Plan Review Details - Permit 17040694
Plan Review Stops For Permit 17040694
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By jwitmer Date 2017-06-08 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 11:00 Sent To  
Notes
2017-06-08 11:40:432014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040694
 ADD: 3000 N. AUSTRALIAN AVE.
 CONT: DOSDOURIAN ENTERPRISES
 TEL: 561-844-2990
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 08/ 2017
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: SHEET A103 KEYNOTE NUMBER A197
 REPAIR ROTTING TRUSSES. A STRUCTURAL ENGINEER WILL
 PROVIDE DETAILS ON HOW THE ROTTING TRUSSES ARE GOING TO
 BE REPAIRED. RESPONSE INDICATES STRUCTURAL ENGINEER
 EDWARD ZABALA IS TO PROVIDE DETAILS FOR FIELD REPAIR TO
 TRUSSES.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.. PLEASE SUBMIT TO THE ARCHITECT OF
 RECORD FOR SHOP DRAWING STAMP OF APPROVAL.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-19 Cont ID  
Sent By jwitmer Date 2017-05-19 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2017-05-19 Time 11:00 Sent To  
Notes
2017-05-19 16:13:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040694
 ADD: 3000 N. AUSTRALIAN AVE.
 CONT: DOSDOURIAN ENTERPRISES
 TEL: 561-844-2990
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 19, 2017
 ACTION: DENIED
  
 1A) THE 2014 FBC-EXISTING BUILDING CODE LEVEL II
 COMPLIANCE. 805.2 THE MEANS OF EGRESS SHALL COMPLY WITH
 THE REQUIREMENTS OF THIS SECTION.
 EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF EGRESS SERVING
 IT COMPLIES WITH NFPA 101.
 2. MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF
 THE BUILDING CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.
  
 THIS BUILDING WAS BUILT IN 1994 UNDER THE 1991 SSBC.
 WHEN REVIEWING IF THE CORRIDORS WERE RATED TABLE 700
 UNDER THE HEADING EXIT ACCESS CORRIDORS WALLS AND
 PARTITIONS (1HR.), OPENING PROTECTIVES (20 MIN.).
 FOOTNOTE 4 & 5. FOOTNOTE # 5 DEALS WITH GROUP I
 BUILDINGS SPRINKLERED. FOOTNOTE 4 SEE SECTION 702.4.2.
 EXIT ACCESS CORRIDORS ARE NOT REQUIRED TO BE RATED ON
 ANY SINGLE TENANT SPACE IN A GROUP B BUILDING WHEN THE
 BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM AND SMOKE DETECTORS
 INSTALLED IN RETURN AIR ARRANGED TO SHUT DOWN
 MECHANICAL VENTILATION SYSTEMS IN ACCORDANCE WITH THE
 STANDARD MECHANICAL CODE.
  
 I'VE TAKEN THIS CONCERN TO THE BUILDING OFFICIAL SINCE
 THIS BUILDING IS NOT SPRINKLERED AND THE CORRIDOR WALL
 SHOULD HAVE BEEN RATED FROM THE 1991 SBC. WE HAVE
 REVIEWED THE ORIGINAL 12 SHEETS OF PLANS WHEN THE
 BUILDING WAS BUILT.
 WE HAVE SOME QUESTIONS THE BUILDING OFFICIAL WOULD LIKE
 TO HAVE ANSWERED TO MAKE A FINAL DETERMINATION IF HE
 WILL REQUIRE FIRE RARING OF CORRIDORS WITH OPENING
 PROTECTIVES. THE (2) MECHANICAL CLOSETS SHOWN ON THE
 PLANS, ARE THE WALLS FIRE RATED WITH OPENING
 PROTECTIVES? PLEASE PROVIDE THE CEILING HEIGHT OF THE
 LOBBY, CORRIDORS AND OF THE MAIN AUDITORIUM. PLEASE
 ALSO PROVIDE THE HEADER HEIGHTS FOR THE OPENINGS
 LEADING INTO THE AUDITORIUM FROM THE CORRIDORS AND
 IDENTIFY WHAT APPEARS TO BE A 7.5 FOOT WIDE EITHER
 OPENING, SCREEN AND OR WINDOW ON BOTH SIDES OF THE
 AUDITORIUM SEPARATING THE AUDITORIUM AND CORRIDOR. FROM
 THE LIMITED PLANS THAT WERE ON FILE, IT APPEARS THE
 CORRIDOR CEILING IS AT 10 FT. ELEVATION, THE OPENINGS
 INTO THE AUDITORIUM ARE ASSUMED ALSO 10 FEET TALL, THE
 OPENINGS 7.5 FEET WIDE, HEIGHT UNKNOWN AND THE
 AUDITORIUM CEILING IS ASSUMED TO BE 12 FEET ABOVE THE
 FINISH FLOOR ELEVATION. IN THEORY WE ARE CONSIDERING
 THE LOBBY AS OPEN AND WILL DISPERSE SMOKE INTO THE
 CORRIDORS. THE ISSUE IS THERE ENOUGH OPENINGS FROM THE
 NON-RATED CORRIDOR INTO THE AUDITORIUM TO ALLOW THE
 SMOKE TO ESCAPE TO THE AUDITORIUM CEILING BUILDING DOWN
 ALLOWING ENOUGH TIME FOR THE OCCUPANTS TO LEAVE EITHER
 THROUGH THE FRONT LOBBY ENTRY OR DIRECTLY USING THE 2
 SIDE EXITS. THE 2 SIDE EXITS THAT LEAD FROM THE
 AUDITORIUM ARE SEPARATED BY ? THE MAJOR DIAGONAL
 DISTANCE APART CODE COMPLIANT FOR THAT ROOM.
 PLEASE PROVIDE A SIGNED AND SEALED ANALYSIS OF THE
 BUILDING, PROVIDING WHAT WOULD BE CONSIDERED ALTERNATE
 MATERIALS AND METHODS TO BE REVIEWED BY THE BUILDING
 OFFICIAL AS EQUAL TO THE CODE AT TIME THE BUILDING WAS
 BUILT.
  
 1ST ROUND OF COMMENTS. SHEET G003 THE LIFE SAFETY PLAN
 INDICATES THIS IS AN A3 OCCUPANCY, BUILDING TYPE III-B/
 NON-SPRINKLERED, BUILDING, WITH AN OCCUPANT LOAD OF
 278. THE PLANS FAILS TO SHOW FIRE RATED CORRIDORS 101,
 105 & 116 ( 2014 FBC-B TABLE 1018.1)WITH OPENING
 PROTECTIVES (DOOR & WINDOWS) IN ACCORDANCE WITH TABLE
 716.5.
  
 1B) THE MECHANICAL DUCTS THAT PENETRATE THE CORRIDOR
 WALLS LISTED ABOVE IN COMMENT 1A WILL NEED TO SHOW
 COMPLIANCE WITH FBC-B DUCTS AND AIR TRANSFER OPENINGS ,
 PENETRATIONS THROUGH FIRE RATED WALLS.
  
 1C) COMPLIED.
  
 1D) COMPLIED
  
 1E) SHEET G003 THE BOTTOM LEFT CORNER OF THE SHEET
 INDICATES IN A NOTE ROOMS 111 & 112 TO BE FIRE RATED,
 NOT LOCATED IN THE FLOOR PLAN? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED?
  
 2) SHEET A103 THE ROOF PLAN, SHEET KEY NOTES:
  
 2A)BUILDING PROVISO: A197 REPAIR ROTTING TRUSSES. A
 STRUCTURAL ENGINEER WHO WILL PROVIDE DETAILS ON HOW THE
 ROTTING TRUSSES ARE GOING TO BE REPAIRED. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B-D) COMPLIED.
  
 3) COMPLIED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-19 Cont ID  
Sent By jwitmer Date 2017-04-19 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2017-04-19 Time 10:04 Sent To  
Notes
2017-04-19 13:57:092014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040694
 ADD: 3000 N. AUSTRALIAN AVE.
 CONT: DOSDOURIAN ENTERPRISES
 TEL: 561-844-2990
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 19, 2017
 ACTION: DENIED
  
 1A) SHEET G003 THE LIFE SAFETY PLAN INDICATES THIS IS
 AN A3 OCCUPANCY, BUILDING TYPE III-B/ NON-SPRINKLERED,
 BUILDING, WITH AN OCCUPANT LOAD OF 278. THE PLANS FAILS
 TO SHOW FIRE RATED CORRIDORS 101, 105 & 116 ( 2014
 FBC-B TABLE 1018.1)WITH OPENING PROTECTIVES (DOOR &
 WINDOWS) IN ACCORDANCE WITH TABLE 716.5.
  
 1B) THE MECHANICAL DUCTS THAT PENETRATE THE CORRIDOR
 WALLS LISTED ABOVE IN COMMENT 1A WILL NEED TO SHOW
 COMPLIANCE WITH FBC-B DUCTS AND AIR TRANSFER OPENINGS ,
 PENETRATIONS THROUGH FIRE RATED WALLS.
  
 1C) ROOM 111 THE MAIN AUDITORIUM THE BACK ROW IS
 PARTIALLY BLOCKED, THE AISLE ACCESSWAY IS PARTIALLY
 BLOCKED BY THE END SEAT IN THE NEXT FORWARD ROW AT EACH
 END OF THE ROW. PLEASE REVIEW FBC-B 1028.9.1. EXCEPTION
 3 (2). THIRTY INCHES WHERE THE AISLE DOES NOT SERVES
 MORE THAN 14 SEATS.
  
 1D) ROOM 111 THE MAIN AUDITORIUM THE 4TH ROW FROM THE
 FRONT PLEASE DIMENSION THE CLEAR WITH OF THE AISLES, IT
 APPEARS THEY MAY NOT CONFORM TO: 2014 FBC-B 1028.9.1(4)
 FORTY-TWO INCHES (1067 MM) FOR LEVEL OR RAMPED AISLES
 HAVING SEATING ON BOTH SIDES.
  
 1E) SHEET G003 THE BOTTOM LEFT CORNER OF THE SHEET
 INDICATES IN A NOTE ROOMS 111 & 112 TO BE FIRE RATED,
 NOT LOCATED IN THE FLOOR PLAN? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED?
  
 2) SHEET A103 THE ROOF PLAN, SHEET KEY NOTES:
 2A) A197 REPAIR ROTTING TRUSSES. IS THERE A STRUCTURAL
 ENGINEER WHO WILL BE PROVIDING DETAILS ON HOW THE
 ROTTING TRUSSES ARE GOING TO BE REPAIRED? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) NOTE IN THE ROOF PLAN ITSELF, CONTRACTOR TO VERIFY
 ALL ROOF VENTS ARE CLOSED IN THE MAIN BUILDING ROOF?
 PLEASE PROVIDE HOW COMPLIANCE WITH FBC-B 1203.2 (1-3)
 IS GOING TO BE MET.
  
 2C) NOTE A198 IS RIDGE VENT IS FOR PORTICO ONLY. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THIS APPLICATION.
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 2D) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) PERMIT APPLICATION 17040695 LICENSE # CCC056366/
 FL00914 A ROOFING LICENSE IS WORKING OUT OF THE SCOPE
 OF THEIR LICENSE. REMOVE AND REPLACE EXISTING FINISHES
 AND BATHROOMS. I BELIEVE THIS IS A TYPO AND NEEDS TO BE
 CORRECTED. PLEASE PROVIDE THE AREAS OF THE ROOF THAT
 ARE TO BE REROOFED? PROVIDE THE SQUARE FOOTAGE OF
 ROOFING TO BE REPLACED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By jleahy Date 2017-06-08 Time 17:10 Rev Time 0.00
Received By jleahy Date 2017-06-08 Time 17:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-05-25 Cont ID  
Sent By jleahy Date 2017-05-25 Time 10:46 Rev Time 0.00
Received By jleahy Date 2017-05-25 Time 10:46 Sent To  
Notes
2017-05-25 10:49:45FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE THE FOLLOWING INFORMATION ON PLANS
  
  
 NEED FAULT CURRENT CALCULATION PER:
 110.24 AVAILABLE FAULT CURRENT.
 (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED
 AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT
 INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT
 CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
 CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE
 SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE
 MAXIMUM
 AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE
 EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO
 REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT
 CURRENT
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED
 IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET
 THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL
 HAVE AT LEAST ONE MANUAL CONTROL FOR THE LIGHTING
 SERVING THAT
 AREA. THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE
 AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES
 THE LIGHTS SERVED AND INDICATES THEIR STATUS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By rlecky Date 2017-04-18 Time 15:13 Rev Time 0.00
Received By rlecky Date 2017-04-18 Time 10:47 Sent To  
Notes
2017-04-18 15:16:59PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. INDICATED THE VOLTAGE FOR THE ELECTRICAL
 SERVICE. BOTH 240 VOLT AND 208 VOLTS ARE INDICATED ON
 THE DOCUMENTS. NEC 110.16, 110.22, 110.24
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR NEW
 ELECTRIC SERVICE AND PANEL BOARDS. NEC 110.9, 110.10
  
 INDICATE THE SIZE AND TYPE ELECTRICAL SERVICE
 CONDUCTORS PROPOSED FOR THE NEW SERVICE. NEC
 310.15(B)(16)
  
 SHOW ALL REQUIRED ACCESS AND SAFE WORKING CLEARANCES
 FOR THE ELECTRICAL SERVICE, MAIN DISCONNECTS AND PANEL
 BOARDS. NEC 110.26
  
 VERIFY THE DRINKING COOLER IS PROTECTED WITH AN
 ACCESSIBLE GFCI. NEC 422.52
  
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AT AN
 ACCESSIBLE LOCATION FOR SERVICING THE AIR CONDITIONING
 EQUIPMENT. NEC 210.63, 210.8(B)
  
 VERIFY THE RELOCATED WATER HEATER HAS AN ELECTRICAL
 DISCONNECT. NEC 422.31
  
 ALTERATIONS TO THE INTERIOR LIGHTING SYSTEM OF AN
 EXISTING BUILDING ARE SUBJECT TO THE REQUIREMENTS OF
 THE FLORIDA ENERGY CODE. THIS TYPICALLY INCLUDES THE
 USE OF OCCUPANCY SENSORS AND LIGHTING CONTROLS. THE
 PLAN NEEDS TO PROVIDE A SCOPE OF WORK THAT SPECIFICALLY
 ADDRESSES THE ENERGY CODE REQUIREMENTS. FBC EB 711, FBC
 C405
  
 ROBERT LECKY
 PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By pleduc Date 2017-06-08 Time   Rev Time 0.00
Received By pleduc Date 2017-06-07 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By pleduc Date 2017-05-15 Time   Rev Time 0.00
Received By pleduc Date 2017-05-15 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-26 Cont ID  
Sent By pleduc Date 2017-04-26 Time   Rev Time 0.00
Received By pleduc Date 2017-04-26 Time 11:44 Sent To  
Notes
2017-04-26 15:53:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS AN INCORRECT REFERENCE TO THE FIRE CODE
 INDICATED ON SHEET G 001.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE REVIEW AND INSURE COMPLIANCE.
  
  
  
  
 2) SHEET G 003 - ANY AND ALL WORK ON THE FIRE ALARM
 SYSTEM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2017-06-05 Time 11:44 Sent To  
Notes
2017-06-06 11:45:45C10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-25 Cont ID  
Sent By jleahy Date 2017-05-25 Time 10:50 Rev Time 0.00
Received By jleahy Date 2017-05-11 Time 14:02 Sent To  
Notes
2017-05-12 14:03:36C19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 13:48 Rev Time 0.00
Received By gjohnson Date 2017-04-17 Time 15:31 Sent To  
Notes
2017-04-17 15:32:47B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-04-19 Cont ID  
Sent By jwitmer Date 2017-04-19 Time 13:56 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-06-09 Cont ID  
Sent By ccole Date 2017-06-09 Time 08:44 Rev Time 0.00
Received By ccole Date 2017-06-09 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-19 Cont ID  
Sent By ccole Date 2017-05-19 Time 07:37 Rev Time 0.00
Received By ccole Date 2017-05-18 Time 16:49 Sent To  
Notes
2017-05-19 08:52:162ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040694
 5/19/17
  
 RESULTS: DENIED.
  
 1) IN HIS REPONSE TO COMMENTS FROM THE 1ST REVIEW, THE
 CONTRACTOR IS REQUESTING AN EXCEPTION TO MEETING THE
 REQUIREMENTS OF TABLE 403.3 FOR OCCUPANT DENSITY IN THE
 WORSHIP AUDITORIUM BASED ON HISTORICAL DATA. PLEASE
 MAKE THE REQUEST IN LETTER FORM, AND PROVIDE THE
 HISTORICAL DATA.
  
 2) REVIEW OF THE AC CALCULATIONS FOR THE TWO SYSTEMS
 AC- 1 & 2 SUPPLYING THE AUDITORIUM INDICATE THAT THE
 SENSIBLE AND LATENT HEAT GAIN IN BTUH'S FOR OCCUPANTS
 IS LESS THAN WHAT IS REQUIRED BY TABLE 6B ACCA MANUAL
 N. FOR EXAMPLE THE HEAT GAIN FOR A PERSON SEATED IN A
 PLACE OF WORSHIP- MAN, WOMAN, OR CHILD- IS AN AVERAGE
 OF 383 BTUH PER THE TABLE BUT THE CALCULATIONS ARE
  
 INDICATING 278 BTUH PER PERSON. THE RESULT INDICATES
 THE SYSTEMS MAY BE UNDERSIZED FOR COOLING.
  
 3) AS PREVIOUSLY NOTED IN THE 1ST REVIEW AN ERV IS
 REQUIRED FOR DOA-4 PER TABLE AND SECTION C403.2.6
 FBC-14 ENERGY CONSERVATION. PLEASE NOTE THE PLAN
 INDICATES 832 CFMS OF AIR BEING EXHAUSTED BY EF-1.
  
 4) PLEASE NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR
 DUCTS PENETRATING CORRIDOR WALLS IF IT DETERMINED THAT
 THE CORRIDOR WALLS WILL HAVE TO CHANGE FROM NON-RATED
 TO FIRE-RATED- PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 5) M-501: 2ND REQUEST TO PROVIDE THE WIND LOAD DESIGN
 CRITERIA USED TO ESTABLISH THE PRESSURES AND ANCHORING
 METHODS FOR THE AC CONDENSERS AND DOA UNIT- SECTION
 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-19 Cont ID  
Sent By ccole Date 2017-04-19 Time 17:00 Rev Time 0.00
Received By ccole Date 2017-04-19 Time 15:27 Sent To  
Notes
2017-04-19 17:41:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040694
 4/19/17
  
 1) SHEET M-001: THE OUTSIDE AIR CALCULATION FOR THE
 WORSHIP AUDITORIUM IS NOT IN COMPLIANCE WITH TABLE
 403.3. THE OCCUPANT DENSITY SHALL BE CALCULATED AT 120
 PERSONS AT 1000 S.F. FOR A TOTAL OF 400 PEOPLE. AT 5
 CFMS PER PERSON THE TOTAL REQUIRED O/A PER THE TABLE IS
 2200 CFMS. PLEASE CORRECT THE SCHEDULE ACCORDINGLY AND
 ALSO PROVIDE O/A CALCULATIONS FOR ALL OTHER OCCUPIED
 ROOMS AND SPACES SHOWN ON THE PLANS. THIS WOULD INCLUDE
 THE MEETING ROOMS, CONFERENCE ROOM, LOBBY, NURSING
 MOTHER'S ROOM, LITERATURE ROOM AND PLATFORM AREA.
  
 2) M-101: PLEASE IDENTIFY WITH LABELS ALL ROOMS AND
 SPACES ON THE PLAN.
  
 3) M-101: THE PLAN SHOWS INADEQUATE O/A TO THE WORSHIP
 AUDITORIUM AND MANY ROOMS SUCH AS THE LOBBY, PLATFORM,
 NURSING MOTHER'S, & LITERATURE ROOM ARE NOT BEING
 SUPPLIED WITH ANY O/A.
  
 4) M-101: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE RESTROOMS AND THE AUDITORIUM.
  
 5 ) M-001 & M-101: IT APPEARS BY THE CALCULATION AND
 THE PLAN THAT THE SUPPLY AND RETURN AIR CFMS FOR DOA-4
 UNIT ARE EQUAL. REFER TO TABLE C403.2.6 AND SECTION
 C403.2.6: AN ENERGY RECOVERY VENTILATOR IS REQUIRED.
  
 6 ) M-001 & M-101: IT APPEARS THAT SOME OF THE RETURN
 GRILLS ARE MISLABELED AS DIFFUSERS I.E. GRILLS LABELED
 E & G.
  
 7) M-001 & M-101: DUCT SMOKE DETECTORS ARE REQUIRED IN
 THE RETURN AIR SYSTEMS OF AC-1 & 2, UNLESS
 MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS ARE
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR-
 606.2.1.
  
 8) M-501: PROVIDE THE WIND LOAD DESIGN CRITERIA USED TO
 ESTABLISH THE ANCHORING METHOD FOR THE AC CONDENSERS
 AND DOA UNIT- SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2017-06-12 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 14:04 Sent To  
Notes
2017-05-23 14:21:561ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS FOR ACCESSIBLE ELEMENTS IN
 BATHROOMS SHOW COMPLIANCE WITH FBC ACC 603,604, 605,
 606
  
 2. PROVIDE RISER DIAGRAM FOR NEW WATER PIPING FOR
 RELOCATION OF WATER HEATER. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 09:00 Rev Time 0.00
Received By gjohnson Date 2017-04-28 Time 07:30 Sent To  
Notes
2017-04-28 09:02:011ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE COMPLY WITH ALL OTHER TRADE COMMENTS. WPB
 AMEND TO FBC 107.2.1
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2017-05-22 Cont ID  
Sent By skennedy Date 2017-05-22 Time 12:31 Rev Time 0.00
Received By skennedy Date 2017-05-22 Time 12:31 Sent To  
Notes
2017-05-22 12:32:16THE ROOFING WAS REMOVE AND SUBMITTED AS A SEPARATE
 PERMIT. THE VALUE WAS ADJUSTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-05-19 Cont ID  
Sent By jwitmer Date 2017-05-19 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2017-05-19 Time 16:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-04-19 Time   Rev Time 0.00
Received By   Date 2017-04-19 Time   Sent To  
Notes
2017-05-02 09:25:201A) NOTE A198 IS RIDGE VENT IS FOR PORTICO ONLY. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THIS APPLICATION.
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 1B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  