Plan Review Details - Permit 17040463
Plan Review Stops For Permit 17040463
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-01 Cont ID  
Sent By jleahy Date 2017-05-01 Time 14:30 Rev Time 0.00
Received By jleahy Date 2017-05-01 Time 14:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-20 Cont ID  
Sent By jleahy Date 2017-04-20 Time 13:04 Rev Time 0.00
Received By jleahy Date 2017-04-20 Time 13:03 Sent To  
Notes
2017-04-20 13:08:22NEED LISTING FOR CABLES AND EQUIPMENT JLEAHY 110.3
2017-04-13 13:53:58SENT TO FIRE FIRST

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-01 Cont ID  
Sent By pleduc Date 2017-05-01 Time   Rev Time 0.00
Received By pleduc Date 2017-05-01 Time 09:11 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-14 Cont ID  
Sent By pleduc Date 2017-04-14 Time   Rev Time 0.00
Received By pleduc Date 2017-04-13 Time 17:01 Sent To E
Notes
2017-04-14 10:12:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 CONDUCT THE NECESSARY REVIEW FOR FIRE CODE COMPLAINCE.
  
  
  
  
 2) THERE IS NO TITLE PAGE, INCLUDING NO BUSINESS NAME
 OR ADDRESS, AND NO PROJECT NAME OR ADDRESS ON THE PLAN
 SHEETS.
  
 ADDITIONALLY, THE PLAN SHEETS WERE NO BOUND TOGETHER
 KEEPING THEM ORGANIZED AND AVOIDING MISPLACEMENT OR
 BEING LOST.
  
 PLEASE PROVIDE.
  
  
  
  
 3) THERE IS NO INDICATIONS OF ANY NFPA FIRE CODE
 COMPLIANCE REFERENCES.
  
 PLEASE PROVIDE ALL APPLICABLE NFPA FIRE CODE REFERENCES
 AND ENSURE COMPLIANCE.
  
  
  
 4) THERE IS NO SCOPE OF WORK. IS THIS INSTALLATION
 RELATED TO THE FIRE ALARM SYSTEM? IS ANY WORK NEEDED ON
 THE FIRE ALARM SYSTEM SIDE? ANY FIRE ALARM WWORK SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK AND APPLICABLE
 NOTE OF FIRE ALARM WORK.
  
  
  
 5) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS.
  
 PLEASE PROVIDE APPLICABLE SPEC SHEETS.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-01 Cont ID  
Sent By cpuell Date 2017-05-01 Time 16:15 Rev Time 0.00
Received By cpuell Date 2017-04-27 Time 13:08 Sent To  
Notes
2017-04-28 13:08:18RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-28 Cont ID  
Sent By lmarchan Date 2017-04-28 Time 13:06 Rev Time 0.00
Received By lmarchan Date 2017-04-11 Time 12:42 Sent To  
Notes
2017-04-12 12:43:05ROUTED TO ELECTRICAL INBOX