Plan Review Details - Permit 17040776
Plan Review Stops For Permit 17040776
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By shill Date 2017-08-15 Time 07:17 Rev Time 0.00
Received By shill Date 2017-08-15 Time 07:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-26 Cont ID  
Sent By shill Date 2017-04-26 Time 16:20 Rev Time 0.00
Received By shill Date 2017-04-25 Time 17:16 Sent To  
Notes
2017-04-26 16:21:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. MANY DOORS DO NOT APPEAR TO HAVE THE 18" MANEUVERING
 CLEARANCE REQUIRED, PULL SIDE, FBC A 202.4, FIGURE
 404.2.4.1. REVISE PLAN; SEE DOORS EXAM 108, EXAM 106,
 EXAM 105, OFFICE 104, SUPPLY 113, CHECK ALL. IT IS NOT
 CLEAR WHY SO MANY OF THE EXISTING DOORS DO NOT COMPLY.
 IF ALL DOORS ARE NOT FIXED, PLEASE CONTACT ME PRIOR TO
 RESUBMITTAL.
  
 2. ADVISE AS TO STATUS OF EXPIRED ABANDONED PERMIT
 APPLICATIONS 13060827,15010788,15010790 (AND POSSIBLY
 OTHERS) TO INSTALL A 80KW DIESEL GENERATOR AND FUEL
 TANK. THIS PROPERTY ALSO HAS SEVERAL OTHER EXPIRED
 PERMITS. FOR ASSISTANCE IN RESOLVING THE EXPIRED
 PERMITS, PLEASE CONTACT:
  
 [email protected]
 561-805-6690
  
 OF PARTICULAR CONCERN ARE THE ABANDONED GENERATOR AND
 FUEL TANK APPLICATIONS.
  
 3. FBC A, FBC 107, PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB. A COST BREAK DOWN MAY BE REQUIRED.
  
 4. SEE LOUNGE DOORS AND FBC A 404.2.6, SHOW DISTANCE
 BETWEEN THE TWO DOORS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By jpearson Date 2017-08-21 Time 13:09 Rev Time 0.00
Received By jpearson Date 2017-08-21 Time 13:09 Sent To  
Notes
2017-08-21 13:10:56REVIEWED PER COMMENTS ONLY. JP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-25 Cont ID  
Sent By vperez Date 2017-04-25 Time 08:28 Rev Time 0.00
Received By vperez Date 2017-04-25 Time 08:28 Sent To  
Notes
2017-04-25 08:31:59INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A NOTE TO DRAWINGS INDICATING THAT NO NEW
 LOADS ARE BEING ADDED UNDER THE SCOPE OF WORK. A NOTE
 WILL SUFFICE. FBC 107 MINIMUM PLAN REVIEW CRITERIA
 2. ADD A NOTE TO INDICATE REQUIRED SEPARATE LOW VOLTAGE
 PERMITS FOR TEL/DATA OUTLETS.
 3. SHOW ON PLANS THE EXISTING PANEL BOARD WHERE THE
 EXISTING CIRCUITS ORIGINATE. LABEL POWER AND LIGHTING
 OUTLETS WITH EXISTING CIRCUIT NUMBERS. NO LOAD
 CALCULATIONS ARE REQUIRED DUE TO NO LOADS BEING
 ALTERED. FBC 107 MINIMUM PLAN REVIEW CRITERIA
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By pleduc Date 2017-08-16 Time   Rev Time 0.00
Received By pleduc Date 2017-08-16 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 09:18 Sent To PC
Notes
2017-04-28 12:23:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By cpuell Date 2017-08-11 Time 17:08 Sent To  
Notes
2017-08-14 17:09:15B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-18 Time 13:21 Sent To  
Notes
2017-04-19 13:21:24B25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 15:49 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By ccole Date 2017-04-24 Time 17:48 Rev Time 0.00
Received By ccole Date 2017-04-24 Time 17:39 Sent To  
Notes
2017-04-24 17:48:361ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17040776
 4/24/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-04-26 Cont ID  
Sent By shill Date 2017-04-26 Time 15:50 Rev Time 0.00
Received By shill Date 2017-04-26 Time 15:50 Sent To  
Notes
2017-04-26 15:51:18PAPA VALUE $1,991,349
 CUMULATIVE 5 YEAR IMPROVEMENTS = $716,766 (36%)
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 13:52 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 07:00 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 15:22 Sent To  
Notes
2017-04-28 07:08:171ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2. SHT.ME-1 THE GENERAL PLUMBING NOTES, SHOCK ARRESTOR
 SCHEDULE AND PIPE SLOPE TABLE INDICATE THAT THERE MIGHT
 WORK DONE ON THE PIPING NOT JUST FIXTURE CHANGE OUT
 PLEASE CLARIFY. PER WPB AMEND TO FBC
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  