Plan Review Details - Permit 17040737
Plan Review Stops For Permit 17040737
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-16 Cont ID  
Sent By jwitmer Date 2017-08-16 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-12 Cont ID  
Sent By jwitmer Date 2017-07-12 Time 10:50 Rev Time 0.00
Received By jwitmer Date 2017-07-12 Time 07:15 Sent To  
Notes
2017-07-12 10:50:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040737
 ADD: 4400 PORTOFINO WAY
 CONT: TBD/ TO BE DETERMINED
 TEL: ??????????
 E-MAIL: [email protected] / SANDY MAKSYM
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 12/ 2017
 ACTION: PASSED/ BUILDING PROVISO
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTAL: WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL: IDENTIFY
 GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014
 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL
 BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By jwitmer Date 2017-05-22 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 14:43 Sent To  
Notes
2017-05-22 15:07:352014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040737
 ADD: 4400 PORTOFINO WAY
 CONT: TBD/ TO BE DETERMINED
 TEL: ??????????
 E-MAIL: [email protected] / SANDY MAKSYM
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 19/ 2017
 ACTION: DENIED
  
 1) SHEET 003-A0.03 ALLOWABLE BUILDING INCREASES. UNDER
 THIS HEADING AREA INCREASES WERE TAKEN FOR FIRE
 SPRINKLERS. THE BUILDING MAYBE FIRE SPRINKLERED BUT NO
 FIRE SPRINKLER PLANS WERE SUBMITTED UNDER THIS REVIEW.
 FIRE SPRINKLER PLANS WILL BE REQUIRED FOR THE
 RECONFIGURATION OF SPACE AND FOR BENEATH THE NEW
 MEZZANINE LEVEL AS WELL, ADDITIONAL FIRE AREAS WERE
 ADDED.
 105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY BUILDING
 CONSTRUCTION, ERECTION, ALTERATION, MODIFICATION,
 REPAIR, OR ADDITION UNLESS THE APPLICANT FOR SUCH
 PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH ISSUES
 THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH APPLY
 TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE
 ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE
 DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471,
 FLORIDA STATUTES: 2. FIRE SPRINKLER DOCUMENTS FOR ANY
 NEW BUILDING OR ADDITION WHICH INCLUDES A FIRE
 SPRINKLER SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER
 HEADS. A CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV,
 CERTIFIED UNDER SECTION 633.521, FLORIDA STATUTES, MAY
 DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND
 MAY DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS,
 NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 2) SHEET A0.03 UNDER THE APPLICABLE CODES LIST THE FAIR
 HOUSING ACT DESIGN MANUAL, AND THE AMERICANS WITH
 DISABILITIES ACT, 2010 EDITION ANSI A117.1 2003 EDITION
 FOR CODES THAT DEAL WITH ACCESSIBILITY ELEMENTS. THE
 2014 FBC-ACCESSIBILITY CODE IS NOT MENTIONED AS PART OF
 THE APPLICABLE CODES. SHEETS A0.05 AND A0.06 INCLUDE
 THE 2014 ACCESSIBILITY CODE FOR PUBLIC SPACES
 (LEASING). THE WHERE THE MORE STRINGENT OF THE 2 CODES
 WILL APPLY FOR THE COMMON USE ELEMENTS, PARKING SPACES
 AT THE CLUBHOUSE. A STATEMENT MUST BE ADDED FOR PUBLIC
 AND COMMON USE AREAS, WITH THE EXCEPTION OF THE LEASING
 OFFICE, THAT THE REMAINDER OF THE CLUBHOUSE IS FOR THE
 USE OF THE RESIDENCE AND THEIR GUEST ONLY, NO UNITS ARE
 TO BE RENTED OUT AS TIME SHARE UNITS. IF THE COMMON
 AREAS ARE MADE AVAILABLE TO THE PUBLIC ONLY
 PERIODICALLY, SUCH AS A FESTIVAL OR SEASONAL EVENT,
 THEY MUST COMPLY WITH THE 2014 FLORIDA ACCESSIBILITY
 CODE WHICH IS MORE RESTRICTIVE THAN THE ADA.
  
  
 3A) PLEASE NOTE SHEET A0.07 1ST FLOOR LIFE SAFETY PLAN.
 OF THE EXERCISE ROOM OF 2931 /50 SQ. FT. WITH AN
 OCCUPANT LOAD OF 59. IF EQUIPMENT IS SHOWN, THE AREA
 WHERE THE EQUIPMENT IS LOCATED CAN BE TAKEN AT 50 SQ.
 FT. / OCCUPANT. IF A PORTION OF THE GYM IS FOR LINE
 DANCING, PALATES OR SIMILAR EXERCISING IT CAN BE TAKEN
 AT 15 OR THE MORE RESTRICTIVE 7 SQ. FT. 2931/7= 418
 OCCUPANTS. PLEASE SHOW THE AREAS WHERE EQUIPMENT WILL
 BE PLACED FOR THE REDUCED OCCUPANT LOAD. ASSEMBLY
 OCCUPANT LOADS ARE TAKEN AS NET.
  
 3B) PLEASE NOTE SHEET A0.07 1ST FLOOR LIFE SAFETY PLAN.
 OF THE EXERCISE ROOM WITH 292 SQ. FT. . IF EQUIPMENT IS
 SHOWN, THE AREA WHERE THE EQUIPMENT IS LOCATED CAN BE
 TAKEN AT 50 SQ. FT. / OCCUPANT. PLEASE SHOW THE AREAS
 WHERE EQUIPMENT WILL BE PLACED FOR THE REDUCED OCCUPANT
 LOAD. ASSEMBLY OCCUPANT LOADS ARE TAKEN AS NET.
 4) PLEASE NOTE SHEET A0.08 THE MEZZANINE LIFE SAFETY
 PLAN SHOW AN AREA OF 968 SQ. FT. /50 SQ. FT. WITH AN
 OCCUPANT LOAD OF20. WHERE THE EQUIPMENT IS SHOWN, 313
 SQ. FT. THIS CAN BE TAKEN AT 50 SQ. FT. / OCCUPANT OR 7
 OCCUPANTS. . IF A PORTION OF THE GYM IS FOR LINE
 DANCING, PALATES OR SIMILAR EXERCISING IT CAN BE TAKEN
 AT 15 OR THE MORE RESTRICTIVE 7 SQ. FT. 655/7= 94
 OCCUPANTS. PLEASE SHOW THE AREAS WHERE EQUIPMENT WILL
 BE PLACED FOR THE REDUCED OCCUPANT LOAD. ASSEMBLY
 OCCUPANT LOADS ARE TAKEN AS NET.
  
 5) SHEETS A1.2.2 AND A1.2.3 THE EXERCISE ROOM SHOW
 DOORS;
 20-100 GROUP HARDWARE 01
 20-101 GROUP HARDWARE 03
 20-102 GROUP HARDWARE 03
 I COULD NOT FIND THE HARDWARE SCHEDULE AND COMPLIANCE
 WITH 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 WHEN THE OCCUPANT LOAD IS 50 OR MORE PANIC HARDWARE IS
 REQUIRED.
  
 6) 162_ SHEET SDT-1 DETAIL:
 6A) 4 & 5 BOTH SHOW WEDGE ANCHORS 3-5/8 EMBED. THE
 PLANS ARE SILENT IF THE CELLS ARE ALREADY FILED CELLS
 OR IF THEY ARE TO BE FILED AND WITH WHAT STRENGTH
 GROUT? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 6B) DETAIL #4 SHOWS 1 ? X 1 ? X 1/8 INCH CROSS BRACING
 BUT NO WELDING TYPE OR LENGTH IS GIVEN? 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 8) SHEET 163_STD-4 DETAILS 1 & 2 SHOW THE USE OF 6X6
 WOOD COLUMNS, SPECIES NOT PROVIDED, AND IN DETAIL 1 THE
 USE OF 2 LVLS TO SET ATOP OF THE (2) 6X6 POST. THE
 PLANS INDICATE THE USE OF SIMPSON HD3B CONNECTORS AT
 THE BASE, NO ATTACHMENT TO THE CONCRETE BLOCK? AND
 SIMPSON BEAM HANGERS (LEFT BLANK)?
 WILL HANGERS BE REQUIRED OR STRAPS FROM THE WOOD
 COLUMNS?
  
 9) SHEET A0.07 THE LIFE SAFETY PLAN PLEASE PROVIDE THE
 EXITING FROM THE BUILDING , ASSEMBLY AND BUSINESS AREAS
 THAT EXIT THROUGH THE POOL DECK. HOW WILL KIDS BE KEPT
 FROM THE POOL DECK AND POOL? PLEASE SHOW COMPLIANCE
 WITH EFFECTIVE BARRIER.? A BARRIER WHICH CONSISTS OF A
 BUILDING, OR EQUIVALENT STRUCTURE, PLUS A 48-INCH (1219
 MM) MINIMUM HEIGHT FENCE ON THE REMAINING SIDES OR A
 CONTINUOUS 48-INCH (1219 MM) MINIMUM HEIGHT FENCE. ALL
 ACCESS THROUGH THE BARRIER MUST HAVE ONE OR MORE OF THE
 FOLLOWING SAFETY FEATURES: ALARM, KEY LOCK OR
 SELF-LOCKING DOORS AND GATES. SAFETY COVERS THAT COMPLY
 WITH THE AMERICAN SOCIETY FOR TEST MATERIALS STANDARD
 F1346-91 (2003) MAY ALSO BE CONSIDERED AS AN EFFECTIVE
 BARRIER.
 PLEASE SHOW COMPLIANCE WITH FBC-B 454. 1.3.1.9.
  
 10) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 12) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-19 Cont ID  
Sent By jleahy Date 2017-07-19 Time 16:20 Rev Time 0.00
Received By jleahy Date 2017-07-19 Time 15:59 Sent To  
Notes
2017-07-19 16:21:20FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED ASBUILT PANEL SCHEDULES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 11:48 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 11:48 Sent To  
Notes
2017-05-24 11:54:48JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 PROVIDE CUT SHEETS FOR FIXTURES.
  
 PAGE E1.1L
  
 C405.5 INTERIOR LIGHTING POWER REQUIREMENTS
 (PRESCRIPTIVE).
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR LIGHTING
 EQUIPMENT AS DETERMINED
 IN ACCORDANCE WITH SECTIONS C405.5.1.1 THROUGH
 C405.5.1.4.
  
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND
 C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA.
 THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE
 OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL
 CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR
 LESS ENCLOSED BY FLOOR-TO-
 CEILING HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL
 DEVICES SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF
 LIGHTS WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING THE SPACE, AND SHALL EITHER BE
 MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY TURN
 THE LIGHTING ON TO NOT
 MORE THAN 50 PERCENT POWER.
  
 PAGE E6.1
  
 PANEL SCHEDULES TO VAGUE NEED TO BE MORE SPECIFIC TO
 LOCATIONS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 13:24 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By wjolin Date 2017-06-27 Time 15:55 Rev Time 0.00
Received By wjolin Date 2017-06-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-26 Cont ID  
Sent By wjolin Date 2017-04-26 Time 17:14 Rev Time 0.00
Received By wjolin Date 2017-04-26 Time 15:46 Sent To  
Notes
2017-04-26 17:14:054400 PORTOFINO WAY - CLUBHOUSE
 PERMIT #17040737
 FIRE DEPARTMENT COMMENTS:
  
 GENERAL:
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT WHEN THE SCOPE
 OF WORK AFFECTS 50 OR MORE SPRINKLERS. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
  
 SHEET A0.07:
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SEVERAL EXITS APEAR TO BE ROUTED THROUGH THE POOL DECK
 AREA. THIS WILL REQUIRE THE LIFE SAFETY PLAN TO INCLUDE
 THE OCCUPANTS EGRESSING FROM THE POOL AREA AND SHOWING
 THE EXITS DISCHARGING TO A PUBLIC WAY.
  
 IF THE POOL DECK IS BEING USED TO EGRESS BUILDING
 OCCUPANTS, HOW ARE CHILDREN BEING PROTECTED FROM
 UNRESTRICTED ACCESS INTO THE POOL?
  
 PROVIDE A FURNITURE/EQUIPMENT/SEATING PLAN FOR THE
 FITNESS, KID FITNESS AND CLUB ROOM JUSTIFYING THE USE
 OF 50 AND 15 SQ.FT. OCCUPANT LOAD FACTORS.
  
 THE CONFERENCE ROOM SHOULD BE CALCULATED USING AN
 OCCUPANT LOAD FACTOR OF 15 SQ.FT. IN LIEU OF 100 SQ.FT.
  
 THE LARGE OPEN LOBBY ADJACENT TO THE COFFEE BAR IS
 PRIME SPACE FOR OCCUPANTS TO UTILIZE AS AN ASSEMBLY
 SPACE. THE OFFICE DOES NOT SUPPORT THE DESIGNATION OF
 THIS SPACE AS A BUSINESS OCCUPANCY WITH ONLY 12
 OCCUPANTS.
  
 DESCRIBE WHAT WILL BE STORED IN THE GARAGE. WILL ANY
 GENERAL MAINTENANCE ACTIVITIES OCCUR IN THIS SPACE?
  
  
 SHEET A0.08:
 THE EXERCISE MEZZANINE INDICATES AN OCCUPANT LOAD
 FACTOR OF 50 SQ.FT.; HOWEVER, MORE THAN HALF OF THE
 FLOOR SPACE DOES NOT INDICATE ANY EQUIPMENT JUSTIFYING
 THE LOAD FACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-09-07 Time   Rev Time 0.00
Received By cpuell Date 2017-08-04 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-22 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 11:55 Rev Time 0.00
Received By jleahy Date 2017-04-20 Time 14:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-22 Cont ID  
Sent By jwitmer Date 2017-05-22 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-09-07 Cont ID  
Sent By ccole Date 2017-09-07 Time 16:11 Rev Time 0.00
Received By ccole Date 2017-09-07 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 16:42 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 15:42 Sent To  
Notes
2017-07-24 16:54:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040737
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE SUBMITTED ENERGY FORM C402 IS ACCEPTABLE FOR THE
 RENOVATED POTION OF THE BUILDING BUT CANNOT BE USED FOR
 THE NEW CONDITIONED GARAGE ADDITION WHICH MUST MEET
 FULL COMPLIANCE- SEE SECTION C101.4.3 FBC-14 ENERGY
 CONSERVATION.
  
 2) SHEET M6.3: THE REVISED VENTIALTION CALCULATIONS DO
 NOT INCLUDE AHU'S 6, 7, & 8 WHICH ARE SYSTEMS SUPPLYING
 THE FITNESS CENTER, MEZZANINE, KIDS ROOM, AND THE
 CLUBROOM.
  
 3) AS PREVIOUSLY REQUESTED, PROVIDE THE WIND LOAD
 ENGINEERING FOR TIE DOWN OF THE EXTERIOR CONDENSER
 (CU-G).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 13:53 Rev Time 0.00
Received By ccole Date 2017-05-04 Time 13:52 Sent To  
Notes
2017-05-04 14:06:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040737
 5/4/17
  
 1) BASED ON THE PROJECT INFORMATION LISTED ON SHEET
 A0.03 COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION
 CODE COMPLIANCE IS REQUIRED. THE PROJECT IS LISTED AS A
 LEVEL III ALTERATION, WITH AREAS THAT ARE DESIGNATED AS
 CHANGES OF OCCUPANCY, AND THERE IS AN NEW CONDITIONED
 GARAGE SHOWN ON THE PLANS. PLEASE REFER TO SECTIONS
 C101.4.3 AND C101.4.4 AND PROVIDE ENERGY
  
 CALCULATIONS. SEE SECTION C101.5 FOR COMPLIANCE
 SUBMITTALS, AND C401.2 FOR COMPLIANCE PATHS.
  
 2) SHEET M-6.1: THE SUBMITTED AC COOLING AND HEATING
 CALCULATIONS ARE INDICATING SYSTEMS 2-8 AS SHOWN ON THE
 SCHEDULE ARE OVERSIZED- SEE SECTION C403..2.2 AND
 CORRECT.
  
 3) PROVIDE AC CALCULATIONS FOR THE DUCTLESS SYSTEM IN
 THE GARAGE- CU-G/AHU-G.
  
 4) M-1.1: THE OUTSIDE AIR CALCULATIONS ARE INCOMPLETE
 AND NOT IN COMPLIANCE WITH TABLE 403.3 FBC-14
 MECHANICAL. PLEASE CORRECT THE SCHEDULE SO THAT IT
 INDICATES THE ROOMS OR SPACES THAT THE O/A IS BEING
 SUPPLIED TO, AND INCLUDES THE CORRECT CFMS PER PERSON
 AND CFMS PER SQ. FT. CALCULATION AS REQUIRED BY TABLE
 403.3. THE CURRENT PLAN IS INDICATING O/A CFMS THAT
 DON'T MATCH
  
 THE CFMS IN THE SCHEDULE.
  
 5) M-6.2: PROVIDE THE WIND LOAD DESIGN CRITERIA AND THE
 LATERAL AND UPLIFT PRESSURES USED IN DETERMINING THE
 CONDENSER ANCHORING DETAILS- SECTION 301.15.
  
 6) M-6.2: REVISE THE AHU DETAILS TO SHOW THE PRIMARY
 AND SECONDARY CONDENSATE PIPING DETAILS- SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-21 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2017-07-21 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 06:58 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 06:58 Sent To  
Notes
2017-05-23 07:12:521ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE RISER DIAGRAM FOR NEW PIPING. WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 2. INDICATE ON FLAT PLAN DRAWING WHAT PIPE IS EXISTING
 AND WHAT PIPE IS NEW. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By cpuell Date 2017-09-07 Time 16:33 Rev Time 0.00
Received By cpuell Date 2017-09-07 Time 16:33 Sent To  
Notes
2017-09-07 16:12:42MECH DIG/SIGS VERIFIED ON PLANS AND ENERGY CALCS- CCOLE
2017-08-16 15:00:4308/15/2017 ARCHITECTURAL AND STRUCTURAL SHEETS ARE 100%
 ELECTRONICALLY SIGNED AND SEALED. J. W.
2017-07-24 16:59:03MECH DIG/SIGS VERIFIED- CCOLE- 7/24/17
2017-07-21 12:45:097/21/17 DIG SIG ON PLUMB PG IARE GOOD/GPJ
2017-07-12 11:19:542ND BUILDING REVIEW/ SIGNATURES JULY 12/ 2017 SHEETS
 THAT ARE MISSING THEIR ELECTRONIC SIGNATURE.
 003-A0.03/ V2
 005-A0.06/ V2
 006-A0.07/ V2
 073-A7.01/ V2
 074-A7.02/ V2
 085-A7.61
 162-SDT-3 V2
 163-SDT-4 V2
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-08-29 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-29 Time 14:08 Sent To  
Notes
2017-08-29 14:09:08PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-06-30 Time   Rev Time 0.00
Received By pgreilic Date 2017-06-30 Time 09:00 Sent To  
Notes
2017-06-30 09:01:19PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-05-05 Time   Rev Time 0.00
Received By pgreilic Date 2017-05-05 Time 11:03 Sent To  
Notes
2017-05-05 11:03:40PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved