| 2017-05-03 09:33:24 | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | |
| | E3405.4 LOCATION OF WORKING SPACES AND EQUIPMENT. |
| | REQUIRED WORKING SPACE SHALL NOT BE DESIGNATED FOR |
| | STORAGE. PANELBOARDS AND OVERCURRENT PROTECTION DEVICES |
| | SHALL NOT BE LOCATED IN CLOTHES CLOSETS, IN BATHROOMS, |
| | OR OVER THE STEPS OF A STAIRWAY. |
| | |
| | E3706.2 PANELBOARD CIRCUIT IDENTIFICATION. |
| | ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY |
| | IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT |
| | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF |
| | THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. |
| | CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT |
| | DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | AT LEAST ONE RECEPTACLE OUTLET THAT IS ACCESSIBLE WHILE |
| | STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE. BALCONIES, |
| | DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE OF |
| | THE DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE |
| | OUTLET INSTALLED WITHIN THE PERIMETER OF THE BALCONY, |
| | DECK, OR PORCH. THE RECEPTACLE SHALL BE LOCATED NOT |
| | MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY, |
| | DECK, OR PORCH SURFACE. |
| | |
| | R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| | MM) OF EACH ROOM USED FOR SLEEPING PURPOSES |
| | . |
| | 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY |
| | HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS |
| | SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE |
| | FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE |
| | FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY |
| | EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING |
| | DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED |
| | LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND |
| | TYPE OF CONDUCTORS TO BE USED. |
| | |