Plan Review Details - Permit 17040626
Plan Review Stops For Permit 17040626
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 13:50 Rev Time 0.00
Received By cthroop Date 2017-07-10 Time 13:38 Sent To M
Notes
2017-07-11 13:58:28NO NOTES
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By cthroop Date 2017-05-04 Time 16:40 Rev Time 0.00
Received By cthroop Date 2017-05-04 Time 16:07 Sent To M
Notes
2017-05-04 16:46:51BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN WITH BUILDING SETBACKS.
 2. CMU INFILL DETAIL DOES NOT SHOW VERTICAL
 REINFORCEMSNT. VERTICAL REINFORCEMENT IS REQUIRED AT
 ALL OPENINGS AND CORNERS.
 3. PROVIDE DESIGN WIND LOADS FOR WINDOW AND DOOR
 OPENINGS.
 4. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND
 DOORS.
 5. 4 X FEE WILL BE ASSESSED FOR WORK WITHOUT PERMIT.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-05 Cont ID  
Sent By jleahy Date 2017-07-05 Time 11:05 Rev Time 0.00
Received By jleahy Date 2017-07-05 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By jleahy Date 2017-05-03 Time 09:31 Rev Time 0.00
Received By jleahy Date 2017-05-03 Time 09:31 Sent To  
Notes
2017-05-03 09:33:24JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 E3405.4 LOCATION OF WORKING SPACES AND EQUIPMENT.
 REQUIRED WORKING SPACE SHALL NOT BE DESIGNATED FOR
 STORAGE. PANELBOARDS AND OVERCURRENT PROTECTION DEVICES
 SHALL NOT BE LOCATED IN CLOTHES CLOSETS, IN BATHROOMS,
 OR OVER THE STEPS OF A STAIRWAY.
  
 E3706.2 PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF
 THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR.
 CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT
 DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
  
 E3901.7 OUTDOOR OUTLETS.
 AT LEAST ONE RECEPTACLE OUTLET THAT IS ACCESSIBLE WHILE
 STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE. BALCONIES,
 DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE OF
 THE DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE
 OUTLET INSTALLED WITHIN THE PERIMETER OF THE BALCONY,
 DECK, OR PORCH. THE RECEPTACLE SHALL BE LOCATED NOT
 MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY,
 DECK, OR PORCH SURFACE.
  
 R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES
 .
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE
 FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE
 FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY
 EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING
 DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED
 LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND
 TYPE OF CONDUCTORS TO BE USED.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-05-03 Cont ID  
Sent By gjohnson Date 2017-05-03 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 16:18 Sent To  
Notes
2017-05-03 16:19:48GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By fmittner Date 2017-06-29 Time 16:58 Rev Time 0.00
Received By fmittner Date 2017-06-29 Time 16:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By destabro Date 2017-04-21 Time 14:59 Rev Time 0.00
Received By destabro Date 2017-04-21 Time 14:59 Sent To Z
Notes
2017-04-21 15:03:184/21/2017 - APPLICANT SHOULD SUBMIT A COA FOR THE
 PROPOSED WORK, WHICH ENTAILS REMODELING A GUEST HOUSE
 (BUILT. CA.1955, CHANGED FROM A GARAGE TO A HOUSE IN
 1967). PROPOSED CHANGES INCLUDE CLOSING WINDOW SPACES
 AND REPLACEMENT WINDOW AND DOOR PRODUCTS. NO PRODUCT
 APPROVALS PROVIDED. PLEASE DIRECT QUESTIONS TO DESIREE
 ESTABROOK, HISTORIC PRESERVATION PLANNER, AT
 561.822.1428.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 11:13 Rev Time 0.00
Received By cthroop Date 2017-06-15 Time 11:44 Sent To  
Notes
2017-06-16 11:44:50R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-09 Cont ID  
Sent By hmoser Date 2017-05-09 Time 11:38 Rev Time 0.00
Received By hmoser Date 2017-04-13 Time 15:54 Sent To  
Notes
2017-04-14 15:54:52R32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-19 Cont ID  
Sent By cthroop Date 2017-07-20 Time 11:13 Rev Time 0.00
Received By hmoser Date 2017-07-19 Time 10:22 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-09 Cont ID  
Sent By hmoser Date 2017-05-09 Time 11:38 Rev Time 0.00
Received By hmoser Date 2017-05-09 Time 11:06 Sent To  
Notes
2017-05-09 11:35:34PLAN DENIED
 ADDRESS ON PLAN AND ADDRESS ON APPLICATION
 DO NOT MATCH APPLICATION 629 FLAMINGO,
 PLAN IS 1918 GEORGIA.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-07 Cont ID  
Sent By gjohnson Date 2017-07-07 Time 13:28 Rev Time 0.00
Received By gjohnson Date 2017-07-07 Time 13:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-03 Cont ID  
Sent By gjohnson Date 2017-05-03 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 14:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By fmittner Date 2017-06-29 Time 16:59 Rev Time 0.00
Received By fmittner Date 2017-06-29 Time 16:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By destabro Date 2017-04-21 Time 15:18 Rev Time 0.00
Received By destabro Date 2017-04-21 Time 15:18 Sent To B
Notes
2017-04-21 15:22:184/21/2017 - PLEASE SUBMIT A SITE SURVEY TO SHOW THAT
 THE PROPOSED A/C UNIT IS EITHER ON AN EXISTING CONCRETE
 PAD AND/OR DOES NOT EXTEND MORE THAN FOUR FEET INTO THE
 REAR SETBACK. DLE