Plan Review Details - Permit 17040452
Plan Review Stops For Permit 17040452
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-14 Cont ID  
Sent By jgomez Date 2017-04-14 Time 14:35 Rev Time 0.00
Received By jgomez Date 2017-04-14 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By jgomez Date 2017-04-13 Time 17:47 Rev Time 0.00
Received By jgomez Date 2017-04-13 Time 17:01 Sent To  
Notes
2017-04-13 17:58:47RESIDENTIAL (R3) RE-ROOF REVISION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- IF THE MODIFIED BITUMEN ROOFING SYSTEM WAS REVISED
 FOR NOA 14-0529.02, THEN NEED TO PROVIDE REVISED RAS
 117 CALCULATIONS TO REFLECT THE NEW SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED (2 COPIES) REVISED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 TO
 MEET THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-04-12 Cont ID  
Sent By destabro Date 2017-04-12 Time 13:29 Rev Time 0.00
Received By destabro Date 2017-04-12 Time 13:29 Sent To B
Notes
2017-04-11 16:03:59ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By jgomez Date 2017-04-14 Time 14:35 Rev Time 0.00
Received By jgomez Date 2017-04-14 Time 14:32 Sent To  
Notes
2017-04-14 14:32:38MET WITH CONTRACTOR TO GO OVER PRODUCT APPROVALS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-13 Cont ID  
Sent By jgomez Date 2017-04-13 Time 17:58 Rev Time 0.00
Received By jgomez Date 2017-04-11 Time 13:46 Sent To  
Notes
2017-04-11 13:46:55REVISION ROUTED TO DESTABRO VIA ZONING INBOX