| 2017-04-15 06:07:48 | 1) INDICATE ON THE PLAN IF ANY TUNNELLING WILL BE |
| | REQUIRED UNDER THE STRUCTURE TO ACCESS THE EXISTING |
| | UNDERGROUND PIPE.IF SO, DETAILS AND BACKFILLING |
| | PROCEDURES SHALL BE SUBMITTED THAT CLEARLY SHOW HOW THE |
| | STRUCTURAL INTEGRITY OF THE CONCRETE SLAB WILL BE |
| | MAINTAINED DURING EXCAVATION AND BACKFILLING. |
| | STRUCTURAL FOAM IS NOT PERMITTED BELOW GROUND PER THE |
| | FLORIDA BUILDING CODE, RESIDENTIAL, SECTION 318 AND THE |
| | FLORIDA BUILDING CODE, BUILDING, SECTION 2603.8. |
| | 2) IF THE EXISTING SLAB IS GOING TO BE CUT AND SOIL |
| | REMOVED AND REPLACED, SUBMIT A SLAB REPAIR DETAIL FOR |
| | REVIEW. THE SLAB DETAIL SHALL BE SIGNED AND SEALED BY A |
| | DESIGN PROFESSIONAL REGISTERED IN THE STATE OF FLORIDA |
| | PER FL. STATUTES 471 & 481.IF SOIL IS GOING TO BE |
| | REMOVED AND REPLACED, THE REPLACED SOIL SHALL BE |
| | TREATED WITH A TERMITICIDE IN ACCORDANCE WITH 2014 FBC |
| | SEC.1816.1. |
| | 3) SUBMIT MANUF. SPCECIFICATIONS FOR THE TANKLESS WATER |
| | HEATERS. WPB AMEND TO FBC SEC. 107.2.1. |
| | 4) INDICATE ON THE PLANS IF THE SHOWER VALVES ARE BEING |
| | REPLACED. WPB AMEND TO FBC SEC. 107.2.1. |
| | 5) THIS BUILDING HAS MULTIPE UNITS. WHAT ARE THE UNIT |
| | NUMBERS WHERE THIS WORK IS BEING DONE? THE SUBMITTED |
| | DRAWING APPEARS TO BE FOR 2 SEPARATE DWELLING UNITS. IF |
| | SO, THERE IS A WATER CLOSET AND SHOWER MISSING ON THE |
| | SANITARY RISER ON THE FIRST FLOOR AND A SHOWER IS |
| | MISSING ON THE FIRST FLOOR WATER RISER. CLARIFY. |
| | 6) SUBMIT DETAILS AS TO HOW THE PIPE PENETRATIONS |
| | THROUGH THE FLOOR WILL BE FIRE SAFED TO ENSURE THE FIRE |
| | RATING OF THE FLOOR ( IF RATED). INDICATE IF THE FLOOR |
| | BETWEEN THE UNITS IS FIRE RATED AND THE FIRE RATING OF |
| | THE FLOOR. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC |
| | SEC.714. |
| | 7) INDICATE THE EXTENT OF WALL REMOVAL THAT WILL BE |
| | ASSOCIATED WITH THIS REPAIR AND HOW THIS WORK WILL BE |
| | REPLACED.WPB AMEND TO FBC SEC. 107.2.1. |
| | 8) SUBMIT A FLOOR PLAN SHOWING WHERE THE WORK WILL BE |
| | DONE IN THE UNITS.WPB AMEND TO FBC SEC. 107.2.1. |
| | 9) HOW IS THE INTEGRITY OF THE EXISTING UNDERGROUND |
| | BUILDING DRAIN LINE AND SEWER BEING DETERMINED AS BEING |
| | IN GOOD WORKING CONDITION? IF THE INTERIOR DRAIN PIPING |
| | NEEDS TO BE REPLACED THE EXISTING UNDERGROUND MAY ALSO |
| | NEED TO BE REPLACED. CLARIFY. |
| | 10) AS DRAWN, THE SANITARY RISER SHOWS A KITCHEN SINK |
| | AND WASHING MACHINE ON A WET VENT WHICH IS NOT |
| | PERMITTED PER 2014 FBC-PLUMBING SEC.912.1. ONLY |
| | FIXTURES IN THE BATHROOM GROUPMAY DISCHARGE INTO A WET |
| | VENT. |
| | 11) AS DRAWN, THE SHOWER FOR THE 2ND FLOOR IS NOT |
| | VENTED. THE SHOWER FIXTURE DRAIN SHALL CONNECT TO THE |
| | STACK OR BE INDIVIDUALLY VENTED. 2014 FBC-PLUMBING |
| | SEC.901.2. |
| | 12) CLEANOUTS ARE REQUIRED AT THE BASE OF THE STACKS. |
| | FBC-PLUMBING SEC. 708.3.4. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |