Plan Review Details - Permit 17040497
Plan Review Stops For Permit 17040497
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-19 Cont ID  
Sent By jleahy Date 2017-04-19 Time 14:56 Rev Time 0.00
Received By jleahy Date 2017-04-19 Time 14:56 Sent To I
Notes
2017-04-13 10:37:45SENT TO FIRE FIRST

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-14 Cont ID  
Sent By pleduc Date 2017-04-17 Time   Rev Time 0.00
Received By pleduc Date 2017-04-13 Time 17:01 Sent To E
Notes
2017-04-14 15:12:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION AND TESTING SHALL COMPLY WITH
 REQUIREMENTS OF NFPA 72, CHAPTER 24 AND ALL ASSOCIATED
 CODE REFERENCES.
  
  
 2) PROVIDE A SYSTEM COMMISSIONING TEST REPORT BY
 ACCEPTABLE INDUSTRY STANDARDS OF YOUR CHOICE.
  
 14.4.12.1.2 SYSTEM COMMISSIONING TESTING. SYSTEM
 COMMISSIONING TESTS SHALL COMPLY WITH THE FOLLOWING:
 (1) THE BUILDING OWNER SHALL BE RESPONSIBLE FOR
 ENSURING THAT A COMMISSIONING TEST OF THE PUBLIC SAFETY
 RADIO ENHANCEMENT SYSTEM OCCURS PRIOR TO FINAL
 ACCEPTANCE TESTING WITH THE AUTHORITY HAVING
 JURISDICTION.
 (2) THE COMMISSIONING TEST SHALL ENSURE THAT TWO-WAY
 COVERAGE ON EACH FLOOR OF THE BUILDING MEETS THE
 MINIMUM COVERAGE REQUIREMENTS OF 24.5.2.2.1 AND
 24.5.2.2.2.
 (3) TESTS SHALL BE MADE USING THE FREQUENCIES ASSIGNED
 TO THE JURISDICTION.
 (4) TESTING SHALL BE COORDINATED WITH THE AUTHORITY
 HAVING JURISDICTION TO ENSURE NO UNDUE INTERFERENCE TO
 ANY PUBLIC SAFETY OPERATIONS.
 (5) ALL TESTING SHALL BE DONE ON FREQUENCIES AUTHORIZED
 BY THE FCC.
  
 3) FIRE INSPECTORS WILL WALK THE BUILDING AND CONDUCT
 PORTABLE RADIO TEST AS PART OF THE FINAL TESTING.
  
  
  
 4) THE SYSTEM SHALL HAVE IT'S OWN DEDICATED PANEL IN
 THE COMMAND ROOM.
  
 24.5.2.6.2* DEDICATED PANEL. A DEDICATED MONITORING
 PANEL BE PROVIDED WITHIN THE EMERGENCY COMMAND CENTER
 TO ANNUNCIATE THE STATUS OF ALL SIGNAL BOOSTER
 LOCATIONS. THE MONITORING PANEL SHALL PROVIDE VISUAL
 AND LABELED INDICATION OF THE FOLLOWING FOR EACH SIGNAL
 BOOSTER:
 (1) NORMAL AC POWER
 (2) SIGNAL BOOSTER TROUBLE
 (3) LOSS OF NORMAL AC POWER
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-19 Cont ID  
Sent By jleahy Date 2017-04-19 Time 16:50 Rev Time 0.00
Received By jleahy Date 2017-04-11 Time 13:42 Sent To  
Notes
2017-04-12 13:42:38ROUTED TO ELECTRICAL INBOX