATES THAT THIS IS A LEVEL 2 ALTERATION.
 IS THIS ALSO A CHANGE OF OCCUPANCY?
  
 5. THE PARKING LOT DOES NOT COMPLY WITH THE FLORIDA
 BUILDING CODE OR ADA. THE ACCESSIBLE PARKING SPACE IS
 NOT LOCATED ON THE CLOSEST ROUTE. SUBMIT A PERMIT
 APPLICATION TO BRING THE PARKING LOT INTO COMPLIANCE.
 IT APPEARS THAT THE PARKING LOT WAS RESTRIPED SOME TIME
 BETWEEN 2009 AND 2011 WITHOUT A PERMIT.
  
 6. PAPA RECORDS SHOW THREE SUITE NUMBERS FOR THIS
 LOCATION. DOES APPLICANT PREFER SEPARATE ADDRESSES?
 THIS MAY BE POSSIBLE, PLEASE ADVISE.
  
 THE APPLICATION IS FOR SUITE 102, BUT IF SUBWAY IS
 #101, SHOULDN'T THIS UNIT BE #103? PREVIOUS PERMITS
 SHOW THAT SUITE #102 IS IN THE CENTER; IT IS NOT CLEAR
 WHY THE APPLICATION IS FOR SUITE 102.
  
 7. PROVIDE TOTAL SQUARE FOOT AREA FOR THIS SPACE, FBC
 CHAPTER 10. LS1 SHOWS AN OCCUANT LOAD OF 4 FOR AN
 OFFICE, BUT NO OFFICE IS SHOWN ON THE PLAN. REVISE TO
 CLARIFY.
  
 8. REVISE PLAN TO PROVIDE INFORMATION ABOUT THE
 STOCKROOM AND THE STORAGE AREAS; WHAT WILL BE STORED IN
 THESE SPACES? FBC 107.
  
 9. A LOBBY IS SHOWN, BUT PLAN STATES THIS IS
 MERCANTILE. WHERE IS THE STORE? ONLY A LOBBY, SERVICES
 AREA, STOCKROOM AND STORAGE ARE SHOWN, FBC 107.
  
 10. REVISE PLAN TO CLARIFY WHAT THE PURPOSE IS OF THE
 "SERVICE AREA". IF THIS IS A CHECK OUT COUNTER, REVISE
 PLAN TO INCLUDE DETAILS TO SHOW COMPLIANCE WITH FBC A
 904, CHECK OUT AISLES AND SALES AND SERVICE COUNTERS.
  
 11. THE UNNUMBERED SWING DOOR LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC A 404.2.4, SEE FIGURE
 404.2.4.1(A).
  
 12. REVISE PLAN TO SHOW DETAILS FOR THE ENTRANCE TO
 SHOW COMPLIANCE WITH FBC A 303.
  
 13. PLAN INCLUDES A DESCRIPTIVE NOTE ON EACH SHEET THAT
 STATES "BUILDING REPAIRS"; WHAT WILL BE REPAIRED? FBC
 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-15 Cont ID  
Sent By jleahy Date 2017-06-15 Time 18:12 Rev Time 0.00
Received By jleahy Date 2017-06-15 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-25 Cont ID  
Sent By jleahy Date 2017-04-25 Time 11:42 Rev Time 0.00
Received By jleahy Date 2017-04-25 Time 11:42 Sent To  
Notes
2017-04-25 11:49:19JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL
 FOR THE LIGHTING SERVING THAT AREA. THE REQUIRED
 CONTROLS SHALL BE LOCATED WITHIN THE AREA SERVED
 BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES
 THE LIGHTS SERVED AND INDICATES THEIR STATUS.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR
 LIGHTING EQUIPMENT AS DETERMINED IN ACCORDANCE WITH
 SECTIONS C405.5.1.1 THROUGH C405.5.1.4.
  
 FAULT CURRENT CALCULATION REQUIRED BY 110.24
  
 SUBMIT THE INFORMATION SHOWING LIGHTING CONTROL,
 DENSITY LIGHTING CACULATION, AND FAULT CURRENT
 BEFORE THE ELECTRICAL FINAL FOR REVIEW.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By scaldero Date 2017-06-14 Time 12:54 Rev Time 0.00
Received By scaldero Date 2017-06-14 Time 12:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-27 Cont ID  
Sent By scaldero Date 2017-04-27 Time 11:05 Rev Time 0.00
Received By scaldero Date 2017-04-27 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-24 Cont ID  
Sent By shill Date 2017-07-24 Time 09:48 Rev Time 0.00
Received By shill Date 2017-07-14 Time 10:55 Sent To  
Notes
2017-07-18 10:55:58RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-10 Cont ID  
Sent By shill Date 2017-07-10 Time 16:41 Rev Time 0.00
Received By shill Date 2017-07-03 Time 10:41 Sent To  
Notes
2017-07-03 10:41:44SHILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 14:21 Rev Time 0.00
Received By shill Date 2017-06-08 Time 16:09 Sent To  
Notes
2017-06-09 16:10:02B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-02 Cont ID  
Sent By gjohnson Date 2017-05-02 Time 13:09 Rev Time 0.00
Received By gjohnson Date 2017-04-18 Time 14:07 Sent To  
Notes
2017-04-19 14:07:43B10

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 13:56 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 13:12 Sent To  
Notes
2017-06-16 13:57:21NO PLUMBING WORK UNDER THE SCOPE OF THIS PERMIT

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By gjohnson Date 2017-05-02 Time 13:06 Rev Time 0.00
Received By gjohnson Date 2017-05-02 Time 11:41 Sent To  
Notes
2017-05-02 13:09:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WILL THERE BE ANY PLUMBING WORG DONE. PER WPB AMEND
 TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  