Plan Review Details - Permit 17040361
Plan Review Stops For Permit 17040361
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-30 Cont ID  
Sent By cthroop Date 2017-05-30 Time 12:21 Rev Time 0.00
Received By cthroop Date 2017-05-30 Time 10:43 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By fmittner Date 2017-05-03 Time 13:50 Rev Time 0.00
Received By cthroop Date 2017-05-03 Time 11:44 Sent To  
Notes
2017-05-03 13:53:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR CASEMENT WINDOWS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-30 Cont ID  
Sent By jleahy Date 2017-05-30 Time 15:02 Rev Time 0.00
Received By jleahy Date 2017-05-30 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By jleahy Date 2017-05-02 Time 12:20 Rev Time 0.00
Received By jleahy Date 2017-05-02 Time 12:20 Sent To  
Notes
2017-05-02 12:29:55JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SERVICE MAINS TO BE GROUPED 230.72, FBCRE3601.7
  
 FBCRE3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A
 VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN
 OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS
 ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A
 WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT
 INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS
 WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS.
 FRONT OF "A" AND "B"
  
 UNIT "A"
 SMOKE ALARM AT BOTTOM OF THE STAIRS
 OUTLET ON FRONT OUTSIDE
 OUTLET SPACING PER CODE
  
 UNIT "B"
 OUTLET AT FRONT OUTSIDE
 COUNTER OUTLET BY FRIDGE TO BE GFCI PROTECTED
 OUTLET SPACING PER CODE
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-06-02 Cont ID  
Sent By gjohnson Date 2017-06-08 Time 15:07 Rev Time 0.00
Received By fmittner Date 2017-06-02 Time 15:39 Sent To P
Notes
2017-06-02 15:40:08APPROVED PER COA...HARDIE BOARD NOT VINYL SIDING USE.
2017-06-02 10:55:05ROUTED TO FREDERIKE MITTNER

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-05-30 Cont ID  
Sent By fmittner Date 2017-05-30 Time 15:49 Rev Time 0.00
Received By fmittner Date 2017-05-30 Time 15:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-04-28 Cont ID  
Sent By fmittner Date 2017-04-28 Time 14:45 Rev Time 0.00
Received By fmittner Date 2017-04-21 Time 14:14 Sent To B
Notes
2017-04-28 14:44:10FHM MET APPLICANT ON SITE. NO MORE ORIGINAL WOOD SIDING
 REMAINING UNDERNEATH VINYL. APPLICANT TO SUBMIT COA.
2017-04-21 14:25:124/21/2017 - APPLICANT SHOULD SUBMIT A COA FOR THE
 PROPOSED WINDOW REPLACEMENT, ESPECIALLY IF AREAS ARE TO
 BE ENLARGED FOR EGRESS OR REDUCED IN SIZE. APPLICATION
 FOUND HERE: HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERV
 ICES/HISTORIC-PRESERVATION/APPLICATIONS?PAGE=2
 PER PRIOR DISCUSSIONS WITH FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER, THE APPLICANT SHOULD
 REMOVE THE EXISTING VINYL SIDING (WHICH DOES NOT
 CONFORM TO HISTORIC DISTRICT DESIGN GUIDELINES) AND
 REPAIR THE WOOD SIDING UNDERNEATH. QUESTIONS MAY BE
 DIRECTED TO FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER, AT 561.822.1457. DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-08 Cont ID  
Sent By gjohnson Date 2017-06-08 Time 15:07 Rev Time 0.00
Received By gjohnson Date 2017-05-31 Time 10:04 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-30 Cont ID  
Sent By cthroop Date 2017-05-30 Time 15:54 Rev Time 0.00
Received By cthroop Date 2017-05-08 Time 14:18 Sent To  
Notes
2017-05-09 14:19:12R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-03 Cont ID  
Sent By skennedy Date 2017-05-03 Time 16:00 Rev Time 0.00
Received By skennedy Date 2017-04-07 Time 11:02 Sent To  
Notes
2017-04-10 11:02:50R16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-05-03 Cont ID  
Sent By skennedy Date 2017-05-03 Time 16:00 Rev Time 0.00
Received By skennedy Date 2017-05-03 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-08 Cont ID  
Sent By gjohnson Date 2017-06-08 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2017-06-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 09:02 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 17:47 Sent To  
Notes
2017-05-24 09:02:091ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE VENTS THAT WHERE ADDED TO THE WATER CLOSETS AND
 TUBS ON THE GROUND FLOOR ARE HORIZONTAL DRY VENTS WHICH
 ARE NOTE ALLOWED PER FBC PL 905.3 THE WATER CLOSET AND
 TUB COULD CONNECT TOGETHER TO A BRANCH VENTED BY THE
 LAVATORY. PER FBC PL 912.1
  
 2. CLEAN OUTS ARE MISSING ON THE BASE OF THE SOIL
 STACK. PER FBC PL 708.3.4
  
 3. PLEASE PROVIDE MANUFACTURE SPEC SHEETS FOR THE
 TANKLESS WATER HEATERS. PER WPB AMEND TO FBC
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 17:06 Rev Time 0.00
Received By gjohnson Date 2017-04-28 Time 17:06 Sent To  
Notes
2017-04-28 17:14:031ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE TOILETS AND TUBS ON THE FIRST FLOOR NEED TO BE
 VENTED BEFORE THEY CONNECT TO BUILDING DRAIN. PER FBC
 PL 901.2.1
  
 2. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL AND
 WASTE STACKS. PER FBC PL 708.3.4
  
 3. PROVIDE WATER RISER .PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-04-28 Cont ID  
Sent By destabro Date 2017-04-21 Time 14:12 Rev Time 0.00
Received By fmittner Date 2017-04-28 Time 14:44 Sent To HIST
Notes
2017-04-28 14:45:19LANDSCAPE PLAN SUBMITTED.
2017-04-21 14:14:214/21/2017 - BASED ON VALUE OF WORK, APPLICANT SHOULD
 REMOVE THE TOP SHEET OF THE PLANS AND SUBMIT A SEPARATE
 LANDSCAPE PERMIT. ADDITIONALLY, AN IRRIGATION PLAN
 SHOULD BE PROVIDED. PLEASE DIRECT ALL QUESTIONS TO RAY
 CARANCI, LANDSCAPE PLANNER, AT 561.822.1462. DLE