Plan Review Details - Permit 17040472
Plan Review Stops For Permit 17040472
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By shill Date 2017-05-24 Time 07:07 Rev Time 0.00
Received By shill Date 2017-05-24 Time 06:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-04-14 Cont ID  
Sent By shill Date 2017-04-14 Time 17:52 Rev Time 0.00
Received By shill Date 2017-04-14 Time 17:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-30 Cont ID  
Sent By jpearson Date 2017-05-30 Time 12:43 Rev Time 0.00
Received By jpearson Date 2017-05-30 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-13 Cont ID  
Sent By rlecky Date 2017-04-13 Time 12:38 Rev Time 0.00
Received By rlecky Date 2017-04-13 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 12:23 Rev Time 0.00
Received By wjolin Date 2017-05-31 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-05-09 Cont ID  
Sent By wjolin Date 2017-05-09 Time 14:48 Rev Time 0.00
Received By wjolin Date 2017-05-09 Time 14:41 Sent To  
Notes
2017-05-09 14:48:062100 45TH STREET SUITE B-28
 PERMIT #17040472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ORIGINAL PLAN REVIEW COMMENTS NOT ADDRESSED:
  
 PER NFPA 101 - THE LIFE SAFETY CODE SECTION 8.7, ANY
 AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER THAN
 NORMAL TO THE GENERAL OCCUPANCY (MERCANTILE) OF THE
 BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER OR BE PROTECTED WITH
 AN AUTOMATIC SPRINKLER SYSTEM. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES.
  
 AN ILLUMINATED EXIT SIGN IS NEEDED ABOVE NEW DOOR #001.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By wjolin Date 2017-04-13 Time 10:55 Rev Time 0.00
Received By wjolin Date 2017-04-13 Time 10:16 Sent To  
Notes
2017-04-13 10:38:112100 45TH STREET SUITE B-28
 PERMIT #17040472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 101 - THE LIFE SAFETY CODE SECTION 8.7, ANY
 AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER THAN
 NORMAL TO THE GENERAL OCCUPANCY (MERCANTILE) OF THE
 BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER OR BE PROTECTED WITH
 AN AUTOMATIC SPRINKLER SYSTEM. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES.
  
 AN ILLUMINATED EXIT SIGN IS NEEDED ABOVE NEW DOOR #001.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 12:23 Rev Time 0.00
Received By wjolin Date 2017-05-18 Time 10:14 Sent To  
Notes
2017-05-19 14:44:37B12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-17 Cont ID  
Sent By gjohnson Date 2017-05-17 Time 13:03 Rev Time 0.00
Received By gjohnson Date 2017-05-05 Time 16:18 Sent To  
Notes
2017-05-08 16:19:07B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 09:15 Rev Time 0.00
Received By gjohnson Date 2017-04-11 Time 16:35 Sent To  
Notes
2017-04-12 16:35:41B12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-31 Cont ID  
Sent By ccole Date 2017-05-26 Time 10:08 Rev Time 0.00
Received By ccole Date 2017-05-26 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-10 Cont ID  
Sent By ccole Date 2017-05-10 Time 09:18 Rev Time 0.00
Received By ccole Date 2017-05-10 Time 09:18 Sent To  
Notes
2017-05-10 09:19:432ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040472
 5/10/17
  
 RESULTS: DENIED.
  
 1) THE REQUESTED AC CALCULATIONS AND CORRECTED
 MECHANICAL PLANS WERE NOT SUBMITTED- SEE 1ST REVIEW
 COMMENTS REPRINTED BELOW.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040472
 4/14/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) A DUCT SMOKE DETECOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF AHU-1 UNLESS MANUFACTURER'S SPECIFICATIONS
 INDICATE THE UNIT IS INCAPABLE OF PRODUCING OVER 2000
 CFM'S OF SUPPLY AIR.
  
 3) M002: CORRECT THE SYSTEM IDENTIFICATION IN THE O/A
 SCHEDULE FROM RTU-1 TO AHU-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-14 Cont ID  
Sent By ccole Date 2017-04-14 Time 12:41 Rev Time 0.00
Received By ccole Date 2017-04-14 Time 12:41 Sent To  
Notes
2017-04-14 12:52:091ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040472
 4/14/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) A DUCT SMOKE DETECOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF AHU-1 UNLESS MANUFACTURER'S SPECIFICATIONS
 INDICATE THE UNIT IS INCAPABLE OF PRODUCING OVER 2000
 CFM'S OF SUPPLY AIR.
  
 3) M002: CORRECT THE SYSTEM IDENTIFICATION IN THE O/A
 SCHEDULE FROM RTU-1 TO AHU-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 12:00 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-17 Cont ID  
Sent By gjohnson Date 2017-05-17 Time 13:03 Rev Time 0.00
Received By gjohnson Date 2017-05-17 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 08:55 Sent To  
Notes
2017-04-27 09:15:161ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS FOR ACCESSIBLE BATHROOM.
 PER WPB AMEND TO FBC 107.2.1
  
 2. SHOW CLEAR FLOOR SPACE FOR LAVATORY AND TOILET. PER
 FBC ACC 604.3.1 AND 606.2
  
 3. SHOW COMPLIANCE WITH HEIGHT OF THE WATER CLOSET. PER
 FBC ACC 604.4
  
 4. THE TOILET PAPER DISPENSER SHALL BE 7"- 9" FROM THE
 FRONT OF THE TOILET THE PLAN SHOWS 4"- 9" PLEASE
 CLARIFY. PER FBC ACC 604.7
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC ACC 416.5
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  