Plan Review Details - Permit 17040539
Plan Review Stops For Permit 17040539
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By rmcdouga Date 2017-05-05 Time 18:11 Rev Time 0.00
Received By rmcdouga Date 2017-05-05 Time 17:43 Sent To  
Notes
2017-05-05 18:11:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) INDICATE THE (8) WINDOWS THAT ARE BEING REPLACED ON
 THE PLANS. SPECIFY THE SIZE AND TYPE OF THE WINDOWS
 THAT ARE BEING REPLACED. FBC 107.2.1
  
 2) SHOW COMPLIANCE WITH FBC-R310.1 EMERGENCY ESCAPE AND
 RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING
 A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES
 AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS
 PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD
 ENCLOSURE SHALL COMPLY WITH SECTION R310.3. THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY
 ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT
 BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED
 WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2.
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN
 DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT
 OPENS TO A PUBLIC WAY.
 FBC-R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
 FBC-R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
 FBC-R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
 3) SHOW COMPLIANCE WITH FBC - R301.2.1.2 PROTECTION OF
 OPENINGS.
 GLAZED OPENINGS IN BUILDINGS LOCATED IN WINDBORNE
 DEBRIS REGIONS SHALL BE PROTECTED FROM WINDBORNE
 DEBRIS. GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST
 OF ASTM E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD
 12, TAS 201, 202 AND 203 OR AAMA 506, AS APPLICABLE.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH TYPE OF WINDOW
 AND THE STRUCTURAL MULLIONS.
  
 5) IF STORM PLANELS ARE USED FOR IMPACT PROTECTION.
 THEN SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THEM
 ALONG WITH A KEY PLAN AND AN INSTALLATION SCHEDULE. FBC
 107.3.4 AND FBC 107.2.1
  
 6) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-27 Cont ID  
Sent By jleahy Date 2017-04-27 Time 10:38 Rev Time 0.00
Received By jleahy Date 2017-04-27 Time 10:38 Sent To  
Notes
2017-04-27 10:39:01KITCHEN ELECTRIC ONLY NO OTHER WORK SHOWN ON PLANS
 JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By rmcdouga Date 2017-05-05 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2017-04-12 Time 09:42 Sent To  
Notes
2017-04-13 09:43:07R25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By rmcdouga Date 2017-05-05 Time 17:35 Rev Time 0.00
Received By rmcdouga Date 2017-05-05 Time 17:35 Sent To  
Notes
2017-05-05 17:43:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CLARIFY WHAT TYPE OF A/C UNITS WILL BE INSTALLED.
 SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE A/CS.
 FBC 107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-02 Cont ID  
Sent By gjohnson Date 2017-05-02 Time 11:10 Rev Time 0.00
Received By gjohnson Date 2017-05-02 Time 10:01 Sent To  
Notes
***NONE***