| 2017-04-15 04:44:41 | 1) PLANS DONE IN PENCIL ARE UNACCEPTABLE. SUBMIT TWO |
| | COPIES OF THE PLAN THAT ARE DONE IN AN UNERASABLE |
| | FORMAT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUAL FOR THE LIFT |
| | STATION. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) A CHECK VALVE AND FULL OPEN VALVE LOCATED ON THE |
| | DISCHARGE SIDE OF THE CHECK VALVE IS REQUIRED PER 2014 |
| | FBC-PLUMBING SEC.712.2. ACCESS SHALL BE PROVIDED TO |
| | SUCH VALVES. |
| | 4) THE SUMP DESIGN SHALL COMPLY WITH 2014 FBC- PLUMBING |
| | SEC.712.3. |
| | 5) THE LIFT STATION DISCHARGE CONNECTION TO THE 4" |
| | SEWER SHALL COMPLY WITH 2014 FBC - PLUMBING |
| | SEC.712.3.5. |
| | 6) INDICATE ON THE PLAN IF ANY TUNNELING WILL BE |
| | REQUIRED UNDER THE EXISTING STRUCTURE IN ORDER TO WORK |
| | ON THE EXISTING KITCHEN DRAIN. IF SO, DETAILS AND |
| | BACKFILLING PROCEDURES SHALL BE SUBMITTED THAT CLEARLY |
| | SHOW HOW THE STRUCTURAL INTEGRITY OF THE CONCRETE SLAB |
| | WILL BE MAINTAINED DURING EXCAVATION AND BACKFILLING. |
| | STRUCTURAL FOAM IS NOT PERMITTED BELOW GROUND PER THE |
| | FLORIDA BUILDING CODE, RESIDENTIAL, SECTION 318 AND THE |
| | FLORIDA BUILDING CODE, BUILDING, SECTION 2603.8. |
| | 7) A CLEANOUT IS REQUIRED IN THE 2 INCH LINE PER 2014 |
| | FBC- PLUMBING SEC.708.3.2. |
| | 8) THE LIFT STATION WILL REQUIRE ELECTRIC. WHAT |
| | PROVISIONS ARE BEING DONE TO PROVIDE ELECTRIC TO THE |
| | UNIT? INDICATE ON THE PLANS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |