Plan Review Details - Permit 17040710
Plan Review Stops For Permit 17040710
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-10 Cont ID  
Sent By jwitmer Date 2017-08-10 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2017-08-10 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2017-05-12 Time 11:49 Sent To  
Notes
2017-05-12 14:31:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040710
 ADD: 1601 FORUM PLACE SUITE # 700
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 12/ 2017
 ACTION: DENIED
  
 1) NOTE: 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. IN THE AREA OF
 THE ELEVATOR LOBBY, UNDER THE 2014 FBC-B 713.14.1
 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE. THIS APPLIES TO HIGHRISE BUILDINGS
 SINCE EXCEPTION 4.3 DEALS WITH ELEVATORS SERVING FLOOR
 LEVELS OVER 75 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS IN HIGH-RISE
 BUILDINGS. THE 2012 IBC CODE COMMENTARY ALSO REFLECTS
 THE SAME WORDING. THE FIRE CODES MAY HAVE A MORE
 RESTRICTIVE REQUIREMENT IF SO THEN THE MORE STRINGENT
 OF THE 2 CODES APPLIES.
 2) SHEET A1.11 SHOWS A HORIZONTAL DOOR IDENTIFIED AS #
 30. THE DOOR SCHEDULE INDICATES HARDWARE TYPE 1.
 THE DOOR HARDWARE SCHEDULE IS BLANK. 2014 ACCESS. CODE
 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES (865
 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE IN THE
 FULLY OPEN POSITION, OPERATING HARDWARE SHALL BE
 EXPOSED AND USABLE FROM BOTH SIDES.
  
 3) SHEET A1.11 SHOWS BOOTH SEATING (725). SHEET A4.21
 DETAIL 7 SHOWS THE BOOTH AS RAISED SEATING OFF THE
 FLOOR 8.5 INCHES. PLEASE SHOW WHERE THE EQUIVALENT
 SEATING FOR HANDICAPPED WILL BE? 2014 FBC-ACCESS. CODE
 103 EQUIVALENT FACILITATION. 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4) SHEET A4.23 THE DRINKING FOUNTAIN DETAILS 1,2, & 3
 SHOW A ACCESSIBLE DRINKING FOUNTAIN. TO THE RIGHT SIDE
 OF THE DRINKING FOUNTAINS THERE IS A WALL PARALLEL TO
 THE DRINKING FOUNTAINS. THIS WALL PROTECTS OCCUPANTS
 WITH LOW VISION FROM RUNNING INTO THE DRINKING
 FOUNTAIN. THE RIGHT SIDE DRINKING FOUNTAIN IS ALSO NOT
 MORE THAN 27 INCHES COMPLYING WITH THE REQUIREMENT FOR
 PROTRUDING OBJECTS.
 ON THE LEFT SIDE OF THE DRINKING FOUNTAIN FOR STANDING
 PEOPLE DOES NOT COMPLY WITH PROTRUDING OBJECTS 2014
 FBC-ACCESS. CODE 307.2.
  
 5) SHEET A4.23 THE RECEPTION DESK DOES NOT INDICATE
 COMPLIANCE WITH 2014 ACCESS. CODE 904.3.3 CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
 6) SHEET M2.1 SHOWS A DUCT FOR THE O/A PENETRATING THE
 FIRE RATED ELEVATOR LOBBY WALL. SHOW COMPLIANCE WITH
 713.14.1. SECTION 716.5.3 AS REQUIRED FOR CORRIDOR
 WALLS AND PENETRATIONS OF THE ELEVATOR LOBBY ENCLOSURE
 BY DUCTS AND AIR TRANSFER OPENINGS SHALL BE PROTECTED
 AS REQUIRED FOR CORRIDORS IN ACCORDANCE WITH SECTION
 717.5.4.1.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 08:36 Rev Time 0.00
Received By jleahy Date 2017-05-18 Time 08:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-09 Cont ID  
Sent By wjolin Date 2017-08-09 Time 18:15 Rev Time 0.00
Received By wjolin Date 2017-08-09 Time 18:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-23 Cont ID  
Sent By wjolin Date 2017-06-23 Time 15:32 Rev Time 0.00
Received By wjolin Date 2017-06-23 Time 15:12 Sent To  
Notes
2017-06-23 15:31:591601 FORUM PLACE #700
 PERMIT #17040710
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER FBC SECTION 907.1.1
 CONSTRUCTION DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR
 FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION
 CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL."
 PER SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT: DOOR LOCKING ARRANGEMENTS OF THE
 CORRIDORS AND ELEVATOR LOBBY ONLY PROVIDE A SINGLE
 MEANS OF FREE EGRESS FROM THE MEN'S RESTROOM. A SINGLE
 MEANS OF EGRESS IS NOT PERMITTED IN A HIGH-RISE
 BUILDING.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-19 Cont ID  
Sent By wjolin Date 2017-04-19 Time 15:39 Rev Time 0.00
Received By wjolin Date 2017-04-19 Time 15:18 Sent To  
Notes
2017-04-19 15:37:111601 FORUM PLACE #700
 PERMIT #17040710
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL." PER SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 DOOR LOCKING ARRANGEMENTS OF THE CORRIDORS AND ELEVATOR
 LOBBY ONLY PROVIDE A SINGLE MEANS OF FREE EGRESS FROM
 THE MEN'S RESTROOM. A SINGLE MEANS OF EGRESS IS NOT
 PERMITTED IN A HIGH-RISE BUILDING.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-10 Cont ID  
Sent By   Date 2017-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-02 Time 15:03 Sent To  
Notes
2017-08-03 15:03:45RESUB ROUTED TO WJOLIN VIA FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-21 Time 15:29 Sent To  
Notes
2017-06-22 15:29:21C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By jleahy Date 2017-05-18 Time 08:36 Rev Time 0.00
Received By jleahy Date 2017-04-17 Time 13:38 Sent To  
Notes
2017-04-18 13:38:28C17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-12 Cont ID  
Sent By jwitmer Date 2017-05-12 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2017-05-12 Time 11:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By ccole Date 2017-07-17 Time 16:17 Rev Time 0.00
Received By ccole Date 2017-07-17 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By ccole Date 2017-04-21 Time 11:18 Rev Time 0.00
Received By ccole Date 2017-04-21 Time 11:18 Sent To  
Notes
2017-04-21 11:54:261ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CODES
 PERMIT #17040710
 4/21/17
  
 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) INDICATE HOW EF-1 WAS SIZED- PROVIDE A CALCULATION.
  
 3) M2.1: PROVIDE FLEX DUCT SIZES ON THE PLAN OR
 RELOCATE THE SCHEDULE FROM SHEET M6.1.
  
 4) M2.1 PROVIDE FIRE OR FIRE/SMOKE DAMPERS FOR THE O/A
 DUCTS AND EXHAUST DUCT PENETRATING THE FIRE-RATED
 ELEVATOR LOBBY WALLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-12 Cont ID  
Sent By gjohnson Date 2017-05-12 Time 09:56 Rev Time 0.00
Received By gjohnson Date 2017-05-12 Time 06:50 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy