Plan Review Details - Permit 17040372
Plan Review Stops For Permit 17040372
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-26 Cont ID  
Sent By tklarge Date 2017-04-26 Time 11:22 Rev Time 0.00
Received By tklarge Date 2017-04-26 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 05:34 Rev Time 0.00
Received By tklarge Date 2017-04-19 Time 11:17 Sent To  
Notes
2017-04-20 11:17:52RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-15 Cont ID  
Sent By tklarge Date 2017-04-15 Time 04:21 Rev Time 0.00
Received By tklarge Date 2017-04-10 Time 13:31 Sent To  
Notes
2017-04-11 13:31:40PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-04-26 Cont ID  
Sent By tklarge Date 2017-04-26 Time 11:22 Rev Time 0.00
Received By tklarge Date 2017-04-26 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-21 Cont ID  
Sent By tklarge Date 2017-04-21 Time 05:33 Rev Time 0.00
Received By tklarge Date 2017-04-21 Time 05:24 Sent To  
Notes
2017-04-21 05:33:541) SUBMIT SIZING CALCULATIONS FOR THE SIZE OF THE
 GREASE TRAP BEING INSTALLED. 2014 FBC-PLUMBING SEC.
 1003.2. CALCULATIONS SHALL BE DONE IN ACCORDANCE WITH
 2014 FBC-PLUMBING SEC.1003.3.4. 2ND REQUEST.
 YOU HAVE SHOWN THE GPM OF EACH SINK COMPARTMENT BUT
 THAT IS NOT THE SIZING CALCULATION REQUESTED. SUBMIT
 CALCULATIONS THAT CONFIRM HOW THE GPM WAS DETERMINED
 FOR EACH COMPARTMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-15 Cont ID  
Sent By tklarge Date 2017-04-15 Time 04:21 Rev Time 0.00
Received By tklarge Date 2017-04-15 Time 04:07 Sent To  
Notes
2017-04-15 04:21:221) SHOW ALL PIPE SIZES OF THE DRAIN LINES ON THE
 PLUMBING DRAWINGS.
 2) SUBMIT SIZING CALCULATIONS FOR THE SIZE OF THE
 GREASE TRAP BEING INSTALLED. 2014 FBC-PLUMBING SEC.
 1003.2. CALCULATIONS SHALL BE DONE IN ACCORDANCE WITH
 2014 FBC-PLUMBING SEC.1003.3.4.
 3) THE CAPACITY OF THE GREASE TRAP SHALL COMPLY WITH
 2014 FBC-PLUMBING TABLE 1003.3..4.1.
 4) INDICATE THE SIZE OF THE UNIT ON BOTH COPIES OF THE
 SPECIFICATIONS FROM ZURN.
 5) PLACE THE ADDRESS & UNIT NUMBER OF THE SPACE ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  